HAC1 Crydom Co., HAC1 Datasheet - Page 7

SWITCH EXTERNAL AUXILIARY CNTCT

HAC1

Manufacturer Part Number
HAC1
Description
SWITCH EXTERNAL AUXILIARY CNTCT
Manufacturer
Crydom Co.
Datasheets

Specifications of HAC1

Relay Terminals
Quick Connect
Contact Current Ac Max
5A
Contact Voltage Ac Max
600V
No. Of Poles
1
Contact Configuration
SPDT-1NO / 1NC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
3RHP Series Solid State Contactor
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
HAC16WT
Manufacturer:
GRAYHILL
Quantity:
20 000
Output: The Crydom 3RHP 3 Phase Hybrid Solid State Contactor is available for either 40 or
50 amps rms load current @ 280 or 600 VAC 3 Phase operation, 50/60 Hz and includes internal
over temperature protection. See Figure 8 for typical application wiring.
rated load (see Figures 9, 10 & 11 for wiring).
General Specifications: Operating temperature of the 3RHP series is from -20
shown in Figure 6, output derating occurs above 65
operations/min. @ 50% duty cycle. Life expectancy is > 2 million operations @ full rated load
current. Isolation input to output is 4000 VAC.
Mechanical dimensions of the 3RHP are presented in Figure 7. Notice that the footprint is
identical to the industry standard three pole/three-phase Definite Purpose Contactors.
Safety Agency approvals/ratings: CE certified, UL and cUL recognized, UL 508 100K cycle
overload endurance tested.
The 3RHP can also be operated on single phase 120 or 240 VAC, 50/60 Hz supplies at full
Figure 6a - Derating for 3RHP 40A.
Crydom Inc.
2320 Paseo de las Americas, Suite 201
San Diego, CA, 92154
Tel: (619) 210-1550
Fax: (619) 710-8544
E-Mail: sales@crydom.com
Web: www.crydom.com
o
Figure 6b - Derating for 3RHP 50A.
C ambient. Max operating frequency is 30
o
to 75
o
C. As
7