201 15A ETA, 201 15A Datasheet - Page 2

CIRCUIT BREAKER, THERMAL MAG, 1P, 15A

201 15A

Manufacturer Part Number
201 15A
Description
CIRCUIT BREAKER, THERMAL MAG, 1P, 15A
Manufacturer
ETA
Datasheet

Specifications of 201 15A

Actuator Style
Two Button
No. Of Poles
1
Current Rating
15A
Voltage Rating Vdc
65V
Voltage Rating Vac
250V
Mounting Type
DIN Rail
Length/height, External
80mm
Voltage Ac
250V
External Depth
64mm
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
2
120
Type 201 0.05...7 A
1)
2)
Dimensions
Internal connection diagram
Typical time/current characteristics
10000
Magnetic tripping currents are increased by 20% on DC supplies.
Magnetic tripping currents are decreased by 20% on AC supplies.
.472-.551
0.001
1000
12-14
0.01
100
0.1
10
1
symmetrical rail EN 50022-35x7.5
current rating in A
Phillips screw, size 2 to EN ISO 4757
+140 °F
+60 °C
1
2
… times rated current
4 6 8 10
Thermal-Magnetic Circuit Breaker 201/-WA
+73.4 °F
1.77
+23 °C
45
3.15
80
20
.335
ø8.5
AC/DC
40
line 1
60 80100
I >
2
1)
black
white
-30 °C
-22 °F
.453
11.5
slot for fitting labels from
Weidmüller
type dekafix
Phoenix
type ZBFM5 or ZB8
.492
12.5
Type 201 8...16 A
10000
0.001
1000
0.01
100
conductor cross
section max.
0.5 - 10 mm
(AWG 20-AWG 8)
rigid conductor
0.5 - 6 mm
(AWG 20-AWG 10)
flexible conductor
tightening torque
max. 0.8 Nm
0.1
10
1
www.e-t-a.com
1
2
2
2
… times rated current
4 6 8 10
This is a metric design and millimeter dimensions take precedence ( mm )
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section 9
– Technical information.
Ambient temperature °F
Derating factor
Installation drawing
mounting area
20
cable entry
AC/DC
40
60 80100
1)
°C
-22
-30
0.76 0.79 0.83 0.88
Type 201-WA
10000
0.001
1000
0.01
100
0.1
-4
-20
10
1
1
+14 +32 +73.4 +104 +122 +140
-10
2
0
0.05...10 A
… times rated current
4 6 8 10
+23
1
cable entry
operating area
(reinforced insulation)
inch
+40 +50
1.08 1.16 1.24
20
DC/AC
05/06
40
60 80100
(020505)
+60
2)