JDZ-40E Cooper/Bussmann, JDZ-40E Datasheet

no-image

JDZ-40E

Manufacturer Part Number
JDZ-40E
Description
Fuses JDZ-40E
Manufacturer
Cooper/Bussmann
Type
Bussmann Unspecified Fuser
Series
JDZr
Datasheet

Specifications of JDZ-40E

Current Rating
40 Amps
Voltage Rating
8.3 KVolts
Termination Style
Cartridge
Product
Medium Voltage Fuse
Interrupt Rating
80000 Amps / 50000 Amps
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
JDZ-40E
Medium Voltage Fuses
Section Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
E-Rated Fues
For transformers & feeders . . . . . . . . . . . . . . . . . . . . . . .75
CL-14 & bolt-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
CL-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
For potential & small power transformers . . . . . . . . . . 78-79
R-Rated fuses for motor circuit protection . . . 80-82
British IEC fuses for motor circuit protection . . . 83
DIN IEC fuses for transformer protection . . . . . . 84
Potential transformer fuses . . . . . . . . . . . . . . . . . 85
British IEC fuses for oil-filled switchgear . . . . . . 86
Fast-acting fuses . . . . . . . . . . . . . . . . . . . . . . . . . 87
EEI-NEMA Type K & T and Type H & N fuses . . . 88
BBU Boric acid fuses . . . . . . . . . . . . . . . . . . . 89-90
Fuseclips for medium and high voltage fuses . . . 91
Page
71

Related parts for JDZ-40E

JDZ-40E Summary of contents

Page 1

... British IEC fuses for motor circuit protection . . . 83 DIN IEC fuses for transformer protection . . . . . . 84 Potential transformer fuses . . . . . . . . . . . . . . . . . 85 British IEC fuses for oil-filled switchgear . . . . . . 86 Fast-acting fuses . . . . . . . . . . . . . . . . . . . . . . . . . 87 EEI-NEMA Type K & T and Type H & N fuses . . . 88 BBU Boric acid fuses . . . . . . . . . . . . . . . . . . . 89-90 Fuseclips for medium and high voltage fuses . . . 91 ...

Page 2

... E-Rated fuses are used to protect feeder circuits, power transformers and potential transformers. E-Rated fuses have defined current response times specified by ANSI C37.46. E-Rated fuses 100A and below must melt in 300sec at an rms current within the range of 200% to 240% of the continuous current rating. E-Rated fuses above 100A must melt in 600sec at an rms current within the range of 240% to 264% of the continuous current rating of the fuse ...

Page 3

... Medium Voltage Fuses E-rated Fuses for Transformers and Feeders MV055 and MV155 Specifications Description: E-rated medium, voltage current- limiting fuses: for transformer and feeder protection. Dimensions: See Catalog Numbers table. Construction: Silver ribbon element surrounded by silica filler housed in a fiberglass tube and plated endcaps. An epoxy paint protects the fuse tube from the surrounding environment ...

Page 4

... Medium Voltage Fuses E-rated Fuses for Transformer & Feeders JCX, JCY, JCU, JCZ and JDZ Specifications Description: Indoor/enclosure E-rated medium voltage, current- limiting fuses for feeders and power transformers with blown fuse indication. Dimensions: See Catalog Numbers table. Construction: plated ferrules. ...

Page 5

... JCZ-125E 125 8300 JCZ-150E 150 8300 JCZ-200E 200 8300 JDZ-20E 20 8300 JDZ-25E 25 8300 JDZ-30E 30 8300 JDZ-40E 40 8300 JDZ-50E 50 8300 JDZ-65E 65 8300 JDZ-80E 80 8300 JDZ-100E 100 8300 JDZ-125E 125 8300 Recommended fuseclips: see page 91 - 1A0065, 9078A67G04, A3354730 General Notes: 1. All fuses are fitted with a striker pin which can be used for indication or tripping purposes. ...

Page 6

... Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes • 50/60Hz operating frequency make these fuses applicable world-wide Typical Applications • 5.0kV Transformer Primary Protection • ...

Page 7

... Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes • 50/60 Hz operating frequency make these fuses applicable world-wide Typical Applications • 15.0kV Transformer Primary Protection • ...

Page 8

... JCT-5E 5 15.5kV JCT-10E 10 15.5kV Fuse clip for 1.56 and 1.6 inch diameter fuses - 1A0835. Fuse clip for 0.81 inch diameter fuses - 1A1837. Data Sheet: 6002 For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa 78 Features and Benefits • Sized for retrofitting in existing hardware • ...

