NLP250N-99S24J ARTESYN, NLP250N-99S24J Datasheet - Page 3

no-image

NLP250N-99S24J

Manufacturer Part Number
NLP250N-99S24J
Description
AC/DC Power Supply Single-OUT 24V 7.3A 250W 18-Pin
Manufacturer
ARTESYN
Datasheet

Specifications of NLP250N-99S24J

Input Voltage
85 to 264 V
Output Voltage
24 V
Maximum Current Rating
2.78(rms) A
Maximum Output Current
7.3 A
Number Of Outputs
1
Maximum Output Power
250 W
Efficiency
86(Typ) %
Input Frequency
47 to 63 Hz
Operating Temperature
0 to 70 °C
Mechanical Drawing
J1
Notes
1 Free air convection. Maximum continuous output power not to exceed 175 W.
2 200 LFM (250 LFM with cover) forced air cooling from the longer side.
3
4 CAUTION: Allow a minimum of 1 second after disconnecting line power when
Ordering Information
E
L
N
Output Voltage
Refer to Figure 1 for the derating curve.
Maximum continuous output power not to exceed 250 W.
Figure is peak-to-peak for room temperature rating. Output noise
measurements are made across a 20 MHz bandwidth using a 6 inch twisted
pair, terminated with a 10 µF tantalum capacitor and a 0.1 µF ceramic
capacitor.
making thermal measurements. For optimum reliability no part of the heatsink
should exceed 115 °C and no semi-conductor case temperature should exceed
120 °C.
12 V
24 V
7.000 [177.80]
Min
0 A
0 A
Max (free air)
14.6 A
1.500 [38.10]
7.3 A
Output Current
(1,4)
VR7
Max (forced air)
J3
JP1
J4
J2
10.5 A
21 A
1
1
1
(2,4)
Ripple
120 mV
240 mV
(28.96)
1.140
0.25 (6.35)
5 No external filtering required during conducted emissions testing but some
6 This product is only for inclusion by professional installers within other
7 Three orthogonal axes, random vibration 10 minutes for each axes, 2.4 G
8 5 V sb (standby) output is available whenever AC is present, regardless of
9 The ‘J’ suffix indicates that these parts are Pb-free (RoHS 6/6) compliant.
10 NOTICE: Some models do not support all options. Please contact your local
applications may require additional filtering to achieve system compliance.
Compliance with radiated EMI specifications may require mounting in a
suitable enclosure.
equipment and must not be operated as a stand alone product.
remote ON/OFF signal status. 12 V (fan) present when main output is present.
“CJ” suffix indicates covered RoHS version.
Emerson Network Power representative or use the on-line model number
search tool at http://www.PowerConversion.com to find a suitable alternative.
(3)
Total Regulation
± 2.0%
± 2.0%
MAX. SCREW PENETRATION 0.08IN
CUSTOMER MOUNTING HOLES
Model Numbers
BOTTOM VIEW
NLP250N-99S12J
NLP250N-99S24J
4.700 (119.38)
5.500 (139.70)
Embedded Power for
Business-Critical Continuity
5.850 (148.59)
6.250 (158.75)
4 PLACES
4 PLACES
M3.0
6-32
M3.0
6-32
(9, 10)
NLP250 Medical Series
Rev.10.1.09_181
 of 4

Related parts for NLP250N-99S24J