405A100F1X ATC Diversified Electronics, 405A100F1X Datasheet - Page 3

no-image

405A100F1X

Manufacturer Part Number
405A100F1X
Description
Relay; E-Mech; Timing; On Delay; SPDT; Cur-Rtg 10A; Ctrl-V 24-240/24AC/DC; Socket Mnt
Manufacturer
ATC Diversified Electronics
Datasheet

Specifications of 405A100F1X

Brand/series
405A Series
Contact Form
SPDT
Current, Rating
10 A
Function
Timing
Mounting Type
Socket
Number Of Pins
8
Power, Rating
240 VA
Relay Type
Electro Mechanical
Standards
cULus, CSA, CE
Termination
Plug-In
Timer Type
On Delay
Timing Range
1 or 10 sec.⁄min.⁄hrs.
Voltage, Control
240⁄24 VAC⁄VDC
Voltage, Rating
250⁄30 VAC⁄VDC
Timing Ranges
1 and 10 Sec, Min., Hours
Universal Power Supply
24-240 VAC and 24 VDC
• ON-Delay version with instantaneous relay
• Selectable ON-Delay/Interval Timing Mode version
• Output Contacts rated 10A 120/240 VAC and 30 VDC
• Six Timing Ranges in a single unit
• Timing Ranges:
• Universal Power Supply: 24-240 VAC and 24 VDC
• 48mm
• Large and easy to read dial shows decimal points
• Round (octal) socket mount or mount in panel cutout
• Watertight when panel mounted
• Range and Mode select are tamper proof when panel mounted
• Unique flashing cycle progress indication
2
1 and 10 SEC, MIN, and hours
5 and 50 SEC, MIN, and hours
DIN Standard housing
when panel mounted, these switches are not accessible to the operator. This tamper proof
The Mode select and Range select switches are located on the side of the unit, so that
selected, decimal points are clearly indicated.
The Dial on the 405A is extra large and is easy to read. When fractional ranges are
socket. With an optional mounting clip, the 405A can be panel mounted.
tight when panel mounted. The 405A is mounted in an 8-pin round (octal)
1/16 DIN Housing: The 48mm
replacement units.
Instantaneous & Delayed: A version of the 405A is available with one set
of SPDT instantaneous contacts and one set of SPDT delayed contacts. The
VDC power, greatly simplifying ordering and inventory management of
instantaneous contacts transfer as soon as the timer is powered. The
Universal Power: All 405A timers can be powered using 24-240 VAC or 24
delayed contacts transfer at time out. This contact arrangement can be
used to replace many conventional timers.
power is applied and release at time out.
On Delay/Interval Timing Mode Version: A version of the 405A is avail-
transfer at time out. When in the Interval mode, the contacts transfer when
able with selectable ON-delay or Interval timing modes. This version has a
set of DPDT output contacts. When in the ON-delay mode, the contacts
feature prevents unauthorized or hazardous changes to the timing
mode and range from being made.
Cycle Progress Indication: The 405A LED indicator provides a
unique and effective method of cycle progress indication. Off
before timing, the LED blinks at an ever increasing rate as the
cycle progresses: once every 3-1/2 seconds during the first 10% of
the cycle, twice during the second 10%, and so on. At time out,
the LED pulses at a high rate. (In the 1, 5, 10 and 50 second
ranges, the LED is OFF before timing, steady ON during timing,
and pulsing ON after time-out).
Timing begins when the start switch is closed. This starts an oscil-
lator which runs at a frequency determined by the time setting. A
fixed number of counts from the oscillator determines the end of
the timing cycle. The time required to accomplish this depends
upon the oscillator frequency. During timing, an LED located on
the dial face blinks. For the first 10% of the cycle, LED repeatedly
blinks once followed by a pause. For the second 10%, it blinks
twice and so on indicating the cycle progress. The LED flashes
rapidly and continuously after time out.
MODEL...F1X
The instantaneous contacts (3-1-4) transfer immediately after the
start switch is closed. The delayed contacts (6-8-5) transfer after
the timing cycle indicated on the front dial setting. Both contacts
remain transferred until the unit is reset.
MODEL...F2X
ON DELAY MODE: At time out, the DPDT relay transfers its
contacts. These contacts remain transferred until the start switch
is opened or power is removed by some other means. The 405A
then resets and is ready for another cycle.
INTERVAL MODE: When the start switch is closed, the DPDT relay
transfers its contacts. The contacts remain transferred until time
out. The timer will not start again until the start switch is opened
or power is removed by some other means. The 405A then resets
and is ready for another cycle.
\\\
OPERATIONS
2
(1/16 DIN) housing is compact and is water-

Related parts for 405A100F1X