1180-01-10A E-T-A Circuit Protection and Control, 1180-01-10A Datasheet - Page 3

no-image

1180-01-10A

Manufacturer Part Number
1180-01-10A
Description
Circuit Breaker; Therm; Push; Cur-Rtg 10A; Plug-In; 1 Pole; Vol-Rtg 250/65VAC/VDC
Manufacturer
E-T-A Circuit Protection and Control
Type
Thermalr
Datasheet

Specifications of 1180-01-10A

Actuator Type
Push
Application
For protection of loads in power distribution systems in control cabinets and process control
Brand/series
1180 Series
Current, Rating
10 A
Dielectric Strength
3000
Dimensions
0.961"Lx0.323"Wx1.92"H
Mounting Type
Plug-In
Number Of Poles
1
Resistance, Insulation
100 Megohms (Min.) @ 500 VDC
Standards
CBE Standard EN⁄IEC 60934, VDE Approved, UL Listed
Temperature, Operating, Maximum
60 °C
Temperature, Operating, Minimum
-20 °C
Termination
Blade
Voltage, Rating
250/65 VAC/VDC
Lead Free Status / Rohs Status
RoHS Compliant part
1
1 - 42
Dimensions
Internal connection diagram
Shock directions
14.5
.571
16.6
.654
18.2
.717
19,8
.780
24.4
.961
1
.205
Thermal Overcurrent Circuit Breaker 1180-...
5.2
2
slot for fitting labels
(see accessory 1)
3
1
2
current rating
5
6
4
label
Y 307 374 01
.043
.122
1.1
3.1
.024
0.6
.142
3.6
Note: When several devices are mounted together, each device should
only carry 80 % of its rating or it must be overrated accordingly.
This is a metric design and millimeter dimensions take precedence ( mm )
Typical time/current characteristics at +23 °C7+73.4 °F
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also
section 9 – Technical information.
Ambient temperature °F
Derating factor
10000
1000
100
0.1
10
1
1
°C
2
… times rated current
-22 -4
-30 -20
0.8 0.76 0.84 0.92 1
4
6
8 10
+14 +32 +73.4 +104 +122 +140
-10
0
20
+23
40
inch
+40 +50
1.08 1.16 1.24
0.1 - 5 A
6 - 10 A
+60