ATV11HU05F1A SQUARE D, ATV11HU05F1A Datasheet - Page 2

no-image

ATV11HU05F1A

Manufacturer Part Number
ATV11HU05F1A
Description
SD DRIVE 115V 1PH .25HP/.18KW VFD ATV11A
Manufacturer
SQUARE D
Datasheet
Complementary
Product destination
Supply voltage limits
Network frequency limits
Speed drive output frequency
Nominal switching frequency
Speed range
Transient overtorque
Regulation loop
Motor slip compensation
Prospective line Isc
Output voltage
Insulation
Analogue input number
Discrete input number
2
Discrete input logic
Discrete output type
Minimum switching cur-
rent
Maximum switching
current
Protection type
Frequency resolution
Electromagnetic com-
patibility
Motor cable length
Vibration resistance
Shock resistance
Relative humidity
Ambient air tempera-
ture for operation
Operating altitude
Asynchronous motors
85...130 V
47.5...63 Hz
0...200 Hz
4 kHz
1...20
150...170 % of nominal motor torque
Adjustable frequency
Factory-set with the speed loop stability and gain
Possible correction for machines with high resistive torque/inertia/fast cycles
Adjustable
Preset in factory
1 kA
<= 2 x power supply voltage
Electrical between power and control
1
4
Logic input not wired LI1...LI4 < 5 V
Negative logic (source) LI1...LI4 > 11 V
Positive logic (source) LI1...LI4 < 5 V > 11 V
Assignable as external voltage DO 30 V max, 30 mA
Assignable as internal voltage DO
Assignable as open collector logic output DO 100
Ohm, 50 mA max
Factory set as PWM open collector output DO at 2
kHz 10 mA max
Protected relay logic RA-RC 1 NO
10 mA 24 V DC RA-RC
2 A 250 V AC inductive cos phi = 0.4 7 ms RA-RC
2 A 30 V DC inductive cos phi = 0.4 7 ms RA-RC
5 A 250 V AC resistive cos phi = 1 0 ms RA-RC
5 A 30 V DC resistive cos phi = 1 0 ms RA-RC
Line supply overvoltage drive
Line supply undervoltage drive
Overcurrent between output phases and earth (on
power up only) drive
Overheating protection drive
Short-circuit between motor phases drive
Thermal protection motor
0.1 Hz display unit
Converter A/D, 10 bits analog input
1.2/50 μs - 8/20 μs surge immunity test level 3 EN/
IEC 61000-4-5
Electrical fast transient/burst immunity test level 4
EN/IEC 61000-4-4
Electrostatic discharge immunity test level 3 EN/IEC
61000-4-2
Radiated radio-frequency electromagnetic field im-
munity test level 3 EN/IEC 61000-4-3
5 m with additional EMC filter from 2 to 16 kHz EN
55011 class B
20 m with additional EMC filter from 2 to 16 kHz EN
55011 class A group 1
1 gn 13...200 Hz EN/IEC 60068-2-6
1.5 mm peak to peak 3...13 Hz EN/IEC 60068-2-6
15 gn 11 ms EN/IEC 60068-2-27
5...93 % without condensation IEC 60068-2-3
5...93 % without dripping water IEC 60068-2-3
-10...40 °C without derating
-10...50 °C by removing the protective cover from
the top of the drive
≤ 60 °C with current derating of 2.2 % per °C above
50 °C
> 1000 m with current derating 1 % per 100 m
≤ 1000 m without derating

Related parts for ATV11HU05F1A