490NAD91105 SQUARE D, 490NAD91105 Datasheet - Page 14

PROFIBUS PLC CONNECTOR, RECEPTACLE, 9POS

490NAD91105

Manufacturer Part Number
490NAD91105
Description
PROFIBUS PLC CONNECTOR, RECEPTACLE, 9POS
Manufacturer
SQUARE D
Series
NADr
Datasheet

Specifications of 490NAD91105

Connector Type
PLC
Gender
Plug
No. Of Contacts
9
Connector Mounting
Cable
For Use With
Square D Advantys STB Distributed I/OSystem
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Selection guide
Applications
Bus or network type
Bus or network nature
Structure
Medium
Configuration
NIM (Network Interface
Module) features
Services used
Type of NIM module
Pages
14
Physical interface
Data rate
Number of devices
(1)
Maximum length
Number of I/O modules per
Advantys STB island (1)
Power supply
Logic power supply
CANopen devices supported
Standard
Basic (3)
Advantys
Solution
Network Interface Modules
(1) One Advantys STB island corresponds to 1 device on the bus or the network.
(2) Depending on the nature of the CANopen devices, this maximum number may be limited to 7.
(3) Does not support: the CANopen bus extension module, hot swapping, Advantys software.
Data exchange between master PLC and Advantys STB I/O modules
Ethernet TCP/IP Network
Industrial LAN
10 BASE-T
10 Mbit/s
Shielded dual twisted pair via Ethernet
ConneXium
Up to 256 per segment,
unlimited with switches
100 m (109.3 yd) according to 802.3 standard
1000 m (1093.6 yd) with ConneXium
system
> 3000 m (3280.8 yd) with fiber optic
connection
Standard NIM: up to 32 modules on 1 primary
segment and up to 6 extension segments
c 24 V not isolated (19.2…30 V)
Provides c 5 V logic power to all the I/O modules of an island (1200 mA)
Up to 12 devices (2)
- Embedded Web (configuration, diagnostics,
and access to variables)
- TCP/IP Modbus
- SNMP agent
- DHCP client service
STB NIP 2212
20
cabling system
STB Distributed I/O
cabling
CANopen bus
CAN field bus
ISO 1198
10 Kbit/s…1 Mbit/s depending on bus length
Shielded dual twisted pair
127 slaves
From 30 m (32.8 yd) (1 Mbit/s) to 5,000 m
(5468.0 yd) (10 Kbit/s)
Standard NIM: up to 32 modules on 1 primary
segment and up to 6 extension segments
Basic NIM: up to 12 modules on 1 primary
segment
- Process Data Object (PDO)
- Service Data Object (SDO)
- Network management (NMT)
STB NCO 2212
STB NCO 1010
0