369306 WALTHER, 369306 Datasheet - Page 3

SOCKET, FREE, 230V, 63A, 2P+E WAY

369306

Manufacturer Part Number
369306
Description
SOCKET, FREE, 230V, 63A, 2P+E WAY
Manufacturer
WALTHER
Datasheets

Specifications of 369306

Gender
Receptacle
Voltage Rating
230V
Current Rating
63A
Connector Mounting
Cable Mount
Colour
Blue
Connector Mounting Orientation
Cable
Contact Material
Brass
Contact Plating
Nickel
Ip/nema
RoHS Compliant
Connector Body Material
Nylon 6
Rohs Compliant
Yes
Contact Termination
Screw
iec309final.indd 19
ELECTRICAL
Insulation Resistance
Per IEC 309-1, Clause 19
Dielectric Strength
Per IEC 309-1, Clause 19
Norm. Operation, Connect
& Disconnect Cycles
Per IEC 309-1, Clause 21
Breaking Capacity
Per IEC 309-1, Clause 20
Temperature Rise
Per IEC 309-1, Clause 22
MECHANICAL
Cable Secureness
Per IEC 309, Clause 23
Impact
Per IEC 309, Clause 24
ENVIRONMENTAL
Flammability
Ambient Temperature
Range
Moisture Resistance
UV Resistance
We declare, under our sole responsibility, the conformity of the following
products and standards:
This declaration of conformity is according to the EC regulations 73/23,
91/368 and 89/336 (Low Voltage Directive), module A, in consideration of
DIN EN 45 014.
IEC 309 PIN & SLEEVE DEVICES
IEC 309 PIN & SLEEVE DEVICES
WALTHER WERKE, Ferdinand Walther GmbH
Plugs and Sockets (Pin and Sleeve devices)
DECLARATION OF CONFORMITY
DIN EN 60 309, T. 1
DIN EN 60 309, T. 2
Ramsener Strasse 6
67304 Eisenberg
Exposed plastic materials are UV stabilized.
highest point of the device being 5cm (2”)
Splashproof (IP44): Device is sprayed with
24 hours in water at a temp. of 25°C, the
afterwards subjected to splashing water in
Maximum 50 K rise at full rated current.
Watertight (IP67): Device immersed for
voltage and 125% of the rated current.
Tested at 110 % of the rated operating
water for 10 minutes and immediately
A device is wired with a 2.25m length
500V for 1 min. Resistance ≥ 5M Ω
height of 75 cm, 8 times. The device
of flexible cord and dropped from a
is then tested for applicable degrees
of protection against moisture.
Minimum: -25°C with impact
Per IEC 309-1, Clause 27
below the water level.
all directions (360°).
Self-extinguishing
3000V for 1 min.
Maximum: 90°C
See Table 1
See Table 2
PERFORMANCE SPECIFICATIONS
PERFORMANCE SPECIFICATIONS
DIN EN ISO 9001
TABLE 1
The test sequence is conducted by using a no-load, followed by a load
sequence.
TABLE 2
The flexible cord or cable is twisted and pulled. Values for the applied
twisting torque and force of pull are shown in Table 2. In all cases the cord
displacement is less than 2mm.
Amperes
Amperes
Device
Device
Rating
Rating
125
125
16
32
63
16
32
63
Connect and Disconnect Cycles
5000 p.f of 0.6
1000 p.f of 0.6
1000 p.f of 0.6
250 p.f of 0.7
Load at Rated
Current and
Cycles with
Voltage
Cable Secureness Test
Force
100
120
200
80
N
Minimum test requirements
Certificate Registration No. 4678-01
INTERNATIONAL RATINGS
INTERNATIONAL RATINGS
No-Load
Torque
Cycles
0.350
0.425
1000
1000
N•m
250
0.8
1.5
0
Displacement
Alternating
Alternating
Alternating
Maximum
Sequence
mm
2
2
2
2
19
-
19
10/15/2008 9:53:56 am

Related parts for 369306