S29386 SQUARE D, S29386 Datasheet - Page 29

SHUNT TRIP KIT

S29386

Manufacturer Part Number
S29386
Description
SHUNT TRIP KIT
Manufacturer
SQUARE D
Series
PowerPactr
Datasheet

Specifications of S29386

Operating Voltage
120VAC
Accessory Type
Shunt Trip Kit
For Use With
H- And J-Frame Thermal Magnetic Circuit Breakers
© 2004–2010 Schneider Electric
All Rights Reserved
Power Distribution Connectors
The power distribution connectors (PDC) can be used for multiple load wire connections on one circuit
breaker. Use in place of standard distribution blocks to save space and time. Field installable kit
includes tin-plated aluminum lug, connectors, and required mounting hardware.
Table 35:
See Table 37 for the phase barriers for PDCs.
For use on load end of circuit breaker only
For use in UL 508 Industrial Control applications only
For use in UL 1995/CSA C22.2 No. 236 heating and cooling equipment
For copper wire only
Frame
H-Frame
H-Frame
J-Frame
J-Frame
Power Distribution Connectors
Kit Number
PDC6HD6
PDC3HD2
PDC6JD4
PDC3JD20
Number of Wires
6
3
6
2
and 1
2
and 1
PowerPact
Section 2—Mounting and Connections
®
Wire Range
8–6 AWG
(10—16 mm
14–10 AWG
(2.5—6 mm
2 AWG
(35 mm
14–3 AWG
(2.5—16 mm
6–4 AWG
(16—25 mm
8 AWG
(10 mm
14–10 AWG
(2.5—6 mm
14–6 AWG Cu
(2.5–16 mm
3–2/0 AWG Cu
(35–70 mm
4–1 AWG Cu
(25–70 mm
3–2/0 AWG Cu
(35–70 mm
H- and J-Frame Circuit Breakers
2
2
)
)
2
2
2
2
2
2
2
2
)
)
)
)
)
2
)
)
)
)
Wire Binding Screw Torque
25 lb-in
(2.8 N•m)
20 lb-in
(2.3 N•m)
40 lb-in
(4.5 N•m)
35 lb-in
(4.0 N•m)
35 lb-in
(4.0 N•m)
25 lb-in
(2.8 N•m)
20 lb-in
(2.3 N•m)
35 lb-in
(4.0 N•m)
50 lb-in
(5.6 N•m)
40 lb-in
(4.5 N•m)
50 lb-in
(5.6 N•m)
06/2010