94768 3M, 94768 Datasheet - Page 2

TERM FORK INSUL 22-18AWG #6

94768

Manufacturer Part Number
94768
Description
TERM FORK INSUL 22-18AWG #6
Manufacturer
3M
Series
Highland™r
Datasheet

Specifications of 94768

Terminal Type
Standard
Stud/tab Size
6 Stud
Width - Outer Edges
0.340" (8.64mm)
Length - Overall
0.890" (22.61mm)
Mounting Type
Free Hanging (In-Line)
Termination
Crimp
Wire Gauge
18-22 AWG
Insulation
Insulated
Features
Butted Seam
Color
Red
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
054007-94768
31-6-NB
5400794768
54007947684
80611252687
94768-01
Installation Information
UL Listed and CSA Certified for use on stranded copper
(AWG) wire only.
Strip away the end 3/8 inch of wire insulation.
Make the crimp in the proper station of a recommended
3M crimp tool: TH-440, TH-450 (scissor style), or TR-482,
TR-490 (ratchet style) hand tools.
Electrical Products Division
6801 River Place Blvd.
Austin, TX 78726-9000
http://www.3M.com/elpd
3M is a trademark of 3M.
IMPORTANT NOTICE
Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability
associated with such use.
Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture as of the date of purchase.
3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be,
at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will
not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential
regardless of the legal theory asserted.
WARNING
Turn power off before installing or removing terminal. All electrical
work should be done according to appropriate electrical codes.
is a trademark of Underwriters Laboratories.
is a trademark of Canadian Standards Association.
Barrel Crimp (Electrical)
Insulation Crimp (Mechanical)
Engineering Specification
Crimp-type terminals shall, electrically and mechani-
cally, connect to a pre-stripped end of a stranded cop-
per wire and have a flat tongue portion with a central
opening for mounting around a screw or stud.
The terminal line shall offer tongue variations in hole
(stud) size (6, 8 10, etc.) and configuration (ring, fork,
block fork, flanged block fork, locking fork, etc.): and
barrel variations in wire (AWG) size (26-24*, 22-18,
16-14, 12-10, etc.) and construction (non-insulated
brazed seam, vinyl insulated butted seam, nylon insu-
lated with insulation grip, etc.). The terminal line shall
have regulatory agency coverage (UL Listing, CSA
Certification). The terminal tongue shall be marked
with the wire range and manufacturer’s symbol ( ).
The nylon-insulated, standard fork terminal with insu-
lation grip shall be tin-plated, annealed copper, with
the tongue having a specified stud slot (size 0 thru 10)
and a butted seam barrel with a tin plated brass, funnel
entry insulation grip, covered by a molded nylon
sleeve, color coded and sized for a specified (AWG)
wire range (26-24*, 22-18, 16-14, 12-10).
Insulated terminals shall be UL Listed and CSA
Certified for 600 Volts maximum building wire: 1000
Volts maximum in signs, fixtures and luminaires and
have a maximum operating temperature of 221°F
(105°C).
*Not UL Listed or CSA Certified.
© 3M 2002 78-8126-0868-1-A