S201MC4 ABB, S201MC4 Datasheet
S201MC4
Specifications of S201MC4
Related parts for S201MC4
S201MC4 Summary of contents
Page 1
Technical data System ® pro M compact Navigate Document System pro M compact Miniature circuit-breakers S 200/S 200 M Residual-current-operated circuit-breakers F 200 Cross wiring/accessories 1 ...
Page 2
... Form 2327) in their then applicable version. For foreign business, the Standard Terms for Delivery of Products and Services of the Electrical Industry (ABB Form 2293 German- English, or ABB Form 2294 German- French) shall apply in connection with the Standard Sales Terms (ABB-Form 2381 English) in their then applicable version. ...
Page 3
System pro M compact ® Prior to connection of aluminium conductors ensure that their contact points are cleaned, brushed and coated with grease. Miniature circuit-breakers Residual-current-operated circuit breaker Busbars Contents The technology of S 200 ...
Page 4
System pro M compact ® 0052 0051 Outstanding features Applications All round protection against contact with live parts in acordance with DIN VDE 106 part 100. Due to new design: Upper ...
Page 5
System pro M compact ® Outstanding features Applications New quick-fastening technique for easy disconnection of the device from the assembly. No time-consuming extra work: Cross-wiring remains with the assembly. To remove the device, just loosen the screw, lift the device ...
Page 6
Miniature circuit-breakers System The offer at a glance pro M compact ® Description Trip charcteristics The MCBs of the S 200/S 200 M series have a cur- rent-limiting effect. They have two different trip releases acting on the contact mechanism ...
Page 7
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Technical data Specifications: No. of poles: tripping charcteristics: rated current rated voltage max. operating voltage U : Bmax min. operating voltage U ...
Page 8
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Internal resistance and power loss of the miniature circuit-breakers Internal resistance per pole power loss per pole in W type rated device series current B, ...
Page 9
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Tripping characteristics acc. to tripping characteristic and rated current B DIN VDE 0641 0 0 ...
Page 10
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Short circuit selectivity: In the case of a short circuit, selectivity exists up to the values indicated. MCBs short circuit discrimination main circuit breaker S ...
Page 11
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Tripping diagrams Reading example for tripping characte- ristic of the B-type trip characteristics (in connection with the table tripping characteristics on page 9, line B) a Thermal tripping ...
Page 12
... Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Pulse tripping of the MCBs S 200/S 200 M made by ABB-STOTZ-KONTAKT Example: S 201-B16 non-tripping current hold hold I = 201.6 A hold In the case of an impulse of 600 , S 201-B16 maintains current of 201 non-tripping current (electromagnetic release) B-type characteristic = ...
Page 13
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Diagrams of let-through values I Miniature circuit-breakers S 200 B/ request min. pre-arcing e. max. let-through ...
Page 14
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® The influence of ambient temperature and interdependencies in the case of even loads on the load The influence of ambient temperature and interdependencies in the case of even ...
Page 15
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Use of S 200/S 200 M miniature circuit-breakers in direct current circuits 60 VDC/125 VDC In DC systems VDC or, as the case may be, ...
Page 16
Miniature circuit-breakers System S 200/S 200 M series pro M compact ® Installation and operation instructions Installation Can be installed in any mounting position due to snap-on fixing to DIN rails EN 60 715 width MCB ...
Page 17
Supplementary devices System pro M compact ® Additional devices Mounting additional devices Additional devices are always fitted from the right hand side: – signal contact/auxiliary switch S2C-S/H6R for MCBs and RCCBS – auxiliary switch S2C-H6R for MCBs – shunt release ...
Page 18
Supplementary devices System pro M compact ® Installation: 1. Mounting one S2C-S/H6R RCCB or MCB must be in the ON position switch in ON position if fitted to MCB, remove bottom (RCD), if fitted to RCCB middle (MCB) coupling pin ...
Page 19
Supplementary devices System pro M compact ® Technical Data Signal contact/auxiliary switch S2C-S/H6R and auxiliary switch S2C – H6R according to EN 62019 rated current I U 400 V 230 V e min. rated voltage ...
