C200HW-BI101-V1 Omron, C200HW-BI101-V1 Datasheet

no-image

C200HW-BI101-V1

Manufacturer Part Number
C200HW-BI101-V1
Description
BACKPLANE, 10 SLOT, I/O EXP
Manufacturer
Omron
Datasheet

Specifications of C200HW-BI101-V1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Programmable Controllers
C200HX-CPUjj-E/-ZE
C200HG-CPUjj-E/-ZE
C200HE-CPUjj-E/-ZE

Related parts for C200HW-BI101-V1

C200HW-BI101-V1 Summary of contents

Page 1

Programmable Controllers C200HX-CPUjj-E/-ZE C200HG-CPUjj-E/-ZE C200HE-CPUjj-E/-ZE ...

Page 2

C200HX-CPUjj-E/-ZE C200HG-CPUjj-E/-ZE C200HE-CPUjj-E/-ZE Programmable Controllers Installation Guide Revised June 2003 ...

Page 3

iv ...

Page 4

... OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice ...

Page 5

vi ...

Page 6

TABLE OF CONTENTS PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Intended Audience ...

Page 7

...

Page 8

About this Manual: This manual describes the installation of C200HX, C200HG, and C200HE Programmable Controllers, and it includes the sections described below. Programming and operating information is provided in the C200HX/C200HG/C200HE Operation Manual. Please read this manual completely and be ...

Page 9

... Buyer's purchase order or other documents which are inconsistent with addition to, these Terms. Please contact your Omron representative to confirm any additional terms for sales from your Omron company. 2. Prices. All prices stated are current, subject to change without notice by Seller ...

Page 10

This section provides general precautions for using the Programmable Controller (PC) and related devices. The information contained in this section is important for the safe and reliable application of the PC. You must read this section and understand the information ...

Page 11

... This manual provides information for programming and operating OMRON PCs. Be sure to read this manual before attempting to use the software and keep this manual close at hand for reference during operation ...

Page 12

... The loose screws may result in burning or malfunction. Caution When using the C200HW-PA209R Power Supply Unit with an 8-slot or 10-slot ! CPU Backplane or Expansion I/O Backplane, be sure to use only Backplanes with “-V1” at the end of the model number. Using an 8-slot or 10-slot Backplane without “ ...

Page 13

... Mounting or dismounting I/O Units, CPU Units, Memory Cassettes, Power Supply Units, or any other Units. • Assembling the Units. • Setting DIP switches or rotary switches. • Connecting cables or wiring the system. • Connecting or disconnecting the connectors. event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes ...

Page 14

... EC Directives. When incorporated into a device, however, the C200HX/HG may not satisfy this Standard due to the noise produced by the con- tact output when it switches on and off. In such a case, it will be necessary to take countermeasures such as connecting a surge or arc killer, or providing an external means of protection for the PC. The countermeasures taken to satisfy the Standard vary depending on the load devices, wiring, machinery configuration, etc ...

Page 15

Conformance to EC Directives Criteria for Taking Countermeasures (Refer to EN50081-2 for details.) Countermeasures are not required if the frequency of load switching for the whole system with the PC included is less than 5 times per minute. Countermeasures are ...

Page 16

This section provides general information about Programmable Controllers (PCs) and how they fit into a Control System. 1-1 What is a Control System? 1-2 The Role of the ...

Page 17

... It may include everything from a process control computer, if one is used, to the factory computer, down through the PCs (and there may be many of them networked together) and then on down through the network to the control com- ponents: the switches, stepping motors, solenoids, and sensors which monitor and control the mechanical operations. PC ...

Page 18

... Servomotor driver control Power source DC Servomotor Driver DC Servomotor In the typical Control System example shown above controls the move- ment of the workpiece bed across two horizontal axes using Limit Switches and Servomotors to monitor and control movement. Input Unit PC Hand-held Programming Console Power ...

Page 19

... A PC can output to a myriad of devices for use in automated control. Almost any- thing that you can think of could be controlled (perhaps indirectly PC. Some of the most common devices are motors, Solenoids, Servomotors, Stepping Motors, valves, switches, indicator lights, buzzers, and alarms. Some of these output devices; such as the motors, Solenoids, Servomotors, Stepping Motors, 4 ...

Page 20

... The PC continually scans the program in its memory to achieve this control. Block Diagram of PC Signals from switches, sensors, etc. A program for your applications must be designed, and stored in the PC. This program is then executed as part of the cycle of internal operations of the PC. ...

Page 21

How Does a PC Work? Cycle When a PC operates, that is, when it executes its program to control an external system, a series of operations are performed inside the PC. These internal operations can be broadly classified into the ...

Page 22

How Does a PC Work? Flowchart of CPU Operation NO Sets error flags and turns ON or flashes indicator ALARM/ERROR ALARM (Flashing) ERROR (Solid ON) Power application Clears IR area and resets all timers Checks I/O Unit connections Resets watchdog ...

Page 23

...

Page 24

This section describes the system configuration used for the C200HX/C200HG/C200HE PCs and the individual Units used in the system configuration. 2-1 Basic Configuration . . . . . . . . . . . . . . . . . ...

Page 25

Basic Configuration 2-1 Basic Configuration The basic configuration of the PC is shown below. With the C200HX/ C200HG/C200HE two three Expansion I/O Racks (depending on the CPU Unit) can be connected to the CPU Rack, ...

Page 26

... The Power Supply Unit supplies power to the CPU Rack. The Power Supply Units listed in the following table are available. Refer to 2-2-4 Power Supply Units for further details. Note The C200HW-PA204R/PA209R cannot be used with all combinations of CPU Units and Backplanes. Refer to page 23, Restrictions for the C200HW-PA204R/ PA209R, for details. ...

Page 27

... CPU Rack. The following CPU Backplanes are available depending on the number of slot required for Units. Refer to 2-2-5 Backplanes for further details. Note When using the C200HW-PA209R Power Supply Unit with an 8-slot or 10-slot CPU Backplane or Expansion I/O Backplane, be sure to use the C200HW- BC081-V1 or C200HW-BC101-V1. ...

Page 28

... Supply voltage C200HW-PA204 100 to 120 VAC, 200 200 to 240 VAC 240 VAC C200HW-PA204S C200HW-PD204R C200HW-PD209R C200HW-PD024 24 VDC Model Number of slots C200HW-BI031 3 C200HW-BI051 5 C200HW-BI081-V1 8 C200HW-BI101-V1 10 Section 2-1 Power Supply Unit I/O Backplane Remarks , --- Provides 24-VDC output terminals. Equipped with RUN q pp output contacts. 13 ...

Page 29

Units 2-1-3 I/O Connecting Cable The first Expansion I/O Rack is connected to the CPU Rack, and the second and third Expansion I/O Racks are connected to the previous Expansion I/O Rack through I/O Connecting Cable. There are five different ...

Page 30

Units 1, 2, 3... 1. Indicators The indicators (LEDs) on the front cover of the CPU Unit operate as described in the following table. LED RUN (green) Lights when the PC is operating normally in MONITOR or RUN mode. ERR ...

