Specifications of E5CSVR1TFAC100240

No. Of Digits / Alpha
4
Meter Function
Temperature
Digit Height
13.5mm
Power Consumption
5VA
Operating Temperature Range
-10°C To +55°C
Controller Input
Thermocouple / Platinum RTD
Mounting Type
1/16 DIN
Contact Rating
3A, 250VAC
Supply Voltage Min
100VAC
Rohs Compliant
Yes
Thermocouple Type
J, K, L, T, U, N, R, Pt100, JPt100
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Temperature Accuracy ±
0.5%
Output Voltage Max
250VAC
Output Voltage Min
12VDC
Lead Free Status / RoHS Status
Specifications
■ Ratings
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
■ Characteristics
Note: 1. The following exceptions apply to thermocouples.
Supply voltage
Operating voltage range
Power consumption
Sensor input
Control
output
Control method
Alarm output
Setting method
Indication method
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Setting accuracy
Indication accuracy
(ambient temperature of 23°C)
Influence of temperature
Influence of voltage
Hysteresis (for ON/OFF control)
Proportional band (P)
Integral time (I)
Derivative time (D)
Alarm output range
Control period
Sampling period
Insulation resistance
Dielectric strength
Vibration
resistance
Shock resistance
Life expectancy
Weight
Degree of protection
Memory protection
EMC
Approved standards
Conformed standards
2. Models for 24 VAC/DC can also be manufactured.
2. The following exceptions apply to platinum resistance thermometers.
• U, L: ±2°C ±1 digit max.
• R:
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Relay output
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
±3°C ±1 digit max. at 200°C or less
Malfunction 10 to 55 Hz, 20 m/s
Destruction 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s
Destruction 300 m/s
Electrical
Thermocouple (See note 1.):
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
R thermocouple inputs:
Other thermocouple inputs:
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.
0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models)
1 to 999°C (automatic adjustment using auto-tuning/self-tuning)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Absolute-value alarm: Same as the control range
Other:
Alarm hysteresis:
2/20 s
500 ms
20 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
100,000 operations min. (relay output models)
Approx. 120 g (Controller only)
Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMI Radiated:
EMI Conducted:
ESD Immunity:
Radiated Electromagnetic Field Immunity:
Conducted Disturbance Immunity:
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity:
Surge Immunity:
Voltage Dip/Interrupting Immunity:
UL 61010-1 (listing)
CSA C22.2 No.1010-1
EN 61326, EN 61010-1, IEC 61010-1
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.
2
2
min., 3 times each in 6 directions
min., 3 times each in 6 directions
100 to 240 VAC, 50/60 Hz
24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 5 VA
24 VAC: 3 VA, 24 VDC: 2 W
Thermocouple input type:
Platinum resistance thermometer input type:
Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100
SPST-NO, 250 VAC, 3A (resistive load)
ON/OFF or 2-PID (with auto-tuning)
SPST-NO, 250 VAC, 1A (resistive load)
Digital setting using front panel keys
7-segment digital display (character height: 13.5 mm) and deviation indicators
• Setting change prohibit (key protection)
• Input shift
• Temperature unit change (°C/°F)
• Direct/reverse operation
• Temperature range, Sensor switching (K/J/L, Pt100/JPt100)
• Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models.
• Control period switching
• 8-mode alarm output
• Sensor error detection
−10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C
25% to 85%
−25 to 65°C (with no condensation or icing)
2
for 10 min each in X, Y, and Z directions
0 to input setting range full scale (°C or °F)
0.2°C or °F (fixed)
(±1% of PV or ±10°C, whichever is greater) ±1 digit max.
(±1% of PV or ±4°C, whichever is greater) ±1 digit max.
EN 55011 Group 1 Class A
EN 55011 Group 1 Class A
EN 61000-4-2: 4 kV contact discharge (level 2)
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
EN 61000-4-5: Power line:
EN 61000-4-11 0.5 cycle, 100% (rated voltage)
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.
8 kV air discharge (level 3)
10 V/m (900 MHz pulse modulated)
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
K, J, L
Pt100, JPt100
Normal mode 1 kV; Common mode 2 kV
E5CSV
3