DAH4002B HOFFMAN ENCLOSURES, DAH4002B Datasheet

ELECTRIC HEATER, 400W, 0°F-100°F, 230V

DAH4002B

Manufacturer Part Number
DAH4002B
Description
ELECTRIC HEATER, 400W, 0°F-100°F, 230V
Manufacturer
HOFFMAN ENCLOSURES
Datasheet

Specifications of DAH4002B

Voltage Rating Vac
230V
Output Power
400W
External Height - Metric
190mm
External Width - Metric
108mm
External Depth - Metric
132mm
Frequency Max
60Hz
Frequency Min
50Hz
Current Rating
1.7A
External Depth
132mm
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Spec-00051
E P H (763) 422-2211
FX (763) 422-2600
Thermal Management
Heaters
Electric Heater
Heaters
Industry Standards
CSA Certified, CSA File No. LR42186
CE
Application
Protect mechanical, electrical and electronic equipment from low
temperatures, condensation and corrosion with this thermostatically
controlled, fan-driven heater that maintains a stable enclosure
temperature.
Fan draws cool air from the bottom of the enclosure and passes this
air across the thermostat and heating elements before being released
into enclosure cavity. Heated air is discharged through the top of the
heater unit.
Standard Product 
Subject to change without notice
Catalog Number
DAH1001A
DAH1002A
DAH2001A
DAH2002A
DAH4001B
DAH4002B
DAH8001B
DAH8002B
UL 508A Component Recognized; File No. E61997
Watts
100
100
200
200
400
400
800
800
115
230
115
230
115
230
Voltage
115
230
PH (763) 422-2211 • FX (763) 422-2600 • hoffmanonline.com
Hz
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
Amps
0.98
0.49
1.89
0.95
3.72
1.86
7.37
3.69
Specifications
• Aluminum housing
• Thermostat range adjustable from 0 F to 100 F (-18 C to 38 C)
• Four 10-32 x self-tapping screws are included with each heater
• Ball bearing fan
• Terminal strip with clamp connector that accepts both solid and
Finish
Brushed aluminum
Bulletin: D85
These electric heaters are not designed for use in dusty,
dirty, corrosive, or hazardous locations. Portions of the
heater can get hot. Adequate protection must be taken
to protect people from potential burns, and to protect
other components from this heat. Ho man recommends
this heater only be installed in a totally-enclosed metal
enclosure.
Heat sensitive components should not be placed near the
heater discharge area since this air can be quite warm.
The clearance range de nes the space that must be kept
free of these components for proper and safe operation
of the heater.
Heaters
stranded wire
DO NOT INSTALL HEATERS ON WOOD PANELS.
X
in./mm
4.00
102
4.00
102
6.00
152
6.00
152
6.00
152
6.00
152
8.00
203
8.00
203
CAUTION
Weight (lbs.)
4.00
4.00
4.00
4.00
6.00
6.00
6.00
6.00
© 2009 Hoffman Enclosures Inc.
Spec-00051 E
Weight (kg)
1.81
1.81
1.81
1.81
2.72
2.72
2.72
2.72
1

DAH4002B Summary of contents

Page 1

... DAH1002A 100 230 DAH2001A 200 115 DAH2002A 200 230 DAH4001B 400 115 DAH4002B 400 230 DAH8001B 800 115 DAH8002B 800 230 Subject to change without notice PH (763) 422-2211 • FX (763) 422-2600 • hoffmanonline.com Heaters CAUTION These electric heaters are not designed for use in dusty, dirty, corrosive, or hazardous locations ...

Page 2

... Subject to change without notice Heaters PH (763) 422-2211 • FX (763) 422-2600 • hoffmanonline.com © 2009 Hoffman Enclosures Inc. Spec-00051 E ...