Page 31

Units Pin no. Setting 1 ON Writing disabled for user memory. OFF Writing enabled for user memory Contents of the Memory Cassette automatically read when power is turned on. OFF Contents of the Memory Cassette not automatically read ...

Page 32

... I/O data can be directly read and written. There is no need for a backup power supply. The Memory Cassette can also be removed from the CPU Unit and used for storing data. Note The C200HW-ME64K can be used with the C200HX-CPU65-ZE/CPU85-ZE CPU Units only. It cannot be used with other CPU Units. EPROM Memory Cassette With an EPROM Memory Cassette, the program is written using a PROM Writer ...

Page 33

... RS-422/485 port x 1 C200HW-COM04-EV1 Connection port for SYSMAC LINK, SYSMAC NET, or other Communications Units. RS-232C port x 1 (supports protocol macros) C200HW-COM05-EV1 RS-232C port x 2 (supports protocol macros) C200HW-COM06-EV1 RS-422/485 port x 1 (supports protocol macros) RS-232C port x 1 (supports protocol macros) Section 2-2 ...

Page 34

... Units Note Use either the C200HW-COM01 Communications Board for the ZE-ver- sion C200HX/HG/HE CPU Units. Indicators (LEDs) The Communications Board indicators on the front panel of the CPU Unit indi- cate the status of the Board, as described in the following table. 2-2-4 Power Supply Units Power Supply Units provide power to the CPU Rack and the Expansion I/O Racks ...

Page 35

... A (Select the voltage using voltage using Without the metal short bar on short bar on the voltage 5 VDC Without selector 45 W terminals.) 24 VDC 5 VDC, 4.6 A, Without 30 W Section 2-2 RUN output Model Without C200HW-PA204 Without C200HW-PA204S With C200HW-PA204R With C200HW-PA209R Without C200HW-PD024 ...

Page 36

... Voltage Selector Terminals (C200HW-PA20jj Only) Short these terminals with a metal short bar when 100 to 120 VAC is being supplied to the AC input terminals Ground the LG terminal to 100 Ω or less to increase resistance to noise and protect against possible electrical shock ...

Page 37

... The combined power consumption for both 5 V and 24 V must less Input (C200HW-PD024 Only) Supply 24 VDC to the DC input terminals. 7. RUN Output (C200HW-PA204R/PA209R Only) The internal contact will turn ON when the CPU Unit is operating in RUN or MONITOR mode. These terminals are available only on the C200HW- PA204R. Section 2-2 ...

Page 38

... Month ( Jan to Sep, X/Y/Z = Oct/Nov/Dec Day (01 to 31) Section 2-2 Manufacturing number (See below.) Made in the Netherlands 0147 or later Manufacturing number (See below.) Made in the Netherlands 0147 or later I/O Backplanes C200HW-BI031 Same manufacturing manufacturing number as for C200HW-BI051 C200HW-PA204R. C200HW-BI081-V1 (-V1 or later) C200HW-BI101-V1 (-V1 or later) 23 ...

Page 39

Units 2-2-5 Backplanes There are two types of Backplane: the CPU Backplane, used for the CPU Rack, and the I/O Backplane, used for Expansion I/O Racks. The Backplane serves to hold and connect the following types of Unit: the CPU ...

Page 40

... Model number DC Input Unit p C200H-ID211 C200H-ID212 AC Input Unit C200H-IA121 C200H-IA122/IA122V C200H-IA221 C200H-IA222/IA222V AC/DC Input Unit C200H-IM211 C200H-IM212 Note The C200H-ID001/002 cannot be used on the following Backplanes: C200HW- BCjj1/BIjj1. Output Units Name Model number Contact Output Unit C200H-OC221 C200H-OC222 C200H-OC225 C200H-OC223 C200H-OC224 C200H-OC222N C200H-OC226N ...

Page 41

Units Components The Standard I/O Units come in three shapes; A-shape, B-shape, and E-shape. Refer to Appendix D Specifications for the dimensions of each Unit. The num- bers in the diagram correspond to the numbers of the following items in ...

Page 42

Units 1, 2, 3... Units with 10-terminal Terminal Blocks Units with 19-terminal Terminal Blocks 2-2-7 Group-2 High-density I/O Units Group-2 High-density I/O Units come in two varieties; C-shape and D-shape. The shape of the two varieties is the same, but ...

Page 43

Units C-shape Units (32-point Units) D-shape Units (64-point Units) 28 Unit Specifications DC Input Unit 12 VDC; 64 pts 24 VDC; 32 pts 24 VDC; 64 pts Transistor Output Unit 4.5 VDC, 26.4 VDC,100 mA; 32 pts 4.5 ...

Page 44

Units 1, 2, 3... I/O Indicators Units with One 40-pin Connector Units with Two 40-pin Connectors 1. I/O Unit Lock Notch The lock notch fits into the Backplane to hold the Unit in place. 2. Nameplate The nameplate shows the ...

Page 45

Units 2-2-8 High-density I/O Units Classified as Special I/O Units Some High-density I/O Units are classified as Special I/O Units Special I/O Units can be connected depending on the CPU ...

Page 46

Peripheral Devices 2-3 Peripheral Devices There are various Peripheral Devices that can be use to support C200HX/ C200HG/C200HE operation. These Peripheral Devices are introduced in this section. 2-3-1 Programming Consoles There are two Programming Consoles that can be used with ...

Page 47

Peripheral Devices 2-3-2 CX-Programmer The CX-Programmer is a Programming Device that runs on Windows used for full-scale programming operations. Use the following Connecting Cables to connect the computer running the CX-Programmer with the C200HX/HG/ HE(-Z) PCs. Connecting Cables ...

Page 48

... ≤ ≤ Other Units can be added until the total number of Units reaches ten Link Units are used, the number of Units including the PC Link Units must not exceed ten. Section 2 Position Control Units (C200H-NC211, C200HW-NC413) Motion Control Units 2 units max. 33 ...

Page 49

Expanded System Configurations The C200H-MD501, C200H-MD115, and C200H-MD215 can each be set for 128 dynamic input points (64 points x two circuits) and the C200H-OD501 and C200H-OD215 can each be set for 128 dynamic output points (64 points x two ...

Page 50

Expanded System Configurations Analog I/O Units The Analog Input (A/D) Units retrieve analog inputs and the Analog Output (D/A) Unit sends analog outputs. The following Analog I/O Units are available: C200H-AD001 with 4-point analog input, C200H-AD002 with 8-point analog input, ...

Page 51

Expanded System Configurations Voice Unit Voice messages can be input from dynamic microphones or cassette tape recorders and output from loudspeakers or headsets via the Voice Unit. The Voice Unit incorporates a sentence function and word combination function, either of ...

Page 52

Expanded System Configurations Fuzzy Logic Unit The C200H-FZ001 Fuzzy Logic Unit incorporates a high-functional fuzzy Logic processor and allows high-speed fuzzy logic. A personal computer can be connected to the Fuzzy Logic Unit via RS-232C cables for software development and ...

