Specifications of FN 256-160-28

Current Rating (max)
160A
Voltage Rating Max
480VAC
Termination
Screw
Mounting Style
Flange
Operating Temp Range
-25C to 100C
Product Depth (mm)
260mm
Lead Free Status / RoHS Status
Compliant
Technical specifications
Maximum continuous operating voltage:
Operating frequency:
Rated currents:
High potential test voltage:
Protection category:
Overload capability:
Temperature range (operation and storage):
Flammability corresponding to:
Design corresponding to:
MTBF @ 50°C/400V (Mil-HB-217F):
Features and benefits
Compact general purpose
three-phase and neutral line EMC fi lter
FN 256 filters are designed specifically for
applications involving asymmetric loads,
ranging from industrial controls to medical
electronics systems. These typically involve
insufficiently filtered converters and
switch-mode power supplies on different
phases, causing current imbalance and
significant interference problems.
Employing single-stage filter circuits for
each phase and the neutral line, FN 256 fil-
ters provide high attenuation of both sym-
metrical and asymmetrical interference.
3x 480/277VAC
dc to 60Hz
8 to 160A @ 50°C
P –> E 2650VDC for 2 sec
P –> P 2100VDC for 2 sec
IP20
IP00 (filters with connectors -28)
4x rated current at switch on,
1.5x rated current for 1 minute, once per hour
-25°C to +100°C (25/100/21)
UL 94V-2 or better
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
600,000 hours
Three-phase and neutral line filter for
general purpose four-wire filtering
Compact space-saving design
Choice of connection style
Low operating leakage current
Used as a mains input filter, FN 256 filters
also increase conducted immunity and
thus contribute to overall system reliability.
Choice of connection style as well as filter
ratings in line with common fuse values
support a fast and easy application-specific
filter selection and deployment.
A light weight aluminium housing with a
small footprint ensures that the filters can
be easily accommodated on control panels
and in tight power cabinets.
3-phase + neutral line fi lters
FN 256
Approvals
Typical electrical schematic
L1
L2
L3
N
E
Typical applications
Line
General purpose four-wire filtering
High-power office equipment
Power supplies
UPS
Medical applications
Electrical cabinets
Control panels
Cx
Cy
L
R
R1
Load
L1‘
L2‘
L3‘
N‘
E

Related parts for FN 256-160-28

FN 256-160-28 Summary of contents

Page 1

... UL 94V-2 or better UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939 600,000 hours Used as a mains input filter, FN 256 filters ■ also increase conducted immunity and thus contribute to overall system reliability. Choice of connection style as well as filter ■ ...

Page 2

... Components > FN 256 Filter selection table Filter* Rated current @ 50°C (40°C) [A] FN 256-8-46 8 (8.8) FN 256-16-46 16 (17.5) FN 256-25-47 25 (27) FN 256-36-47 36 (39) FN 256-64-52 64 (70) FN 256-80-.. 80 (88) FN 256-120-.. 120 (131) FN 256-160-.. 160 (175 compile a complete part number, please replace the -.. with the required I/O connection style. ...

Page 3

... Components > FN 256 Mechanical data 8 to 64A types 80 to 160A types (-34, -35, -40) Dimensions 8A 16A A 120 120 B 143 143 115 115 127.5 127.5 G 6.5 6 All dimensions in mm; 1 inch = 25.4mm Tolerances according: ISO 2768 22768-m Filter input/output connector cross sections -28 (M10) -34 Solid wire ...

Related keywords