S8VS-03012 Omron Automation, S8VS-03012 Datasheet - Page 4

no-image

S8VS-03012

Manufacturer Part Number
S8VS-03012
Description
Power Supply; 100 to 240 VAC; 50/60 Hz (47 to 450 Hz); 22.5 mm
Manufacturer
Omron Automation
Datasheet

Specifications of S8VS-03012

Brand/series
S8VS Series
Configuration
Enclosed
Current, Inrush
25 A (Max.) (For a Cold Start @ +25 °C)
Current, Rating
0.9 A (Max.) 100 V Input, 0.6 A (Max.) 200 V Input
Frequency
50⁄60 Hz (47 to 450 Hz)
Mounting Type
DIN Rail
Number Of Outputs
1
Operation
Switching
Output
12 VDC @ 2.5 A
Power, Output
30 W
Primary Type
AC-DC
Voltage, Input
100 to 240 VAC
Voltage, Output
12 VDC
Voltage, Rating
100 to 240 VAC
Width
22.5 mm
Lead Free Status / Rohs Status
RoHS Compliant part
Specifications
Ratings/Characteristics
*1. Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
*2. Refer to Engineering Data (15-W, 30-W Models) on page 12 for details.
*3. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting
*4. The overvoltage protection of the S8VS-015 @@ uses a zener diode clamp. If the internal feedback circuit is destroyed by any chance, the load
*5. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
Item
Efficiency (typical)
Input
Output
Additional
functions
Other
temperature of the Power Supply may result in ignition or burning.
the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged.
may be destroyed by the clamped output voltage (approx. 140% to 190% of the rated output voltage).
Voltage *1
Frequency *1
Current
Power factor
Harmonic current emissions
Leakage current
Inrush current *2
Voltage adjustment range *3
Ripple
Input variation influence
Load variation influence
(rated input voltage)
Temperature variation influence
Startup time *2
Hold time *2
Overload protection *2
Overvoltage protection *2
Output voltage indication
Output current indication
Peak-hold current indication
Maintenance forecast monitor indication
Maintenance forecast monitor output
Total run time monitor indication
Total run time monitor output
Undervoltage alarm indication
Undervoltage alarm output
Parallel operation
Series operation
Operating ambient temperature
Storage temperature
Operating ambient humidity
Dielectric strength
Insulation resistance
Vibration resistance
Shock resistance
Output indicator
EMI
EMS
Approved standards
SEMI
Weight
5-V models
12-V models
24-V models
100-V input
200-V input
100-V input
200-V input
100-V input
200-V input
Conducted
Emissions
Radiated
Emissions
Power ratings
Type
72% min.
74% min.
77% min.
100 to 240 VAC (85 to 264 VAC)
50/60 Hz (47 to 450 Hz)
0.45 A max.
0.25 A max.
---
Conforms to EN61000-3-2
0.5 mA max.
1.0 mA max.
25 A max. (for a cold start at 25°C)
50 A max. (for a cold start at 25°C)
−10% to 15% (with V.ADJ)
2.0% (p-p) max. (at rated input/output voltage)
0.5% max. (at 85- to 264-VAC input, 100% load)
2.0% max. (5 V), 1.5% max. (12 V, 24 V), (with rated input, 0 to 100% load)
0.05%/°C max.
100 ms max. (at rated input/output voltage)
20 ms min. (at rated input/output voltage)
105% to 160% of rated load current, voltage drop, automatic
reset
Yes (a zener diode clamp) *4
No
No
No
No
No
No
No
Yes (color: red)
No
No
Models with 24-V output: Possible for up to 2 Power Supplies (with external diode)
Models with 5- or 12-V output: Not possible
Refer to the derating curve in Engineering Data (15-W, 30-W Models). (with no icing or condensation)
−25 to 65°C
25% to 85% (Storage humidity: 25% to 90%)
3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA)
2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA)
1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA)
100 MΩ min. (between all outputs and all inputs/ PE terminals) at 500 VDC
10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions
150 m/s
Yes (color: green)
Conforms to EN61204-3 EN55011 Class B and based on FCC Class A
Conforms to EN61204-3 EN55011 Class B
Conforms to EN61204-3 high severity levels
UL: UL508 (Listing; Class 2: Per UL1310), UL60950-1, UL1604 (Class I/Division2)
cUL: CSA C22.2 No.14 (Class 2), No.60950-1, No.213 (Class I/Division2)
EN/VDE: EN50178 (=VDE0160), EN60950-1 (SELV) (=VDE0805 Teil 1)
According to VDE0106/P100, IP20 (except terminal block)
F47-0200 (200-VAC input)
160 g max.
2
, 3 times each in ±X, ±Y, and ±Z directions
Standard
15 W
70% min.
76% min.
80% min.
0.9 A max.
0.6 A max.
1,000 ms max. (at rated input/output voltage)
105% to 160% of rated load current, voltage drop, intermittent
operation, automatic reset
Yes *5
180 g max.
Standard
30 W
S8VS
4

Related parts for S8VS-03012