Page 53

Expanded System Configurations Cam Positioner Unit A single C200H-CP114 Cam Positioner Unit is as powerful as 48 mechanical cams because it can complete jobs that normally require 48 mechanical cams possible to set 16-point external output and 32-point ...

Page 54

Expanded System Configurations PID Control Unit The PID Control Unit scales inputs from connected sensors and then carries out PID control according to preset control mode. Select the control output of the PID Control Unit from the following. Model C200H-PID01 ...

Page 55

... SYSMAC LINK Systems. 40 SYSMAC LINK Unit C200HW-SLK13/SLK14 (optical) C200HW-SLK23/SLK24 (coaxial cable) SYSMAC-series PC and/or DM Areas. the NETWORK READ (RECV(98)) and NETWORK WRITE (SEND(90)) instructions in the user program. format. C200HW-CE001 or C200HW-CE002 Bus Connection Unit are required to use a SYSMAC LINK Unit. Section 2-4 CPU Unit ...

Page 56

... FA computer format. ming the NETWORK READ (RECV(98)) and NETWORK WRITE (SEND(90)) instructions in the user program. and/ words of data in other data areas. C200HW-CE001 or C200HW-CE002 Bus Connection Unit are required to use a SYSMAC NET Link Unit. Section 2-4 CPU Unit Line server Central power supply ...

Page 57

Expanded System Configurations Host Link Systems A maximum of two Host Link Units can be mounted to slots in either the CPU Rack or an Expansion I/O Rack. The following Host Link Units are available: C200H-LK101-PV1 (optical cable) C200H-LK201-PV1 (RS-232C) ...

Page 58

Expanded System Configurations CompoBus/S Systems The CompoBus high-speed I/O data communications system designed to meet the needs of time-critical FA applications. • The CompoBus/S Master Unit is mounted to the CPU Rack or an Expansion Number of Mountable ...

Page 59

Expanded System Configurations DeviceNet Systems The DeviceNet is an I/O data communications system conforming to the Device- Net standard being developed to standardize device-level networks for FA. • The DeviceNet Master Unit is mounted to the CPU Rack or an ...

Page 60

Expanded System Configurations Remote I/O Systems A maximum of two Optical or Wired Remote I/O Master Units can be mounted to slots in either the CPU Rack or an Expansion I/O Rack. A maximum total of five Slave Racks, each ...

Page 61

... The data link words can be either set automati- cally or that can be set manually to more efficiently meet the needs of specific applications using Controller Link Support Software. nection Unit (C200HW-CE001/CE002/CE012) are required to mount a Con- troller Link Unit to a C200HX/HG/HE PC. Section 2-4 ...

Page 62

... Up to two type I or type II cards can be mounted, or one type III card can be mounted, enabling applications of standard SRAM, ATA, flash memory, and other PC cards. nection Unit (C200HW-CE001/CE002/CE012) are required to mount a PC Card Unit to a C200HX/HG/HE PC. Section 2-4 PC Card Unit Ethernet Set ...

Page 63

...

Page 64

This section describes how to install a PC System, including mounting the various Units and wiring the System. Be sure to follow the instructions carefully during installing. Improper installation can cause the PC to malfunction, resulting in extremely dangerous situations. ...

Page 65

Installation Environment 3-1 Installation Environment This section details the necessary environmental conditions for installing the PC. Proper installation procedures and a proper environment are essential to getting the best performance and reliability from your PC. Caution Static electricity can damage ...

Page 66

Installation Environment Cooling Fan A cooling fan is not always necessary, but may be needed in some installations. Try to avoid mounting the warm area or over a source of heat. A cooling fan is needed if ...

Page 67

... Units that run along the sides of the Racks, keeping the wires from becoming entangled. This figure illustrates the correct way to mount the Racks. Note When using the C200HW-PA209R Power Supply Unit at an ambient tempera- ture exceeding 50°C, in order to improve air circulation, ensure that there is a ...

Page 68

... Allow sufficient clearance in the control panel in which the PC is mounted min min min min. 118 to 153* mm Approx. 180 to 223* mm Note: Figures marked with an asterisk are for when the C200HW-PA209R is mounted. Section 3-1 Ducts, etc. C200HW-PA209R Ducts, etc. C200HW-PA209R Ducts, etc. 53 ...

Page 69

... Units and Backplanes. Refer to page 23, Restrictions for the C200HW-PA204R/ PA209R, for details. 54 A±0.2 CPU Backplane I/O Backplane W Model CPU Backplane p C200HW-BC031 C200HW-BC051 C200HW-BC081-V1 C200HW-BC101-V1 I/O Backplane p C200HW-BI031 C200HW-BI051 C200HW-BI081-V1 C200HW-BI101-V1 Section 3-1 7 118±0 120 118±0 246 mm 260 mm 316 mm 330 mm 421 mm 435 mm 491 mm 505 mm 175 mm 189 mm ...

Page 70

... For 3 slots C200H-ATT31 For 5 slots C200H-ATT51 For 8 slots C200H-ATT81 For 10 slots C200H-ATTA1 Specifications p Model For 3 slots C200HW-ATT32 For 5 slots C200HW-ATT52 For 8 slots C200HW-ATT82 For 10 slots C200HW-ATTA2 Section 3-1 5-dia. holes for mounting Base Insulation Plate (4/6 places) (B) 12 dia. 5 dia (A) (E) Dimensions (mm ...

Page 71

Installation Environment DIN Track Mounting Bracket The DIN Track Mounting Bracket shown below is necessary for mounting the PC to the DIN Track. DIN Track The following DIN Tracks are available. Procedure 1, 2, 3... DIN Track Mounting Bracket 56 ...

Page 72

Installation Environment 2. Mount the Backplane to the DIN Track so that the claws on the Mounting Brackets fit into the upper portion of the DIN Track as shown below. Backplane 3. Loosen the screws attaching the Mounting Brackets to ...

Page 73

Installation Environment 3-1-6 Mounting Units to the Backplane The CPU Unit of the C200HX/C200HG/C200HE has no I/O points built in. In order to complete the necessary to mount at least one or more I/O Units to the ...

Page 74

Installation Environment CPU Units, I/O Power Supply Units and Slave Units must have the screws on the bottom tightened with a Phillips screwdriver. The screwdriver must be held at a slight angle sure to leave enough space below ...

Page 75

Installation Environment 3-1-7 I/O Connecting Cables Each Rack must be mounted vertically, that is with the printing on the front pan- els oriented as it would normally be read. The Racks should be mounted one above the other with the ...

Page 76

Installation Environment 3-1-8 Mounting Memory Cassettes Use the following procedure to mount a Memory Cassette. Caution Be careful to always turn the power off before inserting or removing a Memory ! Cassette Memory Cassette is inserted into or ...

Page 77

Installation Environment 3-1-9 Mounting a Communications Board Caution Be careful to always turn the power off before inserting or removing a Commu- ! nications Board Communications Board is inserted into or removed from the CPU Unit with the ...

