MBX 300 POLESET Fluke, MBX 300 POLESET Datasheet
MBX 300 POLESET
Specifications of MBX 300 POLESET
MBX 300 POLESET Summary of contents
Page 1
... Capable of simultaneously logging up to 500 parameters for days and capturing events, the Fluke 1740 Series helps uncover intermittent and hard-to-find power quality issues. The included PQ Log software quickly assesses the quality of power at the service entrance, substation the load, according to the latest EN50160 standard ...
Page 2
... VA, VAR, PF, energy, flicker, voltage events, and THD Measurement of voltage and current harmonics to the 50th, unbalance, and mains signaling Dust/water resistance Display UPS ride-through Dimensions (HxWxD) Fluke Corporation 1740 Series Three-Phase Power Quality Loggers Memobox Plug and play All three 1740 Series loggers feature easy plug and play setup, for immediate use. The current probes are connected to the logger with a single plug. The instrument automatically detects, scales, and pow- ers the probes using line power from the measured voltages. All accessories are individually calibrated and can be shared with multiple Fluke 1740 series loggers ...
Page 3
... Calculates current harmonics Fluke 1745 and Fluke 1744 loggers can calculate the limits of current harmonics to predict overload of the grid according to the standards VSE, VEOE, VDN, among others. This powerful predictive main- tenance feature enables current harmonics to be observed before a distortion appears in the voltage. View graphs and generate reports with Fluke PQ Log software With its easy-to-use interface, the included PQ Log software assists you with logger setup, enables you to verify actual measurement values quickly using the online function, and downloads data from the logger to a connected PC operating on standard Windows operating systems. You can ® ...
Page 4
... Storage temperature range Reference temperature range Relative humidity Housing Environmental protection Safety Type test voltage EMC Emission Immunity 4 Fluke Corporation 1740 Series Three-Phase Power Quality Loggers Memobox Refers to the reference conditions and is guaranteed for two years years years recommended developed, designed, and manufactured according to DIN ISO 9001 3 °C ± °F ± 30 V ± ± 0 ± 0.1 Hz phase sequence L1, L, L3 interval length: 10 minutes Wye connection (L1, L Power supply -10 ° ...
Page 5
... Connection Current input for clamp Input ranges I ( Intrinsic uncertainty Max. overload Input resistance Current transformer Ration selection Power configurations 5 Fluke Corporation 1740 Series Three-Phase Power Quality Loggers Memobox max 480 V ac max 830 job programming P 3-phase ≤ 999 kV with PTs and ratio App. 80 kΩ per chan. Lx-N Single phase ( connected): app. 300 kΩ Ratio: < ...
Page 6
... Dimensions Weight Measurement A/D converter Anti-aliasing filter Frequency response Interval length Averaging time for Min/max values Time base 6 Fluke Corporation 1740 Series Three-Phase Power Quality Loggers Memobox 660 V absolute, 50 Hz/60 Hz 100 V to 350 V dc Internal fuse: 630 Watts Fluke 1745: Internal battery for typ. > 5 hours ride through with intelligent power management Fluke 1743/44: 3 sec Capacitor Power supply fuse can be replaced in service facility only. Supply can be connected in parallel to measuring inputs (up to 660 V) LEDs for status and voltage levels Fluke 1745: LC-display with backlight for voltage, current, active power, phase sequence ...
Page 7
... MBX CLAMP 3-phase+N current clamps with 1 A/ ranges 1 A/ cable MBX CLAMP 3-phase+N current clamps with 5 A/ ranges 5 A/ cable MBX CLAMP 3-phase+N current clamps with 0 A/ ranges 0 A/ cable Misc accessories MBX 300 POLESET Pole mounting kit for 1743 and 1744 C435 Water-tight hard case with rollers Fluke 1744/43 All instruments include • 4 Flexible probes 15/150/1500/3000 A with m cable • PQ Log software • RS3 interface cable and RS3-USB adapter • ...