Page 20
Residual-current-operated circuit breaker System F 200 series pro M compact ® Description Residual-current protective devices have a balance or, as the case may be, differential current transformer as measuring device that is connected with permanent magnet trip via the secondary ...
Page 21
Residual-current-operated circuit-breakers System F 200 series/FS 201 pro M compact ® Technical data specifications: No. of poles: tripping characteristics: rated current rated residual current tripping range at at tripping time at 1 · I ...
Page 22
Residual-current-operated circuit-breakers System F 200 series/FS 201 pro M compact ® Installation and operation instructions Installation Can be installed in any mounting position due to snap-on fixing to DIN rails EN 50 022 width RCD F ...
Page 23
Residual-current-operated circuit-breakers System F 200 series/FS 201 pro M compact ® Test of protective measure Except for the operating test, the effectiveness of the protection provided within the installation must be tested according to the applicable codes of practice. For ...
Page 24
Busbars for System series S 200, S 200 M, F 200, FS 201 pro M compact ® Description The newly developed pro M compact cross wiring busbar system includes everything that is needed for secure and economic connections of distribution ...
Page 25
Miniature circuit-breakers S 200/S 200 M System Residual-current-operated circuit breakers F 200/FS 201 pro M compact ® Dimensions Dimensions 1-pole S 201, S 202, S 203, S 204 2-pole F 202, F 204, F 204 S FS 201 S 201 ...
Page 26
Accessories System ® Dimensions pro M compact Terminal covers PCD 2 N PCD 0136 Z 96 Enclosure of moulded-plastic QES 4/3 N Flush frame max. No. of modules type dim module = 17.5 mm) S ...
Page 27
Busbars System Dimensions pro M compact ® Dimensions PS 1/2 PS 1/6 PS 1/9 PS 1/12 PS 3/60 auxiliary contact bridge HKB measurements 3/6 PS 3/9 PS 3/ ...
Page 28
Busbars System Dimensions pro M compact ® Dimensions PS 2/12 PS 2/58 PS 2/ measurements 3/ 4/12 PS 4/ 3/12 E 463 ...
Page 29
Miniature circuit-breakers System S 200 series pro M compact ® Selection table D No. of poles 1 6000 3 U Bmax 440 ... 2 U Bmax 440 V 125 V ... 3 U Bmax 440 V 4 ...
Page 30
Miniature circuit-breakers System S 200 series M pro M compact ® Selection table B No. of poles 1 10000 3 U Bmax 440 ... 2 U Bmax 440 V 125 V ... 3 U Bmax 440 V ...
Page 31
Miniature circuit-breakers System S 200 series M pro M compact ® Selection table B No. of poles 10000 With disconnecting neutral Bmax 440 ... Bmax 440 V ...
Page 32
Miniature circuit-breakers System S 200 series M pro M compact ® Selection table C No. of poles 1 10000 3 U Bmax 440 ... 2 U Bmax 440 V 125 V ... 3 U Bmax 440 V ...
Page 33
Miniature circuit-breakers System S 200 series M pro M compact ® Selection table C No. of poles 10000 With disconnecting neutral Bmax 440 ... Attention: S 200 M, ...
Page 34
RCCBs and RCBOs System and their fields of applications pro M compact ® Areas of application In apartments 32 A Socket-outlets Outdoor lightning installations Fire protection in high-risk or high-danger areas Rooms with bath tub or ...
Page 35
... A 0.01…0 201 B 6…40/0, 16/0,03 approved submitted for aproval/planed to be submitted Approved variants on request Approval not required ABB STOTZ-KONTAKT GmbH P.O. Box 10 16 80, 69006 Heidelberg, Germany Eppelheimer Straße 82, 69123 Heidelberg, Germany Telephone: +49 ( 701- 0 Fax: +49 ( 701-723 www.abb.de/stotz-kontakt 52 EL. CSA KEMA Ö ...