Page 78

... Unit during wiring procedures. 2. After completing the wiring, remove the protective label from the top of the Unit before starting operation. The Unit will overheat if operated with this label in place. C200HW-PA204 or C200HW-PA204S Power Supply Unit Screw (3.5 mm head with self-raising pressure plate) ...

Page 79

... Do not ground the secondary coil of the transformer. Current Consumption The current consumption will be 120 VA max. (180 VA max. with the C200HW- PA209) per Rack, and there will be a surge current of at least 5 times the max. current when power is turned on. ...

Page 80

Wiring The output voltage of the 24-VDC output will vary with the current consumption of the load as shown in the following table. Be sure to check the current con- sumption and allowable voltage ranges of the devices connected before ...

Page 81

... RUN Output These terminals turn ON whenever the CPU Unit is operating in RUN or MON- ITOR Mode. Use these terminals under the following specifications These termi- nals are available on the C200HW-PA204R/PA209R only. Crimp Terminals The terminals on the Power Supply Unit are M3.5, self-raising terminals with screws ...

Page 82

Wiring DC Power Source Supply 24 VDC. Keep voltage fluctuations within the specified range (19.2 to 28.8 V). Power Consumption The power consumption will max. per Rack, and there will be a surge current of at least ...

Page 83

Wiring When using an Expansion I/O Rack, the Rack must also be grounded to the GR terminal. The same ground can be used for all connections. If grounding results in operating errors, insulate the CPU Backplane and all Expansion I/O ...

Page 84

Wiring Wiring Be sure that each Unit is securely mounted. In order to prevent wire scraps and other objects from getting inside of the Unit, keep the top-surface label on while wiring the Unit. After the wiring has been completed, ...

Page 85

Wiring I/O Unit Covers A C200H-COV11 Cover is provided as an I/O Unit cover for Units that use 10P terminal block connectors. After the I/O wiring has been completed, slide the cover up from the bottom, as shown in the ...

Page 86

... Input Leakage Current When two-wire sensors, such as photoelectric sensors, proximity sensors, or limit switches with LEDs, are used, the input bit may be turned ON erroneously by leakage current. In order to prevent this, connect a bleeder resistor across the input as shown below. ...

Page 87

Wiring For standard I/O Units: The previous calculations are based on the following equations. Precautions when When using a two-wire sensor with a 12-VDC or 24-VDC input device, check Connecting a Two-wire that the following conditions have been met. Failure ...

Page 88

Wiring Output Circuits Output Short-circuit If a load connected to the output terminals is short-circuited, output elements Protection and printed boards may be damaged. To guard against this, incorporate a fuse in the external circuit. ...

Page 89

Wiring Output Surge Current When connecting a transistor or triac Output Unit to an output device having a high surge current (such as an incandescent lamp), care must be taken to avoid damage to the Output Unit. The transistor and ...

Page 90

Wiring Inductive Load Surge Suppressor When an inductive load is connected to an I/O Unit necessary to connect a surge suppressor or diode in parallel with the load as shown below. This is so that the back EMF ...

Page 91

Wiring External Wiring If power cables must be run alongside the I/O wiring (that is, in parallel with it), at least 300 mm must be left between the power cables and the I/O wiring as shown below. Where: If the ...

Page 92

... The PC ignores all momentary power failures if the interruption lasts no longer than 10 ms (no longer than 2 ms for a DC Power Supply). If the interruption lasts Model C200HW-ATT01 Control panel Rack will be increased by approximate 10 mm. Confirm that the front of the Units, cables, or other parts of the PC do not come into contact with other devices ...

Page 93

Wiring between 10 and 25 ms (between 2 and 5 ms for a DC Power Supply), the inter- ruption may or may not be detected. If the supply voltage drops below 85% of the rated voltage for longer that 25 ...

Page 94

This section describes the function of the Programming Console and its connection methods. 4-1 Using the Programming Console 4-1-1 Nomenclature 4-1-2 Connecting the Programming Console 4-2 Checking Initial Operation Programming Console Operation . . . . . . . . ...

Page 95

Using the Programming Console 4-1 Using the Programming Console 4-1-1 Nomenclature The front panel of the Programming Console is shown below, taking the C200H-PRO27 example. LCD Area This window displays the program contents and monitor status. Mode Selector ...

Page 96

Using the Programming Console 4-1-2 Connecting the Programming Console There are two Programming Console models that can be used with the C200HX/ C200HG/C200HE: the C200H-PRO27-E and the CQM1-PRO01-E. The follow- ing illustration shows how a Programming Console (a C200H-PRO27-E in ...

Page 97

Checking Initial Operation 4-2 Checking Initial Operation After the Programming Console has been connected, it can be used to check initial C200HX/C200HG/C200HE operation. Make sure that the Programming Console is properly connected and that the correct power supply is being ...

Page 98

Troubleshooting, Inspections, and Maintenance The C200HX/C200HG/C200HE provides self-diagnostic functions to identify many types of abnormal system conditions. These functions minimize downtime and enable quick, smooth error correction. This section provides information on hardware and software errors that occur during PC ...

Page 99

Troubleshooting 5-1 Troubleshooting CPU Racks and Expansion I/O Racks Error POWER indicator does not light. RUN indicator does not light. RUN indicator is lit, but RUN output does not turn on. Relays do not operate from a particular number onwards. ...

Page 100

Troubleshooting Input Units Error Indicator lights are turned off, and no inputs turn ON Indicator lights are turned ON, but no inputs turn ON. All inputs remain ON, and will not turn OFF. Inputs do not ...

Page 101

Troubleshooting Output Units Error No outputs turn ON. p Outputs all fail to turn OFF. Indicators do not light, and the outputs for particular Relay numbers do not turn ON. ...

Page 102

Inspection and Maintenance 5-2 Inspection and Maintenance 5-2-1 Replacing Output Unit Fuses The following Output Units each contain one fuse. Replace the fuse if the fuse indicator lights. The OD211, OD212, OA222, and OA224 Output Units do not have fuse ...

Page 103

... Reassemble in reverse order of assembly. 1. Use UL or CSA approved fuses if the UL or CSA standards must be satis- fied. For further details, consult the fuse manufacturer. 2. Fuses in High-density I/O Units cannot be replaced by the user. Refer to your OMRON dealer for service. Output Unit Relay G6B-1174P-FD-US ...

Page 104

Inspection and Maintenance 3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit. 4. Using a Phillips screwdriver, remove the screw from the top of the Unit. 5. Using a ...

Page 105

Inspection and Maintenance ! Caution Check the pin arrangement before inserting a new Relay into the socket. Pins can only be inserted one way not try to force them if they do not go in easily. Applying too ...

Page 106

Inspection and Maintenance OC224V OC226 Note The relays on the C200H-OC222N, C200H-OC224V, and C200H-OC226 can- not be replaced. 5-2-3 Batteries DANGER Batteries can burn, explode, or leak. Absolutely do not short-circuit across the ! terminals, attempt to recharge batteries, or ...

