P7SA-10F Omron, P7SA-10F Datasheet - Page 6

Contact OSTI For Purchase

P7SA-10F

Manufacturer Part Number
P7SA-10F
Description
Contact OSTI For Purchase
Manufacturer
Omron
Series
G7SAr
Type
Socketr
Datasheets

Specifications of P7SA-10F

Number Of Positions
10
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Associated Relay Series
G7SA
Number Of Poles
4
Accessory Type
Sockets
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With/related Products
G7SA Series
For Use With
Z2943 - RELAY SAFETY PCB 3PST-NO/1NC 24V
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
P7SA10F
Z2947

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
P7SA-10F
Manufacturer:
Omron Electronics Inc-EMC Div
Quantity:
135
Safety Precautions
Refer to the “Precautions for All Relays” on page I-9 and “Precautions for All Relays with Forcibly Guided Contacts” on page G-2.
■ Precautions for Correct Use
Do not touch the terminal area of the Relays or the socket terminal
area (charged area) while power is ON. Electric shock will result.
Wiring
Use one of the following wires to connect to the P7SA-10F/10F-ND/
14F/14F-ND.
Tighten each screw of the P7SA-10F/10F-ND/14F/14F-ND to a
torque of 0.98 N·m securely.
Wire the terminals correctly with no mistakes in coil polarity,
otherwise the G7SA will not operate.
Cleaning
The G7SA is not of enclosed construction. Therefore, do not wash
the G7SA with water or detergent.
■ Forcibly Guided Contacts
If an NO contact becomes welded, all NC contacts will maintain a
minimum distance of 0.5 mm when the coil is not energized. Likewise
if an NC contact becomes welded, all NO contacts will maintain a
minimum distance of 0.5 mm when the coil is energized.
Cat. No. J120-E1-03
Stranded wire: 0.75 to 1.5 mm
Solid wire:
(from EN50205)
1.0 to 1.5 mm
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
!CAUTION
2
2
In the interest of product improvement, specifications are subject to change without notice.
Relays with Forcibly Guided Contacts
G7SA
G-9

Related parts for P7SA-10F