Specifications
■ Ratings
Note: 1. DC power supply models require a control power supply capacity of approximately 1 A per Unit when power is turned ON. Particular
16
Supply voltage
Allowable power supply voltage
range
Power consumption
(See note 1.)
Current consumption
Input
External power supply
Event inputs
Output ratings
(depends on
the model)
Display method
Main functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Altitude
Accessories
2. For K3HB-series DeviceNet models, use only the DeviceNet Connector included with the product. The crimp terminals provided are for
attention is required when using two or more DC power supply models. The OMRON S8VS-series DC Power Supply Unit is
recommended.
Thin Cables.
Up/Down Counting Pulse Indicator
Hold input
Reset input
Bank input
Relay output
Transistor output
Linear output
100 to 240 VAC, 24 VAC/VDC, DeviceNet power supply: 24 VDC
85% to 110% of the rated power supply voltage, DeviceNet power supply: 11 to 25 VDC
100 to 240 VAC: 18 VA max. (max. load)
24 VAC/DC: 11 VA/7 W max. (max. load)
DeviceNet power supply: 50 mA max. (24 VDC)
No-voltage, voltage pulse, open collector
12 VDC±10% 80 mA
NPN open collector or no-voltage contact signal
ON residual voltage: 2 V max.
ON current at 0
Max. applied voltage: 30 VDC max.
OFF leakage current: 0.1 mA max.
250 VAC, 30 VDC, 5 A (resistive load)
Mechanical life expectancy: 5,000,000 operations, Electrical life expectancy: 100,000 operations
Maximum load voltage: 24 VDC, Maximum load current: 50 mA, Leakage current: 100 A max.
Linear output 0 to 20 mA DC, 4 to 20 mA:
Linear output 0 to 5 VDC, 1 to 5 VDC, 0 to 10 VDC:
(1 V or less: ±0.15 V; not output for 0 V or less)
Negative LCD (backlit LED) display
7-segment digital display (Character height: PV: 14.2 mm (green/red); SV: 4.9 mm (green))
Scaling function, measurement operation selection, output hysteresis, output OFF delay, output test, display value
selection, display color selection, key protection, bank selection, display refresh period, maximum/minimum hold, re-
set
25% to 85%
2,000 m max.
Watertight packing, 2 fixtures, terminal cover, unit stickers, instruction manual. DeviceNet models also include a De-
viceNet connector (Hirose HR31-5.08P-5SC(01)) and crimp terminals (Hirose HR31-SC-121) (See note 3.)
10 to 55 C (
25 to 65 C (
Load: 500
Load: 5 k
with no icing or condensation
with no icing or condensation
max, Resolution: Approx. 10,000, Output error: ±0.5% FS
max, Resolution: Approx. 10,000, Output error: ±0.5% FS
: 4 mA max.
K3HB-C
)
)