Page 107

... VAC 24 VDC problem does not appear again. as possible in writing and attach it to the Unit before delivering it to your OMRON representative. (See inside back cover for regional offices.) be sure to remove any threads from the cloth before mounting the Unit. Section 5-3 Criteria ...

Page 108

Inspections Inspection Tools • Required Tools • Tools Required in Special Cases • Screwdrivers (flat-blade and Phillips) • Voltage tester (analog or digital) • Industrial alcohol and a clean cotton cloth • Synchroscope • Oscilloscope with pen plotter • Thermometer ...

Page 109

...

Page 110

... See page 23 for CPU Unit and Backplane restrictions. Power supply voltage: 24 VDC Output Model number RS-232C --- No C200HE-CPU11-E/ZE No C200HE-CPU32-E/ZE Yes C200HE-CPU42-E/ZE No C200HG-CPU33-E/ZE Yes C200HG-CPU43-E/ZE No C200HG-CPU53-E/ZE Yes C200HG-CPU63-E/ZE No C200HX-CPU34-E/ZE Yes C200HX-CPU44-E/ZE No C200HX-CPU54-E/ZE Yes C200HX-CPU64-E/ZE Yes C200HX-CPU65-ZE Yes C200HX-CPU85-ZE C200HW-PA204 C200HW-PA204S C200HW-PA204R C200HW-PA209R C200HW-PD024 95 ...

Page 111

... CPU Backplane or Expansion I/O Backplane. Name Memory Cassettes y Communication Boards (See note Card Unit Controller Link Unit Note: Use the V1 Communications Boards for the C200HZ/HG/HE-CPUjj-ZE CPU Units. The C200HW- COM01 can also be used. 96 Specifications 3 slots 5 slots 8 slots (see note) 10 slots (see note) Specifications ...

Page 112

... Input Specify either VDC. Output Specify either 100 or 200 VAC. Specify either VDC. Specify either VDC. Appendix A Model number C200HW-PA204 C200HW-PA204S C200HW-PA204R C200HW-PA209R C200HW-PD024 C200HW-BI031 C200HW-BI051 C200HW-BI081-V1 C200HW-BI101-V1 g C200H-CN311 C200H-CN711 C200H-CN221 C200H-CN521 C200H-CN131 Model number APF/PCF C200H-RT001-P C200H-RT002-P Wired C200H-RT201 C200H-RT202 ...

Page 113

Standard Models I/O Units Name Input Units AC Input Units DC Input Units AC/DC Input Units Interrupt Input Unit (see note) Output Relay Output Units Units Units Triac Output Units Transistor Output Units Units Analog Timer Unit Variable Resistor Connector ...

Page 114

Standard Models Name B7A Interface Units Note 1. If the Interrupt Input Unit is mounted on an Expansion I/O Rack, the interrupt function cannot be used and the Interrupt Input Unit will be treated as an ordinary 8-point Input Unit. ...

Page 115

Standard Models Special I/O Units Name High-density Input Units p I I/O Units (see note 1) (see note 1) Transistor Output Units Input/Transistor Output Units Analog I/O g Analog Input Units g ...

Page 116

Standard Models Name Cam Positioner Unit Data Setting Console Connecting Cables g PID Control Units Position Control Units Motion Control Unit MC Support Software IBM PC/AT or compatible Connecting cable Teaching Box Connection cable for Teaching Box Memory Pack (with ...

Page 117

... The C200H-OV001 Voice Unit cannot be used when an OMRON display device (Programmable Termi- nal) is connected to the peripheral port or the RS-232C port of a C200HX/HG/HE(-Z) CPU Unit in NT Link mode. Connect the Programmable Terminal to the serial communications port of a C200HW-COMjj Communications Board. • When using a C200H-OV001 Voice Unit mounted on the PC, set the baud rate of the CPU Unit’s periph- eral port or RS-232C port to 9,600 bps or less (regardless of the serial communications mode) ...

Page 118

... Power Cable Connects Power Supply Adapter and SYSMAC NET dap Link Unit. Bus Connection Units Connects SYSMAC LINK Unit or SYSMAC NET Link Unit to C200HW COM01/COM04 E Link Unit to C200HW-COM01/COM04-E Communications Board Host Link Units Rack-mounting PC Link Unit Single level: 32 Units Multilevel: 16 Units ...

Page 119

... Either VDC Specifications For IBM PC/AT or compatible For IBM PC/AT or compatible, coaxial cable connector Specifications Appendix A Model number APF/PCF C200H-RM001-PV1 Wired C200H-RM201 C200HW-CLK21 C200HW-PCU01 C200HW-PCS01 Model number G71-IC16 G71-OD16 G7TC-IA16 G7TC-ID16 G7TC-OC16 Model number S3200-NSB11-E 3G8F5-SLK21-E Model number 3G2A9-AL001 3G2A9-AL002-PE 3G2A9-AL002-E ...

Page 120

... S3200-CN specifies H-PCF optical fiber cable. 2. The boxes (jjj) are replaced by codes indicating the standard model lengths, as shown below. Consult with your OMRON representative for longer cables. When ordering longer cables, omit the portion represented by the boxes and specify the length in meters separately, e.g., S3200-CN-20-20 Code ...

Page 121

... Cable only; order desired length be- tween 501 and 800 m in increments 106 Applicable Units SYSMAC NET CV500-SLK11 C1000H-SLK11 C200HW-SLK13/14 --- Specifications Specifications Ambient temp: –10° to 70°C 10° to 70°C Ambient temp: 0° to 55°C (do not expose to ...

Page 122

... I/O Mas- C500-RM001-(P)V1 ter, Remote I/O C500-RT001/RT002-(P)V1 Slave, Host Link 3G2A9-jjj(-P) Unit, and Link Adapter Half-lock con- C200HS-SNT32 nector C200HW-SLK13/14 Full-lock con- CV500-SNT31 nector CV500-SLK11 CV1000H-SLK11 COCF62M and COCF62F are COCF62F are used as a pair. Appendix A Model number ...

Page 123

... S3200-CAT282 C200H-RM001-PV1 2 (provided with C200H-RT001/RT002-P the Tester) C500-RM001-(P)V1 C500-RT001/RT002-(P)V1 S3200-CAT320 S3200-LSU03-01E 2 (provided with C500-SNT31-V4 the Tester) Specifications CV500-SNT31 C200HS-SNT32 CV500-SLK11 C200HW-SLK13/14 CV1000H-SLK11 C500-RM001-(P)V1 C500-RT001/RT002-(P)V1 C200H-RM001-PV1 C200H-RT001/RT002-PV1 S3200-LSU03-01E C500-SNT31-V4 Appendix A Model number Stan- dards S3200-CAK1062 --- Model number Stan- ...

Page 124

Standard Models Note: Use a proper Head Unit model for the optical module to be used. If two types of optical modules (unit type and board type) are used, order an Optical Power Tester plus a proper Head Unit model. ...

