5760S MK (ELECTRIC), 5760S Datasheet

RCD, 63A

5760S

Manufacturer Part Number
5760S
Description
RCD, 63A
Manufacturer
MK (ELECTRIC)
Series
SENTRYr
Datasheet

Specifications of 5760S

No. Of Poles
2
Voltage Rating Vac
230V
Svhc
No SVHC (18-Jun-2010)
Approval Bodies
BS EN61008, IEE
Cross-section Area Max
35mm2
Current Rating
63A
External Depth
76mm
External Length / Height
81mm
External Width
36mm
TECHNICAL DATA SHEET
Sentry
Residual Current Devices
(RCDs)
1:5
©2001 MK Electric Limited The Arnold Centre, Paycocke Road, Basildon, Essex SS14 3EA, United Kingdom Tel: +44 (0)1268 563720 Fax: +44 (0)1268 563064 email: more@mkelectric.co.uk www.mkelectric.co.uk
PRODUCT RANGE
Rating
Double pole, 2 module
16A, 110V
16A, 110V
16A, 230V
16A, 230V
32A, 110V
32A, 230V
40A, 230V
63A, 230V
63A, 230V
63A, 230V
80A, 230V
80A, 110V
80A, 230V
80A, 230V
100A, 230V
100A, 230V
100A, 230V
Double pole, pulsating d.c.,
fault current sensitive, 2 module
16A, 230V
16A, 230V
32A, 230V
40A, 230V
63A, 230V
Time delayed
80A, 230V
100A, 230V
Four pole, 4 module
25A, 230/400V 30mA
40A, 230/400V 30mA
40A, 230/400V 100mA
63A, 230/400V 30mA
63A, 230/400V 100mA
63A, 230/400V 300mA
Four pole, pulsating d.c.,
fault current sensitive, 4 module
25A, 230/400V 30mA
40A, 230/400V 30mA
Tripping current
10mA
30mA
10mA
30mA
30mA
30mA
30mA
30mA
100mA
300mA
30mA
30mA
300mA
100mA
30mA
100mA
300mA
10mA
30mA
30mA
30mA
30mA
100mA
100mA
List No.
6016s
6416s
6316s
5716s
6032s
6730s
5740s
5760s
6160s
5860s
5780s
6080s
5880s
6180s
7700s
6600s
7800s
6216s
6716s
6630s
5640s
5660s
6980s
6400s
6425s
6440s
6240s
6463s
6363s
6263s
6625s
6640s
Description
The Sentry range of RCDs offers a com-
prehensive selection of devices designed to
meet most residential, commercial and light
industrial requirements.
The range includes two and four pole, a.c.,
d.c. fault current sensitive and time delayed
models and a selection of current ratings
from 16 to 100A is available in a variety of
tripping sensitivities.
When in the OFF position a contact gap of
4mm is present, enabling Sentry RCDs to be
used as isolating switches where appropriate.
Positive indication of the opening of the con-
tacts is only given when the legend ‘OFF-O’
can be seen on the RCD dolly
Features
I
I
I
I
I
Meet BS EN and IEE Wiring Regulation
requirements
Extensive range to suit all specifications
Protect against unwanted tripping
Positive contact status indication
Suitable for most residential,
commercial and light industrial
applications
The operating dolly may be locked in either
the ON or OFF position without affecting the
ability of the trip mechanism to operate,
i.e.the RCD is ‘trip-free’. It is not possible to
hold the contacts closed when a fault
condition exists.
All Sentry RCDs incorporate a filtering device
to provide protection against transient surges
in the supply to the unit, thus reducing the
occurrence of unwanted tripping.
This feature is represented by the symbol
all Sentry RCDs.
I
I
Offer a high degree of protection
against electrocution in accidental
shock hazard situations
Two module, double pole units
available up to 100A
Sentry
®
RCDs
Edition 07-01
on

Related parts for 5760S

5760S Summary of contents

Page 1

... 6316s 16A, 230V 30mA 5716s 32A, 110V 30mA 6032s 32A, 230V 30mA 6730s 40A, 230V 30mA 5740s 63A, 230V 30mA 5760s 63A, 230V 100mA 6160s 63A, 230V 300mA 5860s 80A, 230V 30mA 5780s 80A, 110V 30mA 6080s 80A, 230V 300mA 5880s ...

Page 2

TECHNICAL DATA SHEET Sentry Residual Current Devices (RCDs) 2:5 TECHNICAL SPECIFICATION Electrical Rated making and breaking capacity: Normal (/m) 630A (16 - 63A) and residual (/ m) 800A (80 - 100A) Rated conditional short-circuit current: Normal (/nc) 10,000A and residual ...

Page 3

TECHNICAL DATA SHEET Sentry Residual Current Devices (RCDs) 3:5 ©2001 MK Electric Limited The Arnold Centre, Paycocke Road, Basildon, Essex SS14 3EA, United Kingdom Tel: +44 (0)1268 563720 Fax: +44 (0)1268 563064 email: more@mkelectric.co.uk www.mkelectric.co.uk Normal a.c. waveform Pulsating d.c. ...

Page 4

TECHNICAL DATA SHEET Sentry Residual Current Devices (RCDs) 4:5 ©2001 MK Electric Limited The Arnold Centre, Paycocke Road, Basildon, Essex SS14 3EA, United Kingdom Tel: +44 (0)1268 563720 Fax: +44 (0)1268 563064 email: more@mkelectric.co.uk www.mkelectric.co.uk 3 phase, 3 wire systems ...

Page 5

TECHNICAL DATA SHEET Sentry Residual Current Devices (RCDs) 5:5 ©2001 MK Electric Limited The Arnold Centre, Paycocke Road, Basildon, Essex SS14 3EA, United Kingdom Tel: +44 (0)1268 563720 Fax: +44 (0)1268 563064 email: more@mkelectric.co.uk www.mkelectric.co.uk Dimensions (mm) 36 RCD LN ...