PMPU Macromatic, PMPU Datasheet

no-image

PMPU

Manufacturer Part Number
PMPU
Description
Relay; E-Mech; Phase Monitor; SPDT; Cur-Rtg 10A; Ctrl-V 208-480V; Vol-Rtg 240/30AC/DC
Manufacturer
Macromatic
Datasheet

Specifications of PMPU

Brand/series
PMP Series
Contact Form
SPDT
Current, Rating
10 A
Display Type
LED
Function
Phase Monitor
Mounting Type
Socket
Number Of Pins
8
Relay Type
Electro Mechanical
Release Time
1 to 300 Sec.
Standards
cULus, UL, CE
Temperature, Operating
-28 to +60 °C
Termination
Plug-In
Voltage, Control
480 V
Voltage, Rating
240⁄30 VAC⁄VDC
Universal Voltage
One Unit Works on Any 208-480 V System
Temperature
–28° to +55°C
Lead Free Status / Rohs Status
RoHS Compliant part
u
u
u
u
u
u
u
u
PHASE MONITOR RELAYS
Phase Loss, Phase Reversal, Phase
Unbalance, and Under/Over Voltage
PMP Series Plug-in
12
Universal voltage range of
208-480V on PMPU provides
the flexibility to cover a
variety of applications with
one unit
Protects against phase loss,
phase reversal, phase
unbalance, undervoltage and
overvoltage
Variety of user-selectable
and adjustable settings for
the ultimate in three-phase
protection
Automatic or Manual Reset
Multi-Color LED indicates
normal condition and defines
fault to simplify troubleshoot-
ing
Compact plug-in case
utilizing industry-standard 8
pin octal socket
10A SPDT output contacts
(with appropriate socket)
*
n See Page 16 for Sockets & Accessories.
The PMP Series Phase Monitor Relays utilize a microprocessor-based design to provide
protection against phase loss, phase reversal, phase unbalance, undervoltage and
overvoltage. The PMPU is a universal voltage product that works on any three-phase
system voltage from 208-480V (a separate 120V version is available). These devices are
designed to be compatible with most Wye or Delta systems. In Wye systems, a connection
to a neutral is not required. PMP Series products protect against unbalanced voltages or
single phasing regardless of any regenerative voltages.
The relay is energized when the phase sequence and all voltages are correct. Any one of
five fault conditions will de-energize the relay. As standard, re-energization is automatic
upon correction of the fault condition. Manual reset is available if a momentary N.C. switch
is wired to the appropriate terminals. A multi-color LED indicates normal condition and also
provides specific fault indication to simplify troubleshooting.
The PMP Series offers a variety of user-adjustable settings. The percent phase unbalance
is adjustable from 2-10%, and also has a “Disable” setting for those applications where
poor voltage conditions could cause nuisance tripping. The undervoltage drop-out can be
set at 80-95% of operating voltage (overvoltage setting is fixed at 110% of nominal). The
adjustable time delay drop-out on undervoltage (0.1-20 seconds) eliminates nuisance
tripping caused by momentary voltage fluctuations. There is also an adjustable time delay
(1-300 seconds) on both power up and restart after a fault has been cleared.
Requires a 600V-rated socket when used on system voltages greater than 300V.
MOUNTING
Plug-in
STYLE
OPERATING
VOLTAGE
208-480V
50/60 Hz
120V
PRODUCT
NUMBER
PMP120
PMPU *
WIRING/SOCKET n
DIAGRAM 104
8 Pin Octal
70169-D
Revised: 11/07

Related parts for PMPU

PMPU Summary of contents

Page 1

... The PMP Series Phase Monitor Relays utilize a microprocessor-based design to provide protection against phase loss, phase reversal, phase unbalance, undervoltage and overvoltage. The PMPU is a universal voltage product that works on any three-phase system voltage from 208-480V (a separate 120V version is available). These devices are designed to be compatible with most Wye or Delta systems ...

Page 2

... Application Data & Dimensions Hysteresis Load (Burden): Less than 3VA Temperature: -28 Mounting: Uses an 8 pin octal socket. Requires a 600V-rated socket when used on system voltages greater than 300V (Macromatic Product Number 70169-D--see Page 16). Indicator LED: LED Status Green Steady Green Flashing ...