Page 125

... For C200HW-BC081-V1 (8-slot CPU Backplane) For C200HW-BC101-V1 (10-slot CPU Backplane) For C200HW-BI031 (3-slot I/O Backplane) For C200HW-BI051 (5-slot I/O Backplane) For C200HW-BI081-V1 (8-slot I/O Backplane) For C200HW-BI101-V1 (10-slot I/O Backplane) I/O Brackets For 3-slot Backplane For 5-slot Backplane For 8-slot Backplane For 10-slot Backplane External Connectors Solder terminal ...

Page 126

... C200H-PRO27-E Programming Console, a C200H-CN222 Cable for the Programming Con- sole, C500-SU981-E Fuzzy Training Software, an RS-232C Cable, and a carrying belt. Specifications C200H-DIN01 PFP-50N PFP-100N PFP-100N2 PFP-M PFP-S Specifications Specifications C200HW-ZW3AT1-E Specifications Appendix A Model number Standards --- Model number Stan- dards C500-ZL3AT1-E --- Model number Stan- ...

Page 127

...

Page 128

... AC: 2,300 VAC, 50/60 Hz for 1 minute between external terminals and GR terminals with a leakage current max. (see note 2) DC: 1,000 VAC, 50/60 Hz for 1 minute between external terminals and GR terminals with a leakage current max. (see note 2) Appendix B Specifications Specifications C200HW-PA204S C200HW-PA204R 26 VDC, 0.625 A 26 VDC, 0.625 A 24 VDC, 0.8 A Total Total With ...

Page 129

... Rack: 10-slot Rack: Note: If the C200HW-PA209R is used, D will be 153 mm in the above dimensions. Note 1. The output voltage of the 24-VDC output will vary with the current consumption of the load as shown in the following table. Be sure to check the current consumption and allowable voltage ranges of the de- vices connected before using these terminals ...

Page 130

Specifications 3. Vibration Resistance Acceleration (m/s 4. Dimensions (Unit: mm) 5. RUN output is only available when the Power Supply Unit is mounted on the CPU Backplane 9.8 Amplitude 0.075 150 Frequency (Hz) Appendix B ...

Page 131

Specifications CPU Unit Specifications Control Method Stored program I/O Control Cyclic scan and immediate processing are both possible. Method Programming Ladder diagram Method Instruction Length 1 address/instruction words/instruction Number of C200HE-CPUjj-E: Instructions C200HE-CPUjj-ZE: 14 basic instructions + ...

Page 132

... The connections between the C200HX/C200HG/C200HE and a personal com- puter are illustrated below as an example. Applicable Connectors The following connectors are applicable. One plug and one hood are included with the CPU Unit. Plug: Hood: XM2S-0911 (OMRON) or equivalent Port Specifications Pin Abbreviation 1 FG ...

Page 133

Specifications One-to-one Link Connections The RS-232C port on the C200HX/C200HG/C200HE can be connected to the same port on another C200HX/C200HG/C200HE. Wire the cable as shown in the diagram below. Ground the FG terminals of C200HX/C200HG/C200HE Units at a resistance of ...

Page 134

... Note 1. If the Interrupt Input Unit is mounted on an Expansion I/O Rack, the interrupt function cannot be used and the Interrupt Input Unit will be treated as an ordinary 8-point Input Unit. Moreover, Interrupt Input Units cannot be used on Slave Racks. Use a C200HW-BCjj1 Backplane. 2. The Unit can overheat if more than 8 outputs are turned ON simultaneously. ...

Page 135

Specifications Optional Products Name I/O Unit Cover Terminal cover for 8-point or 5-point I/O Units Connector Cover Protective cover for unused Backplane connectors Space Unit Used to hold space for an I/O Unit. Note 1. When ordering, specify the model ...

Page 136

Specifications DC Input Unit C200H-ID212 Circuit Configuration 24 VDC Terminal Connections 24 VDC Rated Input Voltage 24 VDC Operating Input Voltage 20.4 to 26.4 VDC Input Impedance 3 kW Input Current 7 mA (at 24 VDC) ON Voltage 14.4 VDC ...

Page 137

Specifications AC Input Unit C200H-IA121 Circuit Configuration 100 to 120 VAC Terminal Connections 122 Rated Input Voltage 100 to 120 VAC 50/60 Hz Operating Input Voltage 85 to 132 VAC 50/60 Hz Input Impedance 9.7 kW (50 Hz ...

Page 138

Specifications AC Input Unit C200H-IA122/IA122V Circuit Configuration 100 to 120 VAC Terminal Connections Rated Input Voltage 100 to 120 VAC 50/60 Hz Operating Input Voltage 85 to 132 VAC 50/60 Hz Input Impedance 9.7 kW (50 Hz (60 ...

Page 139

Specifications AC Input Unit C200H-IA221 Circuit Configuration 200 to 240 VAC Terminal Connections 124 Rated Input Voltage 200 to 240 VAC 50/60 Hz Operating Input Voltage 170 to 264 VAC 50/60 Hz Input Impedance 21 kW (50 Hz ...

Page 140

Specifications AC Input Unit C200H-IA222/IA222V Circuit Configuration 200 to 240 VAC Terminal Connections Rated Input Voltage 200 to 240 VAC 50/60 Hz Operating Input Voltage 170 to 264 VAC 50/60 Hz Input Impedance 21 kW (50 Hz (60 ...

Page 141

Specifications AC/DC Input Unit C200H-IM211 Circuit Configuration VAC/DC Terminal Connections 126 Rated Input Voltage VDC Operating Input Voltage 10.2 to 26.4 VDC Input Impedance 2 kW Input Current 10 mA typical (at 24 VDC) ...

Page 142

Specifications AC/DC Input Unit C200H-IM212 Circuit Configuration 24 VAC/DC Terminal Connections 24 VAC/DC Rated Input Voltage 24 VDC Operating Input Voltage 20.4 to 26.4 VDC Input Impedance 3 kW Input Current 7 mA typical (at 24 VDC) ON Voltage 14.4 ...

Page 143

Specifications Contact Output Unit C200H-OC221 Circuit Configuration Output indicator Internal Circuit Terminal Connections 250 VAC 24 VDC max. (inductive load resistive load A/Unit) 128 Max. Switching Capacity 2 A 250 VAC (cosf = 1), 2 ...

Page 144

Specifications Contact Output Unit C200H-OC222 Circuit Configuration Output indicator Internal Circuit Terminal Connections Max. Switching Capacity 2 A 250 VAC (cosf = 1 250 VAC (cosf = 0.4 VDC (8 A/Unit) Min. Switching Capacity 10 ...

Page 145

Specifications Contact Output Unit C200H-OC225 Circuit Configuration Internal Circuit Terminal Connections Note This Unit can overheat if more than 8 output points are turned ON simultaneously. 130 Max. Switching Capacity 2 A 250 VAC (cosf = 1 250 ...

Page 146

Specifications Contact Output Unit C200H-OC223 Circuit Configuration Internal Circuit Terminal Connections 250 VAC 24 VDC max. (inductive load resistive load (10 A/Unit) Max. Switching Capacity 2 A 250 VAC (cosf = 1 250 VAC ...

