Page 1
U 164 20 6.5" 0.8" Description These extremely compact DC-DC converters incorporate all necessary input and output filtering, signalling, and protection features, which are required in the majority of applications. The converters provide important ...
Page 2
Voltage suppressor diodes and an independent second control loop protect the outputs against an overvoltage. The converters are designed using planar magnetics transformers and control circuits in hybrid technology. There are always ...
Page 3
Table 1b: Model types DP, EP Output nom o nom o max o nom [V] [W] [W] [V] 3.3 100 132 - 5.1 122 183 - 12 120 192 - 15 120 ...
Page 4
Part Number Description Input voltage nom 24 VDC ................................................................ B 48 VDC ................................................................ C 72 VDC ................................................................ D 110 VDC .............................................................. E 36 VDC ............................................................... G Series .................................................................................... P Number of outputs: Single output ........................................................ 1 ...
Page 5
Output Configuration The P Series allows high flexibility in output configuration to cover almost every individual requirement, by simply wiring outputs in parallel, in seriel independent configuration, as shown in the following diagrams. Parallel or serial operation ...
Page 6
Functional Description The power supplies are equipped with two independent flight-forward converters, switching 180° phase-shifted to minimize the ripple current at the input. They use primary and secondary control circuits in hybrid technology. The two converters, called "powertrains" (PT), ...
Page 7
Electrical Input Data General Conditions: – 25°C, unless T is specified A C – Sense lines connected directly at the connector, inhibit (28) connected to Vi– (32) – R input open Table 2a: Input data Input Characteristics ...
Page 8
Input Fuse and Reverse Polarity A fuse mounted inside the converter protects against further damage in case of a failure. The fuse is not user-accessible. Reverse polarity at the input will cause the fuse to blow. Table 3: Fuse ...
Page 9
Electrical Output Data General Conditions: – 25°C, unless T is specified – Sense lines connected directly at the connector, inhibit (28) connected to Vi– (32). – R input not connected Table 5a: Output data for ...
Page 10
Table 5c: Output data for double-output powertrains. General conditions as in table 5a Output Double-output powertrain Characteristics Conditions 1 V Output voltage nom V Worstcase output V – min voltage T ...
Page 11
Parallel and Series Connection The first outputs of power trains with equal nominal output voltage can be connected in parallel. Where available, we recommend ordering of option T. Any output can be connected in series with any other output. ...
Page 12
Double-output T1 + model 26 Vo2 S2+ S2– Out OK+ Vo2– Out OK– Vo1+ i S1+ Vi+ S1– Vi– Vo1– Double-output T1 model Vo2+ 26 S2+ Out OK+ S2– Vo2– Out OK– Vo1+ i S1+ Vi+ ...
Page 13
Fig tracking output V versus I (powertrain versus I (powertrain 2 ...
Page 14
Auxiliary Functions Primary Inhibit (Remote On / Off) The inhibit input enables (logic low, pull down) or disables (logic high, pull up or open-circuit) the output logic signal (TTL, CMOS) is applied. In systems consisting of several ...
Page 15
V Table 7a: R for V ; approximate values ( nom nom o nom [kΩ Ω Ω Ω Ω ] [kΩ Ω Ω Ω Ω ] ...
Page 16
Electromagnetic Compatibility (EMC) A metal oxide VDR together with an input fuse and a symmetrical input filter form an effective protection against Electromagnetic Immunity Table 9: Immunity type tests Phenomenon Standard Level Supply related RIA 12 B surge EN ...
Page 17
Electromagnetic Emissions All conducted emissions (fig. 20) have been according to IEC/EN 55022 (similar to EN 55011, much better values than requested by EN 50121-3-2, table 3.1). The limits in fig. 20 apply to quasipeak values, which are always ...
Page 18
Immunity to Environmental Conditions Table 10: Mechanical and climatic stress Test method Standard Cab Damp heat IEC/EN 60068-2-78 steady state MIL-STD-810D section 507.2 Kb Salt mist, cyclic IEC/EN 60068-2-52 (sodium chloride NaCl solution) Eb Bump IEC/EN 60068-2-29 (half-sinusoidal) MIL-STD-810D ...
Page 19
Mechanical Data The converters are designed to be inserted in a 19" rack acording to IEC 60297-3. Dimensions in mm. = ∅ 4.5 Fig. 22 Case Q04, weight app. 500 g Aluminium, fully enclosed, black finish and self cooling ...
Page 20
Safety and Installation Instructions Connector Pin Allocation The connector pin allocation table defines the electrical potentials and the physical pin positions on the H15 and H15S2 connector. Pin no. 26, protective earth leading pin to ensure that ...
Page 21
Installation Instructions These converters are components, intended exclusively for inclusion within other equipment by an industrial assembly process professionally competent person. Installation must strictly follow the national safety regulations in respect of the enclosure, mounting, creepage ...
Page 22
Safety of Operator-Accessible Output Circuits If the output circuit of a DC-DC converter is operator accessible, it shall be an SELV circuit according to the IEC/ EN 60950 related safety standards. The following table shows some possible installation configurations, ...
Page 23
Description of Options Option D: Out OK Monitor Option D monitors the state of the output error amplifiers on both power trains rather than the input voltage, output voltage, or the current limit. It signals a fault, when one ...
Page 24
Accessories A great variety of electrical and mechanical accessories are available: • Mating connectors including fast-on, screw, solder, or press-fit terminals • Front panels, system Schroff, for 19" rack in 3U configuration 4 TE (G04-Q04 (G05-Q04), or ...
Page 25
EC Declaration of Conformity Power-One, Inc.,740 Calle Plano, Camarillo, CA. 93012 USA We, declare under our sole responsibility that the products; Power Supply Model to which this declaration relates, is/are in compliance with the following document(s): Quality Standard(s): Directive: ...