RCP-1UT Mean Well, RCP-1UT Datasheet
RCP-1UT
Specifications of RCP-1UT
Related parts for RCP-1UT
RCP-1UT Summary of contents
Page 1
... Note.7) RCP-1000-48 48V 21A 0 ~ 21A 1008W 300mVp-p 46.3 ~ 49.7V 1.0% 0.5% 0.5% 89% 5.5A/230VAC 11A/115VAC 5.5A/230VAC 52.8 ~ 64. (TSW2) detect on heatsink of power diode File Name:RCP series-SPEC 2010-10- ...
Page 2
... Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 (EN50082-2), heavy industry level, criteria A MTBF 43.4Khrs min. OTHERS DIMENSION 295*127*41mm (L*W*H) 1.91Kg; 6pcs/12.5Kg/1.04CUFT PACKING SPECIFICATION - Rack System MODEL RCP-3K1U -12 MODULE RCP-1000-12 RACK RCP-1UI or RCP-1UT OUTPUT VOLTAGE 12V OUTPUT MAX. OUTPUT CURRENT 180A MAX. OUTPUT POWER 2160W Note.6 VOLTAGE RANGE 90 ~ 264VAC Note.5 FREQUENCY RANGE 47 ~ 63Hz INPUT 8 ...
Page 3
... PFC fosc : 110KHz PWM fosc : 90KHz RECTIFIERS ORING & DIODE FILTER CURRENT SHARE DETECTION CIRCUIT FUNCTION O.V.P. OPTIONAL RECTIFIERS CONTROL ON/OFF DETECTION CIRCUIT RECTIFIERS & FILTER File Name:RCP series-SPEC 2010-10- Unit: CURRENT SHARE V_TRIM ON/OFF AC_OK DC_OK T_ALARM AUX POWER (5V/0.3A) AUX GND ...
Page 4
... Front End Power System Mechanical Specification (Rack System RCP-1UT RCP-1UI 22 Module C 10 ADDRESS SWITCH - ADDRESS SWITCH - A 440 Air flow direction Module 466.2 483 Case No. 959A 14 1 CN500 + CN500 + Module File Name:RCP series-SPEC 2010-10- Unit:mm Fig1 25 13 Mounting Bracket 22 ...
Page 5
... T-ALARM ON/OFF-C 20 82Vrms +/-4V. High : when the input voltage in 82Vrms +/-4V. 80%+/-5% below the thermal shut down limit. Static Characteristics 100 Assignment Pin No. Assignment AC-OK DC-OK V-TRIM-C SCL 23 T-ALARM-C SDA 100 115 INPUT VOLTAGE (VAC) 60Hz File Name:RCP series-SPEC 2010-10- Ta=25 264 ...
Page 6
... ON/OFF A ON/OFF B ON/OFF C RCP-1U +V LOAD -V Sense lines should be twisted in pairs Vout (%) 110 108 106 104 102 100 1.2M NC min. 0. Between ON/OFF and - Open Short NC 300K 120K 62K 31K 13K File Name:RCP series-SPEC 2010-10- Output OFF min. 0.1W ...
Page 7
... When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm *Signal between function pin and "-S" Bus Interface Option 5.1 Addressing(A0,A1,A2) The DIP switch down position is logic level "1" and the up position is level "0". Address are applicable when modules RCP-1000 I C function are used OFF ...
Page 8
... Input power fail Output voltage is less than specification Internal temperature is over 60 . PSU turns on Temperature exceeds nominal operating limit. PSU turns off Failure of an internal fan Not used Not used Not used Output Voltage Output Current Internal Temperature File Name:RCP series-SPEC 2010-10- R/W ...