I1A/10A CLAMP PQ3 Fluke, I1A/10A CLAMP PQ3 Datasheet - Page 2

no-image

I1A/10A CLAMP PQ3

Manufacturer Part Number
I1A/10A CLAMP PQ3
Description
3-Phase 1A/10A Mini Current Clamp Set For PQ
Manufacturer
Fluke
Datasheet

Specifications of I1A/10A CLAMP PQ3

Test Probe Functions
Current
Current Ac Max
10A
Dmm Functions
AC Current
For Use With
Fluke 1735 And 1740 Series
Lead Free Status / RoHS Status
na
Operating Instructions
Cleaning
Clean the Probe periodically by wiping it with a damp cloth and
detergent. Do not use abrasive cleaners or solvents. Do not
immerse the Probe in liquids.
Symbols
Electrical Characteristics
Nominal current In: 1 / 10 A ac rms
Overload: up to 13 A rms.
Max. Non-destructive current: 100 A ac rms
Conductor position influence: <0.5 % of range at 50/60 Hz
Error due to adjacent conductor: 15 mA / A at 50 Hz
Phase shift at 2 kHz at 10 A: < 1 degree
Frequency range: 40 Hz to 5 kHz (-3 dB)
Temperature coefficient: 0.015 % of range / C
Working voltage (see section safety): 600 V ac rms or dc
Order reference:
~
W
X
T
-
)
P
1.
2.
3.
4.
3-phase 3024413: I1A/10A CLAMP PQ3
3-phase+N 3024424: I1A/10A CLAMP PQ4
Do not dispose of this product as unsorted municipal waste.
Go to Fluke’s website for recycling information.
Risk of Danger. Important Information. See manual.
Hazardous Voltage. Risk of electric shock.
Double insulation.
Do not apply around or remove from HAZARDOUS LIVE
conductors.
Conforms to relevant Canadian Standards Association
directives.
Conforms to relevant European Union directives.
Use caution when working with voltages
above 60 V dc, 30 V ac rms or 42 V ac peak.
Such voltages pose a shock hazard.
This Clamp is considered to be used in 600
CAT III environments. CAT III equipment is
designed to be used in distribution panels,
feeders and short branch circuit, and the
lighting system in large buildings.
Do not use the Clamp in damp or wet
environments or in locations that hazardous
gases exist.
Do not hold the Current Clamp anywhere
beyond the tactile barrier.
De-energize circuit during installation and
removal of Probe.
Connect the Clamp to the current input jack of the
product. Verify that the product has recognized that a
current Clamp is connected.
In case of uninsulated conductors, de-energize the
circuit before placing the Clamp. Re-energize the
circuit.
Observe and take measurements as required.
Positive output indicates that the current flow is in the
direction shown by the arrow on the Clamp.
In case of uninsulated conductors, de-energize before
removal of the Clamp.
Primary
current
Operating
error in %
of reading
Phase
shift
Specifications
General Specifications
Maximum Conductor Size: 15 mm (0.59 in) diameter bus bar
15 x 17 mm (0.59 x 0.66 in)
Cable length: 2 m (6.56 ft)
Length of measuring head: 122 cm (4 ft)
Operating temperature range: -10 C to +55 C
(14 F to 131 F)
Storage temperature range: -20 C to +70 C
(-4 F to 158 F)
Operating humidity
(non-condensing): 15 % to 85 % rh
Weight: PQ4 730 g (1.6 lb); PQ3 560 g (1.25 lb)
Reference Conditions
Environment temperature range: +18 C to +26 C
(64.4 F to 78.8 F)
Humidity: 20 to 75 % rh
Altitude: max. 2000 m (1.24 mi)
Current: sinusoidal waveform, 48 Hz to 65 Hz, distortion
factor: <1 %, no dc component
Load impedance for voltage output: 1 M , <100 pF
Safety Standards
IEC/EN61010-1: 2001
IEC/EN61010-2-032:2002
IEC/EN61010-031:2002
Safety Specifications
Category Rating: 600 V CAT III, pollution degree 2
EMC Standards: IEC/EN 61326-1:2006
Measurement Considerations
Observe the following guidelines when making measurements:
Accuracy (at 50 Hz)
Center the conductor inside the Clamp jaw.
Make sure the Clamp is perpendicular to the conductor.
For optimal reading, make sure the conductor is positioned
between the alignment marks on the jaws of the Clamp.
Avoid taking measurements close to other current-carrying
conductors.
Not specified
0.025 A to
0.5 A
2.5 %
0.5 A to 2.5 A
1.5 %
<2
2.5 A to 5 A
<0.5
0.5 %
5 A to 10 A
0.5 %
<1