E5ANR3HMT500NAC100240 Omron Automation, E5ANR3HMT500NAC100240 Datasheet
E5ANR3HMT500NAC100240
Specifications of E5ANR3HMT500NAC100240
Related parts for E5ANR3HMT500NAC100240
E5ANR3HMT500NAC100240 Summary of contents
Page 1
Basic-type Digital Temperature Controller E5AN/E5EN New 96 x 96-mm and 48 x 96-mm Basic Temperature Controllers with Enhanced Functions and Performance. Improved Indication Accuracy and