205-11-1-42-4A-502-H AIRPAX, 205-11-1-42-4A-502-H Datasheet - Page 16

no-image

205-11-1-42-4A-502-H

Manufacturer Part Number
205-11-1-42-4A-502-H
Description
Circuit Breaker Magnetic Circuit Protectors 2Pole 5A 4-Pin
Manufacturer
AIRPAX
Type
Magnetic Circuit Protectorsr
Datasheet

Specifications of 205-11-1-42-4A-502-H

Current Rating
5 A
Number Of Poles
2
182
205/295 SPECIFICATIONS
Trip free
Will trip open on overload, even when the handle is forcibly
held on or restrained. This prevents operator from damaging
the circuit by holding the handle in the ON position.
Trip Indication
The operating handle moves positively to the OFF position on
overload.
Ambient Operation
Operates normally in temperatures between –40°C and +85°C.
Insulation Resistance
Not less than 100 megohms at 500Vdc.
Dielectric Strength
Withstands 1500Vac at 60Hz for 60 seconds or 1800Vac for one
second from terminal to terminal, and from auxiliary switch
terminal to main terminal.
endurance
Per UL 1077 (6000 operations at rated load plus 4000 operations
with no load). Tested at a maximum rate of six times per
minute. rating above 50 amperes operate a minimum of 5000
operations.
Notes: DCR and impedance based on 100% rated current applied and stablized a minimum of one hour.
Tolerance: .02 amperes to 2.5 amperes, ± 20%; 2.6 amperes to 20 amperes, ± 25%; 21 amperes to 50 amperes, ± 50%. Consult factory for special values and for coil
impedance of delays not shown
Current
Ratings
(Amps)
0.05
0.10
0.50
1.0
5.0
10.0
15.0
20.0
30.0
50.0
205/295 - NOMINAL DCR / IMPeDANCe
APL/UPL, 205/295 - 205/295 Specifications
50
162
35.4
1.2
.236
.021
.0060
.0040
.0032
.0021
.0020
59
540
105
4.2
1.02
.048
.0121
.0067
.0047
.0036
.0024
Resistance (ohms)
DC Delays
51, 52, 53
506
125
4.5
1.2
.059
.0140
.0092
.0052
.0036
.0026
Dual Coil
51, 52, 53
576
150
5.6
1.41
.070
.0160
.0100
.0070
.0040
.0023
60
174
42.5
1.9
.41
.030
.0075
.0038
.0024
.0022
.0020
Dual Coil Ratings
5-65Vdc and 5-250Vac for three terminal configurations.
5-120Vac and 5-120Vdc for four terminal configurations. Not
available in delays 64, 65 and 66.
295 Ratings
0.05-100 amperes, 65Vdc, 0.050-60 amperes, 250Vac maximum,
50/60Hz or 400Hz. 51-100 amperes at 65Vdc and 120Vac
maximum. 30 amperes at 277/480Vac for 3 phase WYE
Connected applications only. ratings to 20 amperes at 277Vac,
50/60Hz are available upon request.
205 Ratings
205 protectors are UL (File No. E-66410) and CSA (File No.
Lr-26229) recognized as Component Appliance Controls in the
following configurations and ratings.
205D Ratings
205D protectors are UL-1500 (Marine Ignition Protection)
recognized at 65Vdc or 250Vac to 60 amperes maximum at
1000 AIC. Consult factory for application details.
Configurations
Series, Shunt, relay, Auxiliary Switch, Switch Only.
Poles
One through nine.
69
419
103.4
4
.955
.045
.0105
.0068
.0049
.0032
.0020
AC, 50/60Hz Delays
Impedance (ohms)
600, 61, 62
71, 72, 73
582
119.0
4.1
1.08
.048
.0134
.0070
.0050
.0035
.0025
64, 65, 66
Dual Coil 61, 62
691
160
6.2
1.56
.068
.0174
.0120
.0069
.0037
.0030
http://airpax.sensata.com/
40, 49
1975
495
22
5.01
.240
.0520
.0260
.0140
.0079
.0036
Impedance (ohms)
AC, 400Hz Delays
41, 42, 43
1195
284
12
2.72
.140
.0283
.0140
.0088
.0043
.0028

Related parts for 205-11-1-42-4A-502-H