SWS5024 TDK Corporation, SWS5024 Datasheet

AC/DC Power Supply Single-OUT 24V 2.1A 5-Pin

SWS5024

Manufacturer Part Number
SWS5024
Description
AC/DC Power Supply Single-OUT 24V 2.1A 5-Pin
Manufacturer
TDK Corporation
Series
SWSr
Type
Enclosedr
Datasheets

Specifications of SWS5024

Input Voltage
85 to 265 V
Output Voltage
24 V
Maximum Current Rating
1.2 A
Maximum Output Current
2.1 A
Number Of Outputs
1
Efficiency
84(Typ) %
Input Frequency
47 to 63 Hz
Operating Temperature
-10 to 70 °C
Voltage - Output
24V
Power (watts)
50W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
24 VDC @ 2.1A
Size / Dimension
6.26" L x 3.62" W x 1.46" H (159mm x 91.9mm x 37.1mm)
Power (watts) - Rated
50.4W
Approvals
CE, CSA, EN, UL
Line Regulation
5%
Load Regulation
5%
Output Current (max)
2.1A
Output Power (max)
50W
Screening Level
Commercial
Operating Temperature Min Deg. C
-10C
Operating Temperature Max Deg. C
70C
Mounting Style
Desktop
Pin Count
5
Brand/series
SWS Series
Configuration
Enclosed
Current, Output
2.1 A (Max.)
Dimensions
3.62 in. W x 1.46 in. H x 6.26 in. D
Frequency, Input
47 to 63 Hz
Output
24 VDC @ 2.1 A
Power, Output
50 W
Primary Type
AC-DC
Special Features
PFC
Standards
UL Listed, CSA Certified, CE Marked
Temperature, Operating
-10 to +70 °C
Voltage, Input
85 to 265/120 to 370 VAC/VDC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Compliant
Other names
285-1625
SWS50-24
* Read instruction manual carefully , before using the power supply unit.
* 1 : At maximum output power, nominal input voltage, Ta = 25°C.
* 2 : For cases where conformance to various safety specs ( UL, CSA, EN ) are required, to be described as 100 - 240VAC, 50 / 60Hz on name plate.
* 3 : Please refer to Output Derating Curve for input voltage less than 100VAC (next page).
* 4 : Not applicable for the in-rush current to Noise Filter for less than 0.2ms.
* 5 : Please refer to Fig A for measurement of line & load regulation, ripple and noise voltage.
* 6 : 85 - 265VAC, constant load.
* 7 : No load - Full load(Maximum power), constant input voltage.
* 8 : Current limiting with automatic recovery.
* 9 : OVP circuit will shutdown output, manual reset (Re power on).
*10: Measured by each measuring method of UL, CSA, EN.
*11: Refer to Output Derating Curve (CA729-01-02_) for details of output derating
SWS50 SPECIFICATIONS
10 Line Regulation
11 Load Regulation
12 Temperature Coefficient
13 Over Current Protection
14 Over Voltage Protection
15 Hold-Up Time (Typ)
16 Leakage current
17 Series Operation
18 Operating Temperature
19 Operating Humidity
20 Storage Temperature
21 Storage Humidity
22 Cooling
23 Withstand Voltage
24 Isolation Resistance
25 Vibration
26 Safety
27 EMI
28 Immunity
29 Weight (Typ)
30 Dimension
1
2
3
4
5
6
7
8
9
Nominal Output Voltage
Maximum Output Current
Maximum Output Power
Efficiency (Typ)
Input Voltage Range
Input Current (Typ)
Inrush Current (Typ)
Output Voltage Range
Ripple and Noise
Ripple & noise are measured at 20MHz by using a 12'' twisted pair terminated with a 0.1uF and 47uF capacitor.
Avoid to operate at overload or dead short for more than 30seconds.
versus ambient temperature and mounting method .
ITEMS
= NOTES=
(115/230VAC)
(115/230VAC)
(115/230VAC)
(115/230VAC) ( * 1, 5 ) mV
MODEL
( * 2, 3 )
( * 5, 6 ) mV
( * 5, 7 ) mV
( * 10 )
( * 11 )
( * 1 )
( * 1 )
( * 1 )
( * 1 )
( * 1 )
( * 4 )
( * 8 )
( * 9 )
mm
DENSEI-LAMBDA
W
%
V
A
A
V
A
V
g
2.97~3.63
3.79~4.95
SWS50-3
0.7 / 0.5
73 / 70
10.5~
3.3
10
33
80
20
40
More than 100MΩ at Ta=25°C and 70%RH, Output - FG : 500VDC
Input - Output : 3.0kVAC (20mA), Input - FG : 2.0kVAC (20mA)
Approved by UL60950-1, CSA60950-1, EN60950-1, EN50178
1mA Max, 0.3mA(Typ) at 115VAC / 0.6mA(Typ) at 230VAC
20A at 115VAC, 40A at 230VAC, Ta=25
Built to meet FCC-Class B, EN55011/EN55022-B
- 10 ~ + 60 °C (Refer to Output Derating Curve)
5.75~6.95
At no operating, 10 - 55Hz ( sweep for 1min )
SWS50-5
Built to meet EN61000-4-2,-3,-4,-5,-6,-8,-11
85 ~ 265VAC (47-63Hz) or 120 ~ 370VDC
4.5~5.5
77 / 75
Output - FG : 500VAC (100mA) for 1min.
10.5~
37 x 92 x 159 (Refer to Outline Drawing)
19.6m/s
10
50
80
20
50
5
30 ~ 90 %RH (No dewdrop)
10 ~ 95%RH (No dewdrop)
Measurement point for Vo Line/Load Regulation, and
ripple and noise.
2
Constant, X, Y, Z 1hour each
Less than 0.02%/°C
Convection cooling
20ms / 160ms
- 30 ~ +85°C
SWS50-12
10.8~13.2
13.8~16.2
Possible
82 / 79
51.6
4.5~
400
4.3
TB1
12
80
48
96
1.2 / 0.6
+V
-V
SWS50-15
13.5~16.5
17.2~20.3
o
84 / 80
C, Cold Start
3.7~
52.5
100
120
3.5
15
60
Fig. A
A
SWS50-24
21.6~26.4
27.6~32.4
84 / 80
2.2~
50.4
100
144
2.1
24
96

Related parts for SWS5024