JCK-A-6R Cooper/Bussmann, JCK-A-6R Datasheet

Fuses 2540V 170A

JCK-A-6R

Manufacturer Part Number
JCK-A-6R
Description
Fuses 2540V 170A
Manufacturer
Cooper/Bussmann
Type
Medium Voltager
Datasheet

Specifications of JCK-A-6R

Voltage Rating (vac)
2540V
Current Rating
170A
Mounting
Surface Mount
Product Depth (mm)
Not Requiredmm
Product Height (mm)
Not Requiredmm
Voltage Rating
2.54 KVolts
Termination Style
Cartridge
Fuse Type
Fast Acting
Dimensions
11.24 in L x 3 in D
Product
Medium Voltage Fuse
Interrupt Rating
80 KAmps / 50 KAmps
Lead Free Status / RoHS Status
Compliant
Lead Free Status / RoHS Status
Compliant
Catalog Symbol:
R-Rated
Medium Voltage
Current Limiting
2400V AC — JCK, JCK-A, JCK-B, JCH
4800V AC — JCL, JCL-A, JCL-B, JCG
7200V AC — JCR-A, JCR-B
Max. Design Voltage
UL Recognized:
UL Recognized (GUIDE #MSSS2, FILE # E96676)
R-Rated Fuses
For Motor Circuit Protection
Medium Voltage
2-26-03
SB03044
JCK, JCK-A, JCK-B, JCH, JCL, JCL-A,
JCL-B, JCG, JCR-A, & JCR-B
2540V AC — JCK, JCK-A,
5080V AC — JCL, JCL-A
8300V AC — JCR-A, JCR-B
2540V AC — JCK, JCK-A
5080V AC — JCL, JCL-A
JCK-B, JCH
JCL-B, JCG
(2R-24R)
• R-Rated medium voltage fuses are back-up current limiting
• The JCK-A, JCL-A, & JCR-A are supplied with Cutler-
• This single hookeye is on one end of the fuse and aids in the
• Current limiting fuses may be designated as R-Rated if they
• Bussmann R-Rated current limiting fuses are designed for
• These fuses offer a high level of fault current interruption in a
• Open fuse indication on all fuses.
JCK, JCK-A, JCK-B, JCH,
fuses used in conjunction with medium voltage motors and
motor controllers.
Hammer Ampgard Hookeye.
insertion and removal of the fuse.
meet the following requirements:
1. The fuse will safely interrupt all currents between its
2. The fuse will melt in a range of 15 to 35 seconds at a
value of 100 times the “R’ number (ANSI C37.46).
use with medium voltage starters to provide short-circuit
protection for the motor and motor controller.
self-contained, non-venting package which can be mounted
indoors or in an enclosure.
minimum and maximum interrupting ratings.
JCG, JCR-A, & JCR-B
JCL, JCL-A, JCL-B,
Form No. JCK, JCK-A, JCK-B, JCH, JCL,
JCL-A, JCL-B, JCG, JCR-A, & JCR-B
Bussmann
Data Sheet: 6001
Page 1 of 8
®

Related parts for JCK-A-6R

JCK-A-6R Summary of contents

Page 1

... R-Rated medium voltage fuses are back-up current limiting fuses used in conjunction with medium voltage motors and motor controllers. • The JCK-A, JCL-A, & JCR-A are supplied with Cutler- Hammer Ampgard Hookeye. • This single hookeye is on one end of the fuse and aids in the insertion and removal of the fuse. • ...

Page 2

... R-Rated; Indoor/Enclosure; With Cutler-Hammer Ampgard Hookeye (See Figure 1) JCK-A- 2540V JCK-A-3R 100 3R 2540V JCK-A-4R 130 4R 2540V JCK-A-5R 150 5R 27540V JCK-A-6R 170 6R 2540V JCK-A-9R 200 9R 2540V JCK-A-12R 230 12R 2540V JCK-A-18R 390 18R 2540V JCK-A-24R 450 24R 2540V 2400V ...

Page 3

... Form No. JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B Page Data Sheet: 6001 ...

Page 4

... SB03044 JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B INDICATOR Showing Fuse is Open Bussmann ® INDICATOR Showing Fuse is Open 0.38" (9.5mm) B Form No. JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B Page Data Sheet: 6001 ...

Page 5

... JCK, JCK-A, JCK-B, JCH, Total Clearing Curves 168-A PROSPECTIVE SHORT CIRCUIT CURRENT (X10) RMS SYMMETRICAL AMPERES Bussmann JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B Form No. JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B Data Sheet: 6001 ® Page ...

Page 6

... JCK, JCK-A, JCK-B, JCH, JCG, JCR-A, & JCR-B Time-Current Curve: Total Clearing 50999-2 PROSPECTIVE SHORT CIRCUIT CURRENT (X10) RMS SYMMETRICAL AMPERES Bussmann JCL, JCL-A, JCL-B, Form No. JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B Page Data Sheet: 6001 ® ...

Page 7

... JCK, JCK-A, JCK-B, JCH, JCG, JCR-A, & JCR-B Time-Current Curve: Total Clearing 51000-2 PROSPECTIVE SHORT CIRCUIT CURRENT (X10) RMS SYMMETRICAL AMPERES Bussmann JCL, JCL-A, JCL-B, Form No. JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B Page Data Sheet: 6001 ® ...

Page 8

... JCK, JCK-A, JCK-B, JCH, JCG, JCR-A, & JCR-B Time-Current Curve: Total Clearing 51001-2 PROSPECTIVE SHORT CIRCUIT CURRENT (X10) RMS SYMMETRICAL AMPERES Bussmann JCL, JCL-A, JCL-B, Form No. JCK, JCK-A, JCK-B, JCH, JCL, JCL-A, JCL-B, JCG, JCR-A, & JCR-B Page Data Sheet: 6001 ® ...

Related keywords