61F-GP-N8-V50 AC110 Omron, 61F-GP-N8-V50 AC110 Datasheet - Page 34

no-image

61F-GP-N8-V50 AC110

Manufacturer Part Number
61F-GP-N8-V50 AC110
Description
LEVEL CONTROLLER
Manufacturer
Omron
Series
61Fr
Type
Level Control - Variable Sensitivityr
Datasheets

Specifications of 61F-GP-N8-V50 AC110

Applications
Supply and Drain Control
Mounting Type
Socket Mount (8 pos)
Voltage - Supply
110VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
61F-GP-N8-V50AC110
61FGPN8V50AC110
61F-APN2
When operating two pumps alternately for controlling the one-point liquid level, use the Relay in combination with 61F Controller.
Specifications
Ratings
Contact Ratings (With G2RK Keep Relay)
Characteristics
When power is applied to the input terminals 2 and 7, the power will
be transmitted through the alternate operation control circuit and
output circuit to turn ON the contacts (NO condition) between 1 and
3 and between 6 and 8. This state will be held by a magnetic lock
even when the power to the input terminals is turned OFF.
When power is again applied to the input terminals, the contact (NO
condition) will turn OFF and the contacts (NC condition) between 1
and 4 and between 5 and 8 will turn ON. This state will be held even
when the power to the input terminals is turned OFF.
Internal Circuit Diagram
Supply voltage
Operating voltage range
Power consumption
Max. load
Carry contact
Max. operating current
Max. switching capacity
Response time
Minimum pulse width
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Life expectancy
Ambient temperature
Ambient humidity
61F-APN2 Solid-state Alternate Operation Relay
2
7
61F-APN2 Compact Plug-in Model
Item
G2RK (61F-APN2)
100, 110, 200, 220 VAC; 50/60 Hz
85% to 110% of rated voltage
3 VA
3 A at 250 VAC
3 A
3 A
750 VA
Operate: 25 ms max.
Release: 30 ms max.
Min. ON time:
Min. OFF time: 200 ms min.
100 MΩ min. at 500 VDC (between each terminal and power supply)
2,000 VAC, 50/60 Hz for 1 min (between each terminal and power supply)
10 to 55 Hz, 1-mm double amplitude
10 G (approx. 98 m/s
Mechanical:
Electrical:
Operating: --10°C to 55°C
Operating: 45% to 85% RH
Resistive load (cosφ = 1)
1,000,000 operations (at operating frequency of 1,800 operations/hour)
100,000 operations min.
(rated load)
40 ms min.
2
)
X/c
X/c
1
2
The above operation repeats each time power is applied to the input
terminals (power application pulse response system). Refer to the
following internal circuit diagram.
4
3
1
5
6
8
1.5 A at 250 VAC
375 VA
Inductive load (cosφ = 0.4, L/R = 7 ms)
61F-APN2