JDL36250 SQUARE D, JDL36250 Datasheet - Page 6

CIRCUIT BREAKER, THERMAL MAG, 3P, 250A

JDL36250

Manufacturer Part Number
JDL36250
Description
CIRCUIT BREAKER, THERMAL MAG, 3P, 250A
Manufacturer
SQUARE D
Series
PowerPactr
Type
Standardr
Datasheets

Specifications of JDL36250

Actuator Style
Toggle
No. Of Poles
3
Current Rating
250A
Voltage Rating Vdc
250V
Voltage Rating Vac
600V
Mounting Type
DIN Rail
Terminals
Lug
Actuator Type
Handle
Brand/series
JD Series
Characteristic
Adjustable Trip
Current, Rating
250 A
Dimensions
7.52 (H) × 4.12 (W) × 5.00 (D) in.
Frame Type
J
Number Of Poles
3
Terminal Type
Line: Lug - Load: Lug
Voltage Rating
600/250 VAC/DC
Weight
5.00 lbs.
Wire Size
#3/0-350 AWG/kcmil (Al/Cu)
Ampere Interrupting Ratings
25 k @ 240 VAC, 18k @ 480 VAC
Standards
UL489, CSA, NOM, IEC 60947, CE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
6
PowerPact
Section 1—General Information
06/2010
®
H- and J-Frame Circuit Breakers
Dual-Break Rotating Contacts
All PowerPact
that reduce the amount of peak current during a short circuit fault. This reduces the let-through
currents and enhances equipment protection.
Reduced Let-Through Currents
The moving contact has the shape of an elongated “S” and rotates around an
floating axis. The shape of the fixed and moving contacts are such that the
repelling forces appear as soon as the circuit reaches approximately 15 times I
Due to the rotating movement, repulsion is rapid and the device greatly limits
short-circuit currents, whatever the interrupting level of the unit (D, G, J or L). The
fault current is extinguished before it can fully develop. Lower let-through currents
provide less peak energy, reducing the required bus bar bracing, lowering
enclosure pressure, and delivering improved series or combination ratings. See
page 13 for UL Current Limiting labels.
Internal Operating Mechanism
H-frame and J-frame circuit breakers have an over-center toggle
mechanism providing quick-make, quick-break operation. The operating
mechanism is also trip-free, which allows tripping even when the circuit
breaker handle is held in the “ON” position.
Internal cross-bars provide common opening and closing of all poles with a
single operating handle.
All H-frame and J-frame circuit breakers have an integral push-to-trip
button in the cover to manually trip the circuit breaker. This should be used
as part of a regular preventive maintenance program.
Handle Position Indication
The H-frame and J-frame circuit breaker handle can assume any of three positions, ON, tripped or
OFF as shown. The center tripped position provides positive visual indication that the circuit breaker
has tripped.
The circuit breaker can be reset by first pushing the handle to the extreme “OFF” position. Power can
then be restored to the load by pushing the handle to the “ON” position.
®
H-frame and J-frame circuit breakers are equipped with dual-break rotating contacts
ON
OFF
Tripped
© 2004–2010 Schneider Electric
n
.
All Rights Reserved
Push-to-Trip