DLP100241/E TDK Corporation, DLP100241/E Datasheet

AC/DC Power Supply Single-OUT 24V 4.1A 98.4W

DLP100241/E

Manufacturer Part Number
DLP100241/E
Description
AC/DC Power Supply Single-OUT 24V 4.1A 98.4W
Manufacturer
TDK Corporation
Series
DLPr

Specifications of DLP100241/E

Input Voltage
85 to 132|170 to 265 V
Output Voltage
24 V
Maximum Current Rating
2.3 A
Maximum Output Current
4.1 A
Number Of Outputs
1
Maximum Output Power
98.4 W
Efficiency
85 %
Input Frequency
47 to 63 Hz
Operating Temperature
-10 to 70 °C
Voltage - Output
24V
Power (watts)
100W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 132VAC, 170 ~ 265VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 4.1A
Size / Dimension
4.33" L x 2.36" W x 3.82" H (110mm x 60mm x 97mm)
Power (watts) - Rated
98.4W
Approvals
CE, CSA, EN, IEC, UL
Brand/series
DLP Series
Configuration
Enclosed
Current, Inrush
20 A (Typ.) @ 100 VAC⁄45 A (Typ.) @ 230 VAC
Current, Rating
2.3 A @ 100 VAC⁄1.2 A @ 230 VAC
Frequency
47 to 63 Hz
Height
110 mm
Operation
Linear
Output
24 VDC @ 4.1 A
Power, Output
98.4 W
Primary Type
AC-DC
Special Features
PFC
Temperature, Operating, Maximum
60 °C
Temperature, Operating, Minimum
-10 °C
Voltage, Input
85 to 132/170 to 265 VAC
Voltage, Output
24 VDC
Voltage, Rating
170 to 265⁄85 to 132 VAC
Width
97 mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
RoHS Compliant part
Other names
285-1206
DLP100-24-1/E
CA734-01-01/2-B
This specifications sheet also apply to option model /EJ
* Read instruction manual carefully , before using the power supply unit.
* 1: At 100/230VAC and maximum output power, Ta = 25°C.
* 2 : For cases where conformance to various safety specs ( UL, CSA, EN ) are required, to be described as
* 3 : Not applicable for the in-rush current to Noise Filter for less than 0.2ms.
* 4 : Please refer to Fig A for measurement of line & load regulation and output ripple voltage.
* 5 : 85-132VAC/170-265VAC, constant load.
* 6 : No load - Full load(Maximum power), constant input voltage.
* 7 : Constant current limit with automatic recovery.
* 8 : OVP circuit will shutdown output, manual reset. (Re Power on)
* 9 : Measured by each measuring method of UL, CSA, EN and
*10: At standard mounting method, Fig B.
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
1
2
3
4
5
6
7
8
9
Nominal Output Voltage
Maximum Output Current
Maximum Output Power
Efficiency (100/230VAC) (Typ)
Input Voltage Range
Input Current
Inrush Current (100/230VAC) (Typ)
PFHC
Output Voltage Range
Maximum Ripple & Noise
Maximum Line Regulation
Maximum Load Regulation
Temperature Coefficient
Over Current Protection
Over Voltage Protection
Hold-Up Time
Leakage current
Parallel Operation
Series Operation
Operating Temperature
Operating Humidity
Storage Temperature
Storage Humidity
Cooling
Withstand Voltage
Isolation Resistance
Vibration
Shock (In package)
Safety
EMI
Immunity
Weight (Typ)
Size ( W.H.D.)
- Load(%) is percent of maximum output load ( Item2 and 3 ), do
-For standard mounting, refer to derating curve (CA734-01-02/2_)
DENAN (at 60Hz).
(Measure with JEITA RC-9131 probe)
100-120VAC/200-240VAC, 50 / 60Hz on name plate.
Avoid to operate at overload or dead short for more than 30seconds.
ITEMS
not exceed derating in both Maximum Output Current and Power.
= NOTES=
(100/230VAC) (Typ)
(100/230VAC)
( * 4 )
-10 Ta<0°C
0 Ta 60°C
( * 4, 5 ) mV
( * 4, 6 ) mV
( * 10 )
DLP100-24-1 SPECIFICATIONS
MODEL
( * 1 ) %
( * 2 )
( * 1 ) A
( * 3 )
( * 7 ) A
( * 8 ) V
( * 1 )
( * 9 )
mV
mV
mm
W
V
A
V
g
Approved by UL60950, CSA60950, EN60950, UL508, CSA C22.2 No.14,
More than 100M
Input - Output : 3.0kVAC, Input - FG : 2.0kVAC (20mA) for 1min
10~55Hz (Sweep for 1min) 9.8m/s
Built to meet IEC61000-6-2 (IEC61000-4-2,-3,-4,-5,-6,-8,-11)
Measurement point for
Vo Line/Load Regulation.
Built to meet VCCI-B, FCC-ClassB, EN55011/EN55022-B
Output
terminal
EN50178 CATEGORY III(Primary). Built to meet DENAN.
Class 2 power supply approved by UL508&NFPA725.41
20A at 100VAC, 45A at 230VAC, Ta=25
85~132/170~265VAC (Auto selectable) / 47~63Hz
Convection: -10 ~ +50°C ( 100% ); 60°C ( 70% )
Output - FG : 500VAC (100mA) for 1min.
60x97x110 (Refer to Outline Drawing)
At no operating and with DIN RAIL,
+V
-V
at Ta=25°C and 70%RH, Output - FG : 500VDC
30 ~ 90 %RH (No dewdrop)
Built to meet IEC61000-3-2
10 ~ 95%RH (No dewdrop)
Convection cooling
Less than 0.05%/°C
Less than 0.75mA
Less than 196m/s
DLP100-24-1
Fig. A
- 10 ~ + 60 °C
- 30 ~ +85°C
L
20ms /30ms
30.0~35.0
21.6~28
Possible
2.5/1.1
4.3~
98.4
240
360
120
192
540
4.1
24
83
-
2
Measurement point
for Vripple
Constant, X, Y, Z each 1hour
Output terminal
2
+
C1 C2
o
C, Cold Start
A
DENSEI-LAMBDA
C1 : Elec. Cap 100uF
C2 : Film Cap 0.1uF
Bandwidth of scope : 100MHz
L : 150mm
Input terminal
Rail
Fig. B

Related parts for DLP100241/E

DLP100241/E Summary of contents

Page 1

CA734-01-01/2-B This specifications sheet also apply to option model /EJ ITEMS Nominal Output Voltage 1 2 Maximum Output Current Maximum Output Power 3 Efficiency (100/230VAC) (Typ) 4 Input Voltage Range 5 Input Current (100/230VAC) (Typ) 6 Inrush Current (100/230VAC) (Typ) ...

Page 2

CA734-01-02/2 (This specifications sheet also apply to option model /EJ) 100 -10 DLP100-24-1 OUTPUT DERATING DLP100-24-1 *COOLING: CONVECTION COOLING LOADING CONDITION(%) Standard Mounting Ta(°C) -10~50 60 OUTPUT DERATING CURVE (°C) ...

Related keywords