Page 147

Specifications Contact Output Unit C200H-OC224 Circuit Configuration Internal Circuit Terminal Connections 250 VAC 24 VDC max. (inductive load resistive load (16 A/Unit) 132 Max. Switching Capacity 2 A 250 VAC (cosf = 1 250 ...

Page 148

Specifications Contact Output Unit C200H-OC222V/OC222N Circuit Configuration Output indicator Internal Circuit Terminal Connections Max. Switching Capacity 2 A 250 VAC (cosf = 1 250 VAC (cosf = 0.4 VDC (8 A/Unit) Min. Switching Capacity 10 ...

Page 149

Specifications Contact Output Unit C200H-OC226/OC226N Circuit Configuration Internal Circuit Terminal Connections 134 Max. Switching Capacity 2 A 250 VAC (cosf = 1 250 VAC (cosf = 0.4 VDC (8 A/Unit) Min. Switching Capacity 10 mA ...

Page 150

Specifications Contact Output Unit C200H-OC224V/OC224N Circuit Configuration Internal Circuit Terminal Connections 250 VAC 24 VDC max. (inductive load resistive load (16 A/Unit) Note There are no restrictions in the polarity when connecting a DC power supply. ...

Page 151

... Specifications Life Expectancy of Contact Output Unit The C200H-OC221/222/223/224/225 Contact Output Unit uses OMRON’s G6B-1174P-FD-US Relay. The life of the G6B-1174P-FD-US Relay varies with the contact current and ambient temperature. Refer to the following graphs to calculate this value, and be sure to replace the Relays before their service life expires. ...

Page 152

Specifications Arc killer circuit examples are listed in the following table. Circuit Current method Yes Yes Power supply Diode method No Yes Power supply Varistor method Yes Yes Power supply Note Do not connect a capacitor as ...

Page 153

Specifications Transistor Output Unit C200H-OD411 Circuit Configuration Output indicator Internal Circuit Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits. Terminal Connections Note Be sure ...

Page 154

Specifications Transistor Output Unit C200H-OD211 Circuit Configuration Output indicator Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections 24 VDC (0.3 A max., 2 A/Unit) Note Be sure to ...

Page 155

Specifications Transistor Output Unit C200H-OD212 Circuit Configuration Units manufactured on or before October 9, 2002 (manufacturing numbers 09X2 or earlier) Output indicator Fuse: UL-TSC-8A-N1 (Nagasawa) Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there ...

Page 156

Specifications Terminal Connections 24 VDC (0.3 A max ) Note Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF. Transistor Output Unit C200H-OD213 Circuit Configuration Output indicator Internal Circuit Note ...

Page 157

Specifications Terminal Connections 24 VDC (2.1 A max., 5.2 A/Unit) Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF. Transistor Output Unit C200H-OD214 (Load Short-circuit Protection Provided) Circuit Configuration ...

Page 158

Specifications Terminal Connections 24 VDC (0.8 A max., 2.4 A/Unit) Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF. C200H-OD214 Short-Circuit Protection The C200H-OD214 Output Unit is equipped with ...

Page 159

Specifications Clearing the Alarm When the short-circuit has been eliminated, reset the Unit by pressing the reset button. The alarm indicator will go out, the alarm output will turn OFF, and the output will be reset. Programming Example If there ...

Page 160

Specifications Terminal Connections Transistor Output Unit C200H-OD217 Circuit Configuration Internal Circuit VDC COM NC Max. Switching Capacity 0 ...

Page 161

Specifications Terminal Connections C200H-OD21A Transistor Output Unit (16 Points, Sourcing) (Load Circuit Protection Provided) Circuit Configuration Note When short-circuit/overload protection is activated, all 16 outputs will be switched OFF and the ALARM output becomes active (low level). The problem can ...

Page 162

Specifications the ALARM output or by connecting an alarm output indicator. It’s not possible to connect both the Input Unit and the indicator at the same time. Unless the external I/O power supply is connected and turned ON, the indicator ...

Page 163

Specifications Circuit Configuration Output indicator Internal Circuit Fuse 125 V (5.2-dia.x20) GGS (Nagasawa) Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits. Terminal ...

Page 164

Specifications Triac Output Unit C200H-OA221 Circuit Configuration Internal Circuit Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits. Terminal Connections Max. Switching Capacity 1 A ...

Page 165

Specifications Triac Output Unit C200H-OA222V Circuit Configuration Internal Circuit Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections 250 VAC max. (0.3 A max., 2 A/Unit) 150 Max. Switching ...

Page 166

Specifications Triac Output Unit C200H-OA223 Circuit Configuration Output indicator Internal Circuit Fuse 250 V (5.2-dia.x20) HT (SOC) Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used ...

Page 167

Specifications Triac Output Unit C200H-OA224 Circuit Configuration Output indicator Internal Circuit Fuse: 3.15 A 250 V (5.2-dia.x20) MT4 (SOC) Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections 250 ...

Page 168

Specifications Group-2 High-density I/O Units In the following diagrams, “m” is the first word allocated to the Unit in PC memory. DC Input Unit C200H-ID111 (64 Points) Circuit Configuration A CN1 B A CN2 B Rated Input Voltage 12 VDC ...

Page 169

... Note 1. I/O word “m” is determined by the I/O number setting ( 030 + 2 × I/O number). For the C200HX/ C200HG/C200HX/C200HW Unit), the I/O word is as follows Unit 030 + 2 × I/O number Unit 330 + 2 × (I/O number – The power can be supplied in either polarity, but the same polarity must be used for all COM terminals in each connector ...

Page 170

Specifications DC Input Unit C200H-ID216 (32 Points) Circuit Configuration and Simultaneously Usable Points COM 1000 pF IN00 680 W A IN07 COM IN08 5.6 kW Input indicator IN15 COM 1000 pF IN00 680 W B IN07 COM IN08 5.6 kW ...

Page 171

Specifications Terminal Connections 24 VDC 24 VDC Note 1. I/O word “m” is determined by the I/O number setting ( 030 + 2 × I/O number). 2. The power can be supplied in either polarity, but the same ...

Page 172

Specifications Circuit Configuration and Simultaneously Usable Points COM 1000 pF IN00 680 W A IN07 COM IN08 5.6 kW IN15 COM IN00 IN07 B COM IN08 IN15 COM IN00 1000 pF IN07 A 680 W COM IN08 5.6 kW IN15 ...

Page 173

Specifications DC Input Unit C200H-ID218 Circuit Configuration 0.01 µF to 470 Ω 3.9 kΩ to Input LED indicator 0.01 µF to 470 Ω 3.9 kΩ to Input LED indicator Terminal Connections 158 Rated Input Voltage 24 VDC Input Impedance 3.9 ...

Page 174

Specifications Note 1. The polarity of the input power supply can be either positive or negative. The polarity of all commons, however, must be the same. 2. COM terminals must all be wired even though they are connected internally. DC ...

Page 175

Specifications Terminal Connections ( words 24 VDC 24 VDC Note 1. The polarity of the input power supply can be either positive or negative. The polarity of all commons for CN1 and CN2, however, must be the same. ...

