IMI04160 Red Lion Controls, IMI04160 Datasheet - Page 2

no-image

IMI04160

Manufacturer Part Number
IMI04160
Description
PNL METER DIGITAL 115/230VAC
Manufacturer
Red Lion Controls
Series
IMIr
Type
Rate Meterr
Datasheet

Specifications of IMI04160

Measuring Range
0 ~ 50kHz
Display Style
Red Characters, Black Background
Display Type
LED
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
6
Display Digits - Height
0.560" (14.22mm)
Backlight
Without
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
115/230VAC
Lead Free Status / RoHS Status
Vendor undefined / Vendor undefined
Other names
Q4248729
SPECIFICATIONS (Cont’d)
4. SIGNAL INPUT: (Cont’d)
5. DISPLAY COMBINATIONS: Rate/Total or Rate/Efficiency.
6. RATE/EFFICIENCY:
7. TOTALIZER: Programmable time-base, scale factor (0.001 to 100.000) and
8. PROGRAM DISABLE (PGM.DIS.): Used with programmable lockout
9. E1-CON & E2-CON: External remote inputs which allow activation of
10. ENVIRONMENTAL CONDITIONS:
11. DC OUT: +12 VDC ±25% @ 60 mA max.
12. SERIAL COMMUNICATIONS (Optional):
13. ALARMS (Optional):
14. ANALOG OUTPUT (Optional): Digital scaling and offseting
15. LINEARIZER/PEAK/VALLEY: 9-segment multiple slope scaling for
16. CERTIFICATIONS AND COMPLIANCES:
Accuracy: 0.01% ±1 digit
Min. Input Frequency: 0.01 Hz
Programmable Update Time Range: 0.2 secs to 100.0 secs
low-end cutout. Max. response time 0.2 secs.
menus to limit operator entry when active. Connect to common (TBA #7) to
activate.
various functions (reset total, peak indicator mode, trigger mode, etc).
V
Operating Temperature: 0 to 50°C
Storage Temperature: -40 to 80°C
Operating and Storage Humidity: 85% max. RH (non-condensing) from
Altitude: Up to 2000 meters
Type: Bi-directional 20 mA current loop, 20 mA source provided on transmit
Baud Rate: programmable 300 to 9600
Maximum address: 99 (Actual number in a single loop is limited by serial
Data Format: 10 bit frame, Odd parity (one start bit, 7 data bit, one odd
Serial Hardware Specifications:
Response Time: 0.2 sec min.
Solid State: Two, isolated, sinking open collector NPN transistors acting in
Relays:
Type: Form C (2)
Max. Rating: 5 Amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP
Relay Life Expectancy: 100,000 cycles at Max. load Rating. (As load level
4 to 20 mA:
0 to 10 VDC:
non-linear inputs. Peak and Valley recording.
SAFETY
EN 61010-1, IEC 1010-1
Safety requirements for electrical equipment for measurement, control, and
laboratory use, Part 1
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. Metal bezel of unit connected with ground lead from rear bezel screw to
2.Self-recoverable loss of performance during EMI disturbance at 10 V/m:
IL
0°C to 50°C.
loop. (Powers up to 7 units in a loop with internal current source).
hardware specifications).
parity bit, and one stop bit).
SO - Output Transistor Rating: V
SI - Input Diode Rating: V
parallel with relays.
V
@ 120 VAC (inductive load). The operate time is 5 msec nominal and the
release time is 3 msec nominal.
decreases, life expectancy increases.)
Accuracy: 0.1% of full scale
Resolution: 12 bits
Compliance Voltage: 10 VDC (500 Ω max. loop impedance)
Accuracy: ±(0.1% of reading +35 mV)
Resolution: 12 bits
Min. Load Resistance: 10 KΩ (1 mA max.)
metal mounting panel.
Analog output signal may deviate during EMI distrubance.
For operation without loss of performance:
LOGIC: Sets input trigger level.
NPN O.C.: Provides internal 3.9 KΩ pull-up resistor to +12 VDC.
= 0.8 V
CE
Trigger Level: +2.5V with 30 mV hysteresis.
I
V
mA.
Note: This will allow up to 28 units max. in each loop.
Note: The compliance voltage rating of the source must be greater than
SNK
MAX
= 1V
the sum of the voltage drops around the loop. (Typically a 30 VDC
powered source would be capable of operating between 18 and 22
units in a loop.)
= 3 mA MAX @ 12 VDC
MAX
MAX
IN = 28 VDC
; V
@ 100 mA max.; V
IH
= 2.0 V
MIN
F
= 1.25 V TYP; 1.5 V
; Response Time = 0.2 sec max.
OH
MAX
= 30 VDC max.
= 30 VDC, V
MAX
SAT
= 1 V
MAX
at 20
2
