E5CN-Q2MT500AC100240 Omron Automation, E5CN-Q2MT500AC100240 Datasheet
E5CN-Q2MT500AC100240
Specifications of E5CN-Q2MT500AC100240
Related parts for E5CN-Q2MT500AC100240
E5CN-Q2MT500AC100240 Summary of contents
Page 1
... This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156) E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158) ( mm) 48 × ...
Page 2
... Temperature input Analog input 1 control output Option Units E53-CN@@@ Applicable Controller CN: E5CN or E5CN-H 2. Function 1 Blank: None Q: Control output 2 (voltage for driving SSR) P: Power supply for sensor 3. Function 2 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection ...
Page 3
... VAC/VDC (current/voltage) 100 to 240 VAC Thermocouple or Silver Resistance thermometer 24 VAC/VDC Option Units One of the following Option Units can be mounted to provide the E5CN with additional functions. Communications 3-phase heater burnout/SSR failure/ RS-485 Heater overcurrent detection Heater burnout/SSR failure/Heater overcurrent detection Communications RS-485 ...
Page 4
... Voltage output (for driving SSR) E5CN-Q2TU Current output Relay output 1 Voltage output (for driving SSR) E5CN-Q1LU Current output Analog (current/voltage) Relay output 2 Voltage output (for driving SSR) E5CN-Q2LU Current output Relay output None Voltage output (for driving SSR) E5CN-QTDU Current output Relay output Thermocouple or resistance 1 ...
Page 5
... E58-CIFQ1 Terminal Cover Connectable models Terminal block models Model E53-COV17 Note: The Terminal Cover comes with the E5CN-@@@-500 models. Waterproof Packing Model Y92S-29 Note: The Waterproof Packing is included with the Controller only for models with terminal blocks. Current Transformers (CTs) ...
Page 6
... model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage 100 to 240 VAC: 7.5 VA (max.) (E5CN-R2T at 100 VAC: 3.0 VA) E5CN Power 24 VAC/VDC: 5 VA/3 W (max.) (E5CN-R2TD at 24 VAC: 2.7 VA) consump- 100 to 240 VAC (max ...
Page 7
... JPt100: JIS C 1604-1989, JIS C 1606-1989 Pt100: JIS C 1604-1997, IEC 751 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) Voltage E5CN/E5CN-U Infrared temperature Analog sensor input 115 140 120 70°C 165 260 °C °C ° ...
Page 8
... E5CN/E5CN-U Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will output of the alarm selected from the following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent ...
Page 9
... Non-volatile memory (number of writes: 1,000,000 times) Setup Tool CX-Thermo version 4.0 or higher Provided on the bottom of the E5CN. Use this port to connect a computer to the E5CN when using the Setup Tool. An Setup Tool port E58-CIFQ1 USB-Serial Conversion Cable is required to connect the computer to the E5CN. ✽6 Approved UL 61010-1, CSA C22 ...
Page 10
... ON, and the output assigned to the alarm 1 function will turn ON if the heater current is higher than the set value (i.e., heater overcurrent detection current value). Electrical Life Expectancy Curve for Relays (Reference Values) 500 300 100 E5CN 250 VAC, 30 VDC 3 (resistive load) cosφ ...
Page 11
... USE B Input power supply B • 100 to 240 VAC TC/Pt universal input • 24 VAC/VDC (no polarity) E5CN/E5CN-U A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is sent to the output to which the alarm 1 function is assigned. E53-CNP03N2 Communications (RS-485) and External Power Supply ...
Page 12
... E5CN/E5CN-U Nomenclature E5CN E5CN-U The front panel is the same for the E5CN and E5CN-U. Operation indicators Dimensions E5CN Terminal Models 48 × Waterproof Packing (Accessory) E5CN-U Plug-in Models 48 × Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ1 14 Temperature unit Level Key Mode Key ...
Page 13
... E54-CT3 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Two, M3 (depth: 4) Maximum continuous heater current: 120 A (50/60 Hz) (Maximum continuous heater current for the Temperature Controller is 50 A.) Number of windings: 400±2 Winding resistance: 8±0.8 Ω Armature Lead E5CN/E5CN-U 100 ∞ 10 Distortion 1 kΩ factor 10 100 mV 100 Ω ...
Page 14
... Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets Protective Cover for finger protection (Y92A-48G) is also available. 16 4.7 69.6 to 77.6 72 × 72 Panel ( mm) 72 × × 48 2.2 4.7 77.3 (to back of E5CN) Terminal Layout/Internal Connections 3 4.5 7.8 (Top View 35.4 Two ...