SPECIFICATION
MODEL
OUTPUT
INPUT
PROTECTION
FUNCTION
ENVIRONMENT
SAFETY &
EMC
(Note 4)
OTHERS
NOTE
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
OVER VOLTAGE
OVER TEMPERATURE
DC OK REALY CONTACT RATINGS (max.)
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
EMS IMMUNITY
MTBF
DIMENSION
PACKING
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER
RIPPLE & NOISE (max.)
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
120W Single Output Industrial DIN RAIL with PFC Function
Note.6
Note.7
Note.3
Note.2
SDR-120-12
180W (3 sec.)
1500ms, 60ms/230VAC
20ms/230VAC
88 ~ 264VAC
47 ~ 63Hz
95
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
12V
10A
0 ~ 10A
120W
15A
100mVp-p
12 ~ 14V
Normally w
>150% rated power, constant current limiting with auto-recovery within 3 seconds and shut down o/p voltage after 3 seconds
14 ~ 17V
Protection type : Shut down o/p voltage, re-power on to recover
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
-25 ~ +70
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508 TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level,
criteria A, SEMI F47, GL approved
289.9Khrs min.
40*125.2*113.5mm (W*H*D)
0.67Kg; 20pcs/14.4Kg/1.16CUFT
0.93/230VAC
89%
1.4A/115VAC
35A/115VAC
<1mA / 240VAC
1.0%
0.5%
1.0%
0.03%/
5
,
(TSW : detect on heatsink of power switch)
orks within 110 ~ 150% rated output power for
(0 ~ 50
(Refer to output load derating curve)
I/P-FG:1.5KVAC
124 ~ 370VDC
70A/230VAC
MIL-HDBK-217F (25 )
0.96/115VAC at full load
0.7A/230VAC
20ms/115VAC at full load
30
00ms, 60ms/115VAC
O/P-FG:0.5KVAC
SDR-120-24
24V
5A
0 ~ 5A
120W
7.5A
100mVp-p
24 ~ 28V
91%
29 ~ 33V
1.0%
0.5%
1.0%
at full load
more than 3
O/P-DC OK:0.5KVAC
seconds
PQ
and then shut down o/p voltage
GL
SDR-120
SDR-120-48
48V
2.5A
0 ~ 2.5A
120W
3.75A
120mVp-p
48 ~ 55V
90.5%
56 ~ 65V
1.0%
0.5%
1.0%
File Name:SDR-120-SPEC 2010-12-07
series