CONTROL TEMP DGTL VOLT OUT 24V

E5GN-Q1TD AC/DC24

Manufacturer Part Number
E5GN-Q1TD AC/DC24
Description
CONTROL TEMP DGTL VOLT OUT 24V
Manufacturer
Omron
Type
Digital Temperature Controllerr

Specifications of E5GN-Q1TD AC/DC24

Analog / Digital
Digital
Control Method
ON/OFF
Voltage Rating
24 VAC, 24 VDC
Mounting
Panel
Display Type
11-Segment, 4 Digit
Size
99 mm x 48 mm x 35 mm
Features
Compatible with Support Software (CX-Thermo version 4.2 or higher)
Input Type
Thermocouple
Output Type
Voltage
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Temperature Accuracy ±
0.2%
Output Voltage Max
13.8VDC
Output Voltage Min
10.2VDC
Meter Function
Thermocouple
Thermocouple Type
J, K, T, E, L, U, N, R, S, B, W, PLII
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
E5GNQ1TDACDC24
Z3048
■ Communications Specifications
Note: The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
Wiring Terminals
• The voltage output (control output) is not electrically insulated from
6
Transmission path connection
Communications method
Synchronization method
Baud rate
Transmission code
Data bit length (see note)
Stop bit length (see note)
Error detection
Flow control
Interface (see note)
Retry function
Communications buffer
Communication Model
Standard Model
the internal circuits. When using a grounding thermocouple, do not
connect the control output terminals to the ground. If the control
output terminals are connected to the ground, errors will occur in
the measured temperature values as a result of leakage current.
Two input power supplies are available:
100 to 240 VAC or 24 VAC/VDC (no polarity).
Digital Temperature Controllers
Voltage output
Voltage output
Relay output
Relay output
Input power supply
Input power supply
1
2
Control output
Control output
3
3
12 VDC
21 mA
12 VDC
21 mA
4
4
Multiple points
RS-485 (two-wire, half duplex)
Start-stop synchronization
1,200/2,400/4,800/9,600/19,200 bps
ASCII
7 or 8 bits
1 or 2 bits
Vertical parity (none, even, odd)
Frame check sequence (FCS): with SYSWAY
Block check character (BCC): with CompoWay/F
Not available
RS-485
Not available
40 bytes
B
5
Alarm output/control output 2/input error output
RS-
( )
Host
485
E5GN
A
6
( )
A
7
Analog input
8
B
Analog input
B
9
TC
Pt
• Standard insulation is applied to the power supply I/O sections. If
reinforced insulation is required, connect the input and output ter-
minals to a device without any exposed current-carrying parts or to
a device with standard insulation suitable for the maximum operat-
ing voltage of the power supply I/O section.
Thermocouple
Infrared temperature sensor
Temperature-resistance
thermometer
Two input power supplies are available:
100 to 240 VAC or 24 VAC/VDC (no polarity).