... Progressive Innovative Solutions • Lifetime Warranty • Unique Terminal Block • Innovative Fusing Method • Patented Design HPS I mperator Encapsulated Machine Tool Industrial Control Transformers ® ...
Page 2
... Control Transformer ompany Hammond Power Solutions (HPS) was established in 1917 in Guelph, Ontario and has grown from a small family owned business in the short wave radio market, to the industry leader in magnetic transformer design and manufacturing. HPS has 6 manufacturing facilities and currently has 10 regional distribution centers throughout North America ...
Page 3
A pplications • Automation • Panel Shops • Machines • Panel Boards • Solenoids • Control Applications • Timers Performance Value Quality I ndustries • Paper Mills • Printing • Automotive • Packaging Systems • Process Automation S Q uperior ...
Page 4
... F & B eatures • 600V class, machine tool rated industrial control transformers • 11 standard multi primary and secondary voltage groups available • 50/60 Hertz (60Hz on PH***AJ & PH***AR) • VA range from 1500 1 • Superior insulation system • 50-150VA, temperature rise 55°C, insulation class 105°C • ...
Page 5
Terminal connection numbers molded into terminal block and correspond to nameplate and wiring diagrams, make connecting the HPS Imperator quick and simple. Innovative terminal block design provides for easy hook-up and installation of fuse clips. Optional removable finger safe terminal ...
Page 6
... PH1000AJ B 8.33/4.17 1500 PH1500AJ B 12.5/6.25 Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers. Please refer to page 14 for dimensional drawings. Special voltages and VA sizes available upon request. Group B Primary Voltage: 600 11 Secondary Voltage: ...
Page 7
... Mtg. Output Rating Number Fig. Amps PH50MQMJ 50 A 0.42/0.21 PH75MQMJ 75 A 0.63/0.31 100 PH100MQMJ A 0.83/0.42 150 PH150MQMJ B 1.25/0.63 250 PH250MQMJ B 2.08/1.04 350 PH350MQMJ B 2.92/1.46 PH500MQMJ 500 B 4.17/2.08 PH750MQMJ 750 B 6.25/3.13 1000 PH1000MQMJ B 8.33/4.17 1500 PH1500MQMJ B 12.5/6.25 Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers. ...
Page 8
... B 8.33/4.17 1500 PH1500PP B 12.5/6.25 Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers. Please refer to page 14 for dimensional drawings. Special voltages and VA sizes available upon request. Visit our website: www.hammondpowersolutions.com 7 Overall Mounting Mounting ...
Page 9
... PH1000PG C 83.3/41.7 Secondary fuse clips and fuse clip mounting screws supplied standard with transformers up to and including 500VA. Primary and secondary voltage links/jumpers supplied standard with transformers. Please refer to page 14 for dimensional drawings. Special voltages and VA sizes available upon request. Group H ...
Page 10
... C 8.70/41.67 5.25 Secondary fuse clips and fuse clip mounting screws supplied standard with transformers up to and including 500VA. Primary and secondary voltage links/jumpers supplied standard with transformers. Please refer to page 14 for dimensional drawings. Special voltages and VA sizes available upon request. Group J ...
Page 11
... Standard Secondary Fuse Kits All HPS Imperator control transformers are supplied with standard secondary fuse kits which include: 13/32” 1/2” midget/type CC fuse clips, fuse clip mounting screws, primary and secondary voltage links and the PHAK1 instruction sheet (note: secondary fuse clips and fuse clip mounting screws not supplied on the PH750PG, PH1000PG, PH750MLI and PH1000MLI) ...
Page 12
... Secondary fuse clips are not included or available on these units. Note: All factory installed fuse kits are pre-wired at the transformers highest primary voltage and the lowest secondary voltage. To hook different primary or secondary voltage, please refer to the wiring instruction sheet included with the transformer. ...
Page 13
Sample Accessory Drawings Fuse Clips Voltage Link (for 50, 75 and 100VA) Sample Accessory Assembly Drawings Sample Assembly Drawing for Voltage Link Installation Sample Assembly Drawing for Finger Guard Installation (for 50, 75 and 100VA) Fuse Clips Fused & Unfused ...
Page 14
Overcurrent Protection Secondary The overcurrent protection listed below, in amperes, is 125% of the rated current of the transformer. Choose the next higher fuse rating if these numbers do not correspond with standard fuse selections. Sec. Voltage ...
Page 15
Dimensional Drawings Some actual transformer units may differ from dimensional drawings shown below. FIGURE A (100 VA and less FIGURE For PH750PG, PH1000PG, PH750MLI & PH1000MLI FIGURE B (150 VA to ...
Page 16
... Southgate Drive Guelph, Ontario N1G 3W6 Tel: (519) 822-2441 Fax: (519) 822-9701 Toll Free in Canada: 1-888-798-8882 USA Hammond Power Solutions, Inc. 1100 Lake Street Baraboo, Wisconsin 53913-2866 Tel: (608) 356-3921 Fax: (608) 355-7623 Toll Free in the United States: 1-866-705-4684 www.hammondpowersolutions.com Literature No ...