DLRO200-115 Megger, DLRO200-115 Datasheet - Page 2

DIGITAL LOW RESISTANCE OHMMETER, 1OHM

DLRO200-115

Manufacturer Part Number
DLRO200-115
Description
DIGITAL LOW RESISTANCE OHMMETER, 1OHM
Manufacturer
Megger
Datasheet

Specifications of DLRO200-115

Resolution (ohm)
0.1µohm
Test Current
200A
Accuracy
Voltage
External Height
410mm
External Width
250mm
External Depth
270mm
Weight
32lb
Lead Free Status / RoHS Status
na
Lead Free Status / RoHS Status
na
SPECIFICATIONS
Measurement:
Range: 0.1 µΩ to 999.9 mΩ
(Subject to supply voltage and leads used)
Accuracy:
Current Lead Resistance (Megger supplied leads)
2 x 16 ft (5 m) 25 mm
2 x 16 ft (5 m) 50 mm
2 x 33 ft (10 m) 70 mm
2 x 49 ft (15 m) 95 mm
Maximum Continuous Test Time
More than 10 minutes at 200 A @ 68° F (20º C) ambient.
Power Supply
for full output (additional smoothed):
will start. To repeat a test, simply break contact with the
voltage probes and remake contact.
Measuring individual joints in a busbar is a good example of
the convenience to be gained by using AUTO mode. The
two current leads are connected to the ends of the busbar.
They will remain connected there until all tests have been
completed. When the voltage leads make contact across a
joint, the DLRO200-115 detects that all four leads are
connected, carries out a test and stops. When you move to
the next joint the DLRO200-115 detects the already
completed circuit automatically and carries out the next test,
and so on until all joints have been tested. The results may
be stored automatically and may be recalled to the display
or downloaded for review.
UK
Archcliffe Road, Dover
CT17 9EN England
T +44 (0) 1 304 502101
F +44 (0) 1 304 207342
UKsales@megger.com
Item (Qty)
DLRO200-115 High Current Digital Low Resistance Ohmmeter
115 V (English QWERTY keyboard)
Included Accessories
16 ft. (5 m) Lead set comprising 2 x 25 mm
current leads with clips and 2 potential
leads with clips
Download Manager
User Guide on CD-ROM
RS232 download cable
Quick Start Guide (English)
Voltage:
Current:
Resistance: Better than 1% from
100 to 130 V 50/60 HZ with a load
less than 11 mΩ including current leads
±0.5% ± 0.1 mV
±0.5% ± 0.1 A
100 µΩ to 100 mΩ
2
2
2
2
current leads
current leads
current leads
current leads
UNITED STATES
4271 Bronze Way
Dallas, TX 75237-1019 USA
T 1 800 723 2861 (USA only)
T +1 214 333 3201
F +1 214 331 7399
USsales@megger.com
8 mΩ
4 mΩ
5.4 mΩ
6 mΩ
2
ORDERING INFORMATION
DLRO200-115 E
Cat No.
25955-025
6220-787
6111-442
6172-763
6172-782
OTHER TECHNICAL SALES OFFICES
Täby SWEDEN, Norristown USA,
Sydney AUSTRALIA, Toronto CANADA,
Trappes FRANCE, Kingdom of
BAHRAIN, Mumbai INDIA,
Johannesburg SOUTH AFRICA, and
Chonburi THAILAND
Item (Qty)
Optional Accessories at extra cost
16 ft. (5m) Lead set in bag comprising:
2 x 50mm
2 x potential leads with clips
49 ft. (15m) Lead set comprising 2 x 95 mm
current leads with clamps and
2 x potential leads with clips
33 ft. (10m) Lead set comprising 2 x 70 mm
current leads with clamps and
2 x potential leads with clips
Transport case
Test Modes:
Test Time:
Display:
Warnings
Data Transfer
Storage Capacity:
Memo field:
Test Current
Range:
Accuracy:
Voltmeter input
impedance:
Hum rejection:
Temperature
Operation:
Storage:
Calibration:
Co-efficient:
Max. Humidity: 95% RH non-condensing
Maxi Altitude:
Safety:
EMC:
Dimensions:
Weight:
2
current leads with clamps and
Manual, Auto, Continuous.
10 seconds NORMAL /AUTO mode.
Refreshed every 2 seconds in CONTINUOUS
mode
Large, high resolution backlit liquid crystal
display
Current flowing: - LED. Other warnings are
shown on the lcd display.
Real time or batch download via RS232
using Download Manager.
300 result sets and memo, battery backed
for 10 years.
160 characters max.
Filtered direct current; 10 A to 200 A d.c.
±2% ±2 A
>200 kΩ
5 V rms 50 Hz/60 Hz
14 to +122º F (-10 to +50º C)
-13 to 149º F (-25 to +65º C)
68° F (20º C)
<0.05% per º C
6562 ft. (2000 m)
IEC61010 – (1995)
EN61326 annex A (heavy industrial)
16.4 x 9.84 x 10.63 in.
(410 x 250 x 270 mm)
31.97 lbs. (14.5 kg) excluding test leads
Digital Low Resistance Ohmmeter
Registered to ISO 9001:2000 Reg no. Q 09290
Registered to ISO 14001 Reg no. EMS 61597
DLRO200-115_DS_en_V04
www.megger.com
Megger is a registered trademark
2
2
DLRO 200-115
6220-755
6220-757
6220-756
Cat No.
MC996