04280 LEGRAND, 04280 Datasheet

PLUG, DIN, RAIL, 10-16A, 2P+E WAY

04280

Manufacturer Part Number
04280
Description
PLUG, DIN, RAIL, 10-16A, 2P+E WAY
Manufacturer
LEGRAND
Datasheet

Specifications of 04280

Gender
Plug
Voltage Rating
250V
Current Rating
16A
Connector Mounting
DIN Rail
Contact Termination
Screw
Connector Mounting Orientation
DIN Rail
Contact Material
Copper Alloy
87045 LIMOGES Cedex
Telephone: +33 5 55 06 87 87 - Fax: +33 5 55 06 88 88
1. RANGE
10/16 A - 250 V±
- 2 P + E with safety shutters
- 2 P + E with safety shutters and tamperproof for protected or
specialized circuits
- 2 P + E German standard
2. DIMENSIONS
3. ELECTRICAL CHARACTERISTICS
• Thermal current: 10/16 A
• Rated voltage 250 V
• Overvoltage category 1.2/50 s: 4 kV±
• Dielectric strength: 2 kV±
4. REFERENCE STANDARDS
IEC 884-1
NF C 61-303
5. MECHANICAL CHARACTERISTICS
• Environmental conditions
Storage temperature: - 10 °C to + 70 °C
Operating temperature: - 5 °C to + 40 °C
• Mechanical resistance: IP xx3
44,5
042 80
44
66
60
Technical sheet: FA243A
Power sockets
Cat. No(s): 042 80/82/85
5. MECHANICAL CHARACTERISTICS
• Materials
6. INSTALLATION
• Wiring
Conductors permitted
Flexible with end caps
Rigid
Tools required:
Flat blade screwdriver
Posidrive screwdriver
Tightening torque
Min.
Max.
Recommended
Cage terminals, with combined Posidrive, releasable and captive
screws
Protection against direct contact: IP 2x
Slot on the top of the socket to allow the busbar to pass through
Busbar connection possible. For phase and neutral, connection from
the bottom
042 82
Contacts
Casing
Screw
Polycarbonate
Zinc bichromate finish steel
1.5 to 10 mm
ø 4 to 5.5 mm
Nickel-plated copper
1.5 to 6 mm
Incandescent wire
Bending module
0.8 Nm
1.8 Nm
1.2 Nm
Oxygen index
Pz 1
Density
Colour
Date: 27.11.97
042 85
(continued)
2
2
Grey RAL 7035
960 °C / 30 s
1.18 to 1.25
> 2.20 GPa
34
1

04280 Summary of contents

Page 1

LIMOGES Cedex Telephone: + Fax: + 042 80 1. RANGE 10/ 250 V± with safety shutters - ...

Page 2

Power sockets Cat. No(s): 042 80/82/85 6. INSTALLATION (continued) • Mounting - Mounted on symmetrical rail EN 50-022 - Releasing the claws 2) push the claw downwards 1) Lift up with a screwdriver - On a plate (perforated or not) ...

Related keywords