17. CONSTRUCTION: Die-cast metal front bezel that meets NEMA 4/IP65
18. CONNECTION: Removable terminal blocks.
19. WEIGHT: 1.2 lbs (0.5 kg)
SECONDARY DISPLAY TOTALIZATION OR
EFFICIENCY
input rate efficiency.
the programmable time base and scale factor values. A low-end cutout can be
programmed to stop totalization if desired. The Efficiency display will indicate
the current percentage of the input signal as compared to the programmed
target value.
programmed independent of the input rate signal. The totalizer may be reset via
a remote input (E1-CON or E2-CON) or by the front panel buttons. At loss of
power to the indicator, the contents of the totalizer are saved.
LINEARIZER/PEAK & VALLEY DETECTION
to construct linear segments to linearize the input signal. A maximum of nine
segments are available.
(valley) and the highest reading (peak), automatically, for later recall. This
information is valuable in monitoring the limits of the process over any length
of time since these values are stored at power-down to span over shifts, days,
etc. An external input can be programmed to reset or engage the unit into a
peak/valley reading indicator. Additionally, the peak and valley can be viewed
and reset from the front panel, if so programmed.
ISOLATED SERIAL COMMUNICATIONS OPTION
that can be connected to a printer, a computer, a terminal, or a controller to suit
many data-polling or automatic operation applications. The indicator responds to
a host of commands, which include change alarm value, reset totalizer, and
transmit input rate value. Two loops are required for all hook-ups, a transmit loop
and a receive loop. An internal 20 mA source is provided with the serial option.
Additionally, multiple units and other Red Lion Controls instruments can be
serially addressed, with a maximum address capability of 99 units.
ISOLATED ALARM OPTION
terminals. Six of these are for the two Form-C relays and the other three are the
two open collector transistors, which act in parallel with the relays. The two
alarms are completely independent with programmable values, hysteresis
(deadband), high or low acting, ON/OFF delay, auto or manual reset, triggering
from input rate or total/efficiency, and tracking one another, if desired. If the
alarms are programmed to latch (manual reset), then they will have to be reset
either by the front panel buttons or remote input (E1-CON or E2-CON). The
alarms can be made to activate external alarms, control valves, etc.
Refer to the EMC Installation Guidelines section of the manual for additional
requirements for indoor use when properly installed. Installation Category II,
Pollution Degree 2. Case body is black, high impact plastic (panel gasket and
mounting clips included).
The secondary display can be programmed to indicate either totalization or
The Totalizer totals (adds) input pulses and displays the result according to
The decimal point position of the totalizer or efficiency display is
The linearizer feature is a series of programmable scaling points that are used
The peak/valley detection feature will indicate and record the lowest reading
The serial communication option is a half-duplex, two-way 20 mA current loop
The alarm option consists of an additional printed circuit board with nine
Immunity to EN 50082-2
Electrostatic discharge
Electromagnetic RF fields
Fast transients (burst)
RF conducted interference
Power frequency magnetic fields
Simulation of cordless telephones
Emissions to EN 50081-2
RF interference
information.
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)
I./O and power cables are routed in metal conduit connected to earth ground.
Install power line filter, RLC#LFIL0000 or equivalent
EN 61000-4-2 Level 2; 4 Kv contact
EN 61000-4-3 Level 3; 10 V/m
EN 61000-4-4 Level 4; 2 Kv I/O
EN 61000-4-6 Level 3; 10 V/rms
EN 61000-4-8
ENV 50204
EN 55011
Level 3; 8 Kv air
80 MHz - 1 GHz
Level 3; 2 Kv power
150 KHz - 80 MHz
Level 4; 30 A/m
Level 3; 10 V/m
900 Mhz ±5 MHz
200 Hz, 50% duty cycle
Enclosure class A
Power mains class A
2
1