FN3025HL-30-71 Schaffner EMC Inc, FN3025HL-30-71 Datasheet - Page 2

FILTER 3-PHASE ADV EMC/RFI 30A

FN3025HL-30-71

Manufacturer Part Number
FN3025HL-30-71
Description
FILTER 3-PHASE ADV EMC/RFI 30A
Manufacturer
Schaffner EMC Inc
Series
FN 3025r
Type
Filterr
Datasheet

Specifications of FN3025HL-30-71

Filter Type
Power Line
Voltage - Rated
300V, 520V
Current
30A
Mounting Type
Chassis Mount
Termination Style
Terminal Block
Product
Power Line Filters
Voltage Rating
520 VAC
Current Rating
30 A
Mounting Style
Chassis
Filtered
Yes
Frequency
DC to 60 Hz
Leakage Current
0.4 mA
Brand/series
FN 3025 Series
Current, Leakage
0.4 mA
Current, Rating
30 A
Dimensions
78 H × 50 W × 150 L mm
Frequency, Operating
DC to 60 Hz
Hipot Rating, Line To Ground
2000
Hipot Rating, Line To Line
2250
Ip Rating
IP00
Phase
3
Primary Type
AC
Schaffner Part Number
802-137
Voltage, Operating
520/300 VAC
Voltage, Rating
520/300 VAC
Wire Size
8-7 AWG
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Inductance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
802-137
817-1115
Filter selection table
Filter
FN 3025HL-10-71
FN 3025HL-20-71
FN 3025HL-30-71
FN 3025HL-50-72
FN 3025HP-10-71
FN 3025HP-20-71
FN 3025HP-30-71
FN 3025HP-50-72
FN 3026HL-10-71
FN 3026HL-20-71
FN 3026HL-30-71
FN 3026HL-50-72
FN 3026HP-10-71
*
**
Typical filter attenuation
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym; C = 0.1Ω/100Ω sym; D = 100Ω/0.1Ω sym
10 and 20A HL types
Installation
FN 3026HP-20-71
FN 3026HP-30-71
FN 3026HP-50-72
> Components
Calculated at rated current, 480VAC and cos phi = 0.8. The exact value depends upon the efficiency of the drive, the motor and the entire application.
Maximum leakage under normal operating conditions. Note: if two phases are interrupted, worst case leakage could reach up to 10 times higher levels (at 520VAC/60Hz).
> FN 3025 / FN 3026
Rated current
@ 50°C (40°C)
10 (10.7)
20 (21.4)
30 (32.1)
50 (53.5)
10 (10.7)
20 (21.4)
30 (32.1)
50 (53.5)
10 (10.7)
20 (21.4)
30 (32.1)
50 (53.5)
10 (10.7)
20 (21.4)
30 (32.1)
50 (53.5)
10 and 20A HP types
[A]
power rating*
Typical drive
[kW]
18.5
18.5
18.5
18.5
5.5
5.5
5.5
5.5
11
30
11
30
11
30
11
30
Leakage current**
@ 480VAC/50Hz
30 and 50A HL types
[mA]
0.4
0.4
0.4
0.4
2.5
2.5
2.5
2.5
0.4
0.4
0.4
0.4
2.5
2.5
2.5
2.5
@ 25°C/50Hz
Power loss
FN 3025/FN 3026 are delivered with closed
plastic covers and unfastened terminals. To
install the filter please proceed as follows:
n
n
n
n
n
n
10.5
10.5
10.5
10.5
[W]
4.8
6.2
7.0
4.8
6.2
7.0
4.8
6.2
7.0
4.8
6.2
7.0
Mount the filter on a metal surface with
four screws or snap it onto a TS 35 DIN-
rail.
First connect the green/yellow wire to the
earth stud of the filter.
Gently lift the two hinged plastic covers.
Connect phase wires with cable lugs by
pushing down and tightening the screws.
Please note the torque recommendation on
top of the filter.
Push the covers back into their locked
position to finish the filter installation.
30 and 50A HP types
Input/Output
connections
496-405F August 2009
-71
-71
-71
-72
-71
-71
-71
-72
-71
-71
-71
-72
-71
-71
-71
-72
Page 2/3
Weight
0.52
0.52
0.54
0.93
0.52
0.52
0.54
0.93
0.56
0.56
0.58
0.98
0.56
0.56
0.58
0.98
[kg]