... Typical applications: high current or high inrush power supplies, commercial and industrial. • RoHS compliant. Model Number Structure ■ Model Number Legend Relay with Auxiliary Contact Block G7Z Relay Contact Configuration 4A: 4PST-NO 3A1B: 3PST-NO/SPST-NC 2A2B: DPST-NO/DPST-NC 2. Contact Configuration of Auxiliary Contacts ...
Page 2
... VA 9,680 VA switching capacity NC 11,000 VA 4,400 VA Minimum load VDC Note: The ratings for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block. G7Z 330 Power Relays ■ Accessories (Order Separately) Auxiliary Contact Block ...
Page 3
... The insulation resistance was measured with a 1,000-VDC megohmmeter applied to the same places as those used for checking the dielectric strength. 5. The electrical endurance was measured at an ambient temperature of 23°C. 6. The specifications for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block. Classification Relay (See note 6.) Model G7Z-4A-@Z, G7Z-3A1B-@Z, G7Z-2A2B-@Z 100 mΩ ...
Page 4
... CSA Certification by G7Z 332 Power Relays EN Standard/TÜV Certification: EN 60947-4-1 (Certification No. R50079155) Number of test Model Coil ratings operations G7Z 12, 24 VDC NO contact AC- 440 V, 50/60 Hz 80,000 100,000 100,000 NC contact AC- 440 V, 50/60 Hz 100,000 G73Z — NO contact AC15: 0.5 A, 440 V, 50/ contact DC13: 0.5 A, 110 V ...
Page 5
... Connections ■ Terminal Arrangement/Internal Connections Relay with Auxiliary Contact Block Note: non-polarized coil. G7Z-4A-20Z G7Z-4A-11Z G7Z-3A1B-20Z G7Z-3A1B-11Z G7Z-2A2B-20Z G7Z-2A2B-11Z Auxiliary Contact Block G73Z-20Z G73Z-11Z G7Z-4A-02Z G7Z-3A1B-02Z G7Z-2A2B-02Z G73Z-02Z G7Z 333 Power Relays ...
Page 6
... Note: The dimensions are typical values. Auxiliary Contact Block 32.2 24 Note: The dimensions are typical values. DIN Track Mounting Height (when using the PFP-100N or PFP-50N mounting rail) 15 96.3 75.0 64.3 Note: The dimensions are typical values. G7Z 334 Power Relays 45 Four, M3.5 47 Eight Two ...
Page 7
... OFF. The hot surface may cause burn injury. ■ Precautions for Correct Use Installation • Mount the G7Z with the coil terminal at the top. Up Coil terminal • Do not use the Relay with the terminal screw surfaces facing down. ...
Page 8
... Allow suitable slack on leads when wiring, and do not subject the terminals to excessive force. Microloads The G7Z is used for switching power loads, such as current carry for device power supplies and heater loads. Use an auxiliary contact block (G73Z) if microloads are required for signal applications and operation status feedback ...
Page 9
... Amendment: These Terms constitute the entire agreement between Buyer and Seller relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. 5. Severability: If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision. Power Relays G7Z ...
Page 10
... E. Commerce Drive, Suite B Schaumburg, IL 60173 847-882-2288 06/09 Cat. No. X301-E-1 G7Z Power Relays 2. Programmable Products. Seller shall not be responsible for the user's pro- gramming of a programmable product, or any consequence thereof. 3. Performance Data. Performance data given in this publication is provided as a guide for the user in determining suitability and does not constitute a war- ranty ...