FN258-130-35 Schaffner EMC Inc, FN258-130-35 Datasheet

FILTER 3-PHASE EMC/RFI 130A

FN258-130-35

Manufacturer Part Number
FN258-130-35
Description
FILTER 3-PHASE EMC/RFI 130A
Manufacturer
Schaffner EMC Inc
Series
FN 258r
Type
Filterr
Datasheet

Specifications of FN258-130-35

Filter Type
Power Line
Voltage - Rated
277V, 480V
Current
130A
Mounting Type
Chassis Mount
Termination Style
Terminal Block
Current Rating
130A
Voltage Rating
480V
Leakage Current Max
30mA
Inductance
0.6µH
Mounting Style
Chassis
Filtered
Yes
Frequency
50 Hz
Leakage Current
30 mA
Application
For inverters, servo drives, machinery, machine tools, industrial automation, General purpose
Brand/series
FN 258 Series
Current, Leakage
30 mA
Current, Rating
130 A
Dimensions
240 H × 110 W × 439 L mm
Hipot Rating, Line To Ground
2650
Hipot Rating, Line To Line
2100
Ip Rating
IP20
Phase
3
Primary Type
AC, Inverter/PDS, Multi-Stage
Resistance
1.5 Megaohms
Schaffner Part Number
292-726
Standards
UL Recognized, CSA Certified, IEC Approved
Voltage, Operating
480/277 VAC
Voltage, Range
480 VAC
Voltage, Rating
480 VAC
Wire Size
1/0 AWG
Hipot Test Voltage
P → E 2900 VDC; P → P 2800 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
292-726

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
FN258-130-35
Manufacturer:
SCHAFFNE
Quantity:
2
Technical specifications
Maximum continuous operating voltage:
Operating frequency:
Rated currents:
High potential test voltage:
Protection category:
Overload capability:
Temperature range (operation and storage):
Flammability corresponding to:
Design corresponding to:
MTBF @ 50°C/400V (Mil-HB-217F):
Features and benefits
Book-style EMC/RFI fi lter for three-phase
inverters and power drive systems
FN 258 range of filters provides state-of-
the-art EMI attenuation based on an
innovative multi-stage filter topology.
They help to ensure compliance with
Class A or even Class B limits.
The slim book-style shape allows a
convenient and space-saving installation
next to inverters and motor drives.
With 480VAC rating and filter modules
from 7 to 250A, FN 258 are ready for the
most diverse applications worldwide.
FN 258HV filters up to 130A are designed
for 690VAC distribution networks.
3x 480/277VAC (FN 258, FN 258L, FN 258P)
3x 690/400VAC (FN 258HV, FN 258HVIT)
dc to 60Hz
7 to 250A @ 50° (480V filters)
7 to 130A @ 50° (690V filters)
P –> E 2650VDC for 2 sec (480V filters)
P –> P 2100VDC for 2 sec (480V filters)
P –> E 3100VDC for 2 sec (690V filters)
P –> P 3000VDC for 2 sec (690V filters)
IP20
4x rated current at switch on,
1.5x rated current for 1 minute, once per hour
-25°C to +100°C (25/100/21)
UL 94V-2 or better
UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
220,000 hours
Industry standard EMC solution for
three-phase PDS filtering
Slim space-saving book-style housing
Solid safety connector blocks or optional
wire output connections
Excellent attenuation performance
HV versions for up to 690VAC
HVIT versions for IT distribution networks
P/L versions with low leakage current
FN 258HVIT filters up to 130A meet the
special requirements for the application in
industrial 690VAC IT distribution
networks.
FN 258L and FN 258P filters help to fulfill
tough requirements in respect of leakage
current limitation and provide an excellent
solution to overcome problems with
nuisance tripping of sensitive earth
leakage detectors.
3-phase fi lters
FN 258
Approvals
UL / CSA: FN 258 up to 180A (ex. -180-07)
UL / CSA: HV and HVIT up to 600VAC
Typical electrical schematic
Note: HVIT versions without discharge resistor to ground.
Typical applications
Three-phase variable speed drives and
power drive systems (PDS)
IT power distribution networks
(FN 258HVIT)
Applications comprising energy conversion
devices (inverters, converters)
Process automation equipment
Three-phase power supplies and UPS
Applications with low-leakage current
requirements (FN 258L and FN 258P)

Related parts for FN258-130-35

FN258-130-35 Summary of contents

Page 1

... P –> E 2650VDC for 2 sec (480V filters) P –> P 2100VDC for 2 sec (480V filters) P –> E 3100VDC for 2 sec (690V filters) P –> P 3000VDC for 2 sec (690V filters) IP20 4x rated current at switch on, 1.5x rated current for 1 minute, once per hour -25° ...

Page 2

... Per CISPR 17 50Ω/50Ω sym 50Ω/50Ω asym 0.1Ω/100Ω sym 100Ω/0.1Ω sym 7 to 30A types 42 to 100A types Note: typical attenuation performance of FN 258 standard filters. The behavior of FN 258HV, FN 258HVIT, FN 258P and FN 258L may be slightly different. Leakage current*** Power loss @ 440VAC/50Hz @ 25° ...

Page 3

... X* AWG 16 AWG 14 Y* 300 ±10 300 ± Filters with output wire connections (-07) only. All dimensions in mm; 1 inch = 25.4mm Tolerances according: ISO 2768 22768-m Filter input/output connector cross sections -29 Solid wire 6mm² Flex wire 4mm² AWG type wire AWG 10 Recommended torque 0 ...

Related keywords