Page 176

Specifications Circuit Configuration and Maximum Switching Capacity Units manufactured on or before January 28, 2000 (manufacturing numbers 2810 or earlier*) Output indicator Internal Circuit Output indicator F indicator Fuse blowout detec- tion cir- cuit Units manufactured between January 31, 2000 ...

Page 177

Specifications *Manufacturing Numbers jjY9j 162 Manufacturing plant code ( blank) Year: Last digit of calendar year; e.g., 1999→9, 2000→0 Month (January to September), X (October), Y (November), Z (December) Day Appendix ...

Page 178

... When the fuse blows, the F indicator lights and the error flag corresponding to the I/O number is turned ON. I/O numbers correspond to AR 0205 to AR 0214. For the C200HX/C200HG/C200HX/ C200HW Unit), the following AR and IR bits turn ON Unit: AR 0205 to AR 0214 and IR 28000 to IR 28009 turn ON. ...

Page 179

Specifications Transistor Output Unit C200H-OD219 (64 Points) 164 Max. Switching Capacity 16 mA 4.5 VDC to 100 mA 26.4 VDC (see below) Min. Switching Capacity None Leakage Current 0.1 mA max. Residual Voltage 0.8 V max. ON Response Time 0.1 ...

Page 180

Specifications Circuit Configuration Units manufactured on or before January 28, 2000 (manufacturing numbers 2810 or earlier*) Inter- nal Circuit Indicator switch/ fuse blowout detection circuit Inter- nal Circuit Units manufactured between January 29, 2000 and October 10, 2002 (manufacturing numbers ...

Page 181

Specifications *Manufacturing Numbers jjY9j Maximum Switching Capacity 100 4.5 10 Power Supply Voltage (V) 166 Manufacturing plant code ( blank) Year: Last digit of calendar year; e.g., 1999→9, 2000→0 Month ...

Page 182

Specifications Terminal Connections CN1 I/O word “m+1” I/O word “m” COM ...

Page 183

Specifications Transistor Output Unit C200H-OD21B (32 Points) (Load Short-circuit Protection Provided) Note When the short-circuit/overload protection is activated for a contact point, the output for that point is turned OFF. At the same time, lamp “F” lights up, and the ...

Page 184

Specifications Terminal Connections High-density I/O Units (Special I/O Units) TTL Input Unit C200H-ID501 (32 Points) Circuit Configuration CN1 CN2 I/O word “m” I/O word “m+1” 24 VDC 24 VDC Rated Input Voltage 5 VDC Operating Input Voltage 4.5 to 5.5 ...

Page 185

... Note 1. I/O word “n” is determined by the unit number setting ( 100 + 10 × unit number). For the C200HX/ C200HG/C200HX/C200HW Unit), the I/O word is as follows Unit 100 + 10 × unit number Unit 400 + 10 × (unit number – When pin 2 of the Unit’s DIP switch is ON, input points connector 2 are high-speed inputs. ...

Page 186

Specifications DC Input Unit C200H-ID215 (32 Points) Circuit Configuration COM0 IN00 CN1 IN07 COM1 IN08 IN15 COM2 IN00 CN2 IN07 COM3 IN08 IN15 Terminal Connections CN1 I/O word “n” ...

Page 187

Specifications Usable I/O Points (C200H-ID215) To prevent overheating in the C200H-ID215 that can cause early failure of internal components, limit the number of input points that are ON simultaneously. As shown below, the number of points that can be on ...

Page 188

Specifications TTL Output Unit C200H-OD501 (Used as a 32-point Output Unit) Max. Switching Capacity 5 VDC 35 mA (280 mA/common, 1.12 A/Unit; output resistance 4.7 kW) Min. Switching Capacity None Leakage Current 0.1 mA max. Residual Voltage 0.4 V max. ...

Page 189

Specifications Circuit Configuration Units manufactured on or before November 13, 2002 (manufacturing numbers 13Y2 or earlier) Internal Circuit 174 5 VDC 4.7 kW OUT00 OUT07 CN1 COM0 Fuse 5 VDC OUT08 OUT15 COM1 5 VDC 4.7 kW OUT00 OUT07 CN2 ...

Page 190

Specifications Terminal Connections CN1 I/O word “n” VDC 10 10 COM1 VDC ...

Page 191

Specifications Circuit Configuration Units manufactured on or before November 13, 2002 (manufacturing numbers 13Y2 or earlier) Internal Circuit 176 5 VDC 4.7 kW DATA00 DATA07 COM0 Fuse CN1 5 VDC 4.7 kW STB00 STB07 COM1 Fuse 5 VDC DATA08 DATA15 ...

Page 192

Specifications Terminal Connections CN1 +V1 +V0 COM1 COM0 9 9 STB7 DATA7 8 8 STB6 DATA6 7 7 STB5 DATA5 6 6 STB4 DATA4 5 5 STB3 DATA3 ...

Page 193

Specifications Circuit Configuration Units manufactured on or before November 29, 1999 (manufacturing numbers 29Y9 or earlier VDC OUT00 OUT07 10 kΩ COM0 5 to Fuse 8.2 kΩ 24 VDC Inter- OUT08 nal Cir- OUT15 COM1 cuit 5 ...

Page 194

Specifications Terminal Connections CN1 I/O word “n” VDC 10 10 COM1 VDC ...

Page 195

Specifications Circuit Configuration Units manufactured on or before November 29, 1999 (manufacturing numbers 29Y9 or earlier VDC DATA00 DATA07 10 kΩ COM0 Fuse 8.2 kΩ VDC Inter- nal Cir- STB00 cuit STB07 10 kΩ ...

Page 196

Specifications Terminal Connections CN1 +V1 +V0 COM1 COM0 9 9 STB7 DATA7 8 8 STB6 DATA6 7 7 STB5 DATA5 6 6 STB4 DATA4 5 5 STB3 DATA3 ...

Page 197

Specifications High-density I/O Unit Limitations Limitations on the switching capacity of C200H-OD215/MD115/MD215 Transistor Output Units and the usable number of I/O points in the C200H-ID215 and C200H-MD215 are shown below. Switching Capacity The switching capacity of C200H-OD215/MD115/MD215 Transistor Output Units ...

Page 198

Specifications Circuit Configuration Units manufactured on or before November 21, 2002 (manufacturing numbers 21Y2 or earlier) Internal Circuit 5 VDC 4.7 kW OUT00 OUT07 CN1 (Output) COM0 Fuse 5 VDC OUT08 OUT15 1.1 kW COM1 IN00 IN07 2.4 kW COM2 ...

Page 199

Specifications Terminal Connections CN1 I/O word “n” VDC 10 10 COM1 VDC ...

Page 200

Specifications Circuit Configuration Units manufactured on or before November 21, 2002 (manufacturing numbers 21Y2 or eariler) Internal Circuit 5 VDC 4.7 kW STB00 STB07 CN1 COM0 Fuse 5 VDC STB08 STB15 1.1 kW COM1 DATA00 DATA07 2.4 kW COM2 CN2 ...