Page 9

... CAVH fuses are fitted with a striker pin for indication. Omit ‘H’ for non-indicating fuses. Fuseclip for 0.8 inch diameter fuses - 1A1837. Fuseclip for 1 inch diameter fuses - A3354705. Fuseclip for 1.6 inch diameter fuses - 1A0835. For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Ratings: Volts: — ...

Page 10

... Physically dimensioned for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Available with optional Cutler Hammer insertion and removal • Classified as back-up fuses for current-limited protection of medium voltage motor controllers Typical Applications • Medium Voltage Motor Controllers ...

Page 11

... Medium Voltage Fuses R-rated Fuses for Motor Circuit Protection Catalog Numbers: R-Rated; Indoor/Enclosure 2400V (See Figure 1) JCK-2R 70 2540 11.24 (285.5) JCK-3R 100 2540 11.24 (285.5) JCK-4R 130 2540 11.24 (285.5) JCK-5R 150 2540 11.24 (285.5) JCK-6R 170 2540 11.24 (285.5) JCK-9R ...

Page 12

... Medium Voltage Fuses R-rated Fuses for Motor Circuit Protection Catalog Numbers: R-Rated; Indoor/Enclosure 4800V — With Westinghouse Ampguard Hookeye (See Figure 1) JCL-A-2R 70 5080 15.76 (400.3) JCL-A-3R 100 5080 15.76 (400.3) JCL-A-4R 130 5080 15.76 (400.3) JCL-A-5R 150 5080 15.76 (400.3) JCL-A-6R ...

Page 13

... Medium Voltage Fuses British Standard Dimensioned IEC Fuses for Motor Circuit Protection The Cooper Bussmann range of motor fuses are designed to meet the specific requirements necessary for motor protection. During the starting cycle of direct on-line motors, the fuse elements will reach a considerably higher temperature than during normal operation ...

Page 14

... Recommended fuseclips for DIN style fuses – 270303, A3354745 see page 91. *Not compliant with VDE 0670, part 402. 1 -IR RMS Sym is 63kA 2 -IR RMS Sym is 40kA 3 -IR RMS Sym is 20kA Dimensions - In (mm) 1.77" ...

Page 15

... Basic Catalog Number Recommended Fuse Clips: 1” dia. - A3354705, 1.63” dia. - 1A0835, .819 dia. - 1A1837 Contact Cooper Bussmann for complete specifications on potential transformer fuses For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Ratings: E-Rated: — See single asterisk in Basic Catalog Numbers table Volts: — ...

Page 16

... For 6.6kV systems, 12kV fuses are recommended where possible in the interests of standardization. 4. Wherever possible, 10 inch long FO1 fuses are offered rather than equivalent 14 inch FO2 types. 5. The above recommendations are not generally applicable to transformers feeding motor circuits with starting currents in excess of the transformer full load current. In this event, please consult Cooper Bussmann ...

Page 17

... Medium Voltage Fuses Fast-acting Fuses HVA, HVB, HVJ, HVL, HVR, HVT, HVU, HVW & HVX Specifications Description: Medium voltage, non-time delay, fast-acting fuses. Dimensions: See Basic Catalog Numbers table. Ratings: Volts: — 1-10kV (See Basic Catalog Numbers table) Amps: — 1 ⁄ ...

Page 18

... Type N Fuses Type N fuses conform to previous NEMA standards and have been superseded by Type K and T links. Type N fuses are manufactured in the universal button design in ratings of 5 through 200A for use in NEMA standard dimensioned cutouts rated through 27kV. ...

Page 19

... BBU less susceptible to failure caused by vibration, corona corrosion and fuse element aging. The components are housed in a fiberglass reinforced resin tube with plated copper contacts. BBU fuses can directly replace competitive equivalent units. Element Vapor Rod withdraws, ...

Page 20

... E (Standard), K (Fast) and SE (Slow). Contact Cooper Bussmann for application details. Application Notes Low currents, usually referred to as overload currents, must be considered as BBU fuses have a rather low thermal capacity. They cannot carry overloads of the same magnitude/duration as motors and transformers of equal continuous currents. For this reason, the BBU fuse must be ...

Page 21

... Medium Voltage Fuses Fuseclips for Medium & High Voltage Fuses Recommended Fuseclips for Medium Voltage Fuses A3354710 2 (50.8) 3.749 1.979 2.009 A3354730 3 (76) 4.139 2.449 3.009 A3354745 1.77 (45) 3.50 2.50 1.77 Fuseclips are for single barrel applications only. Are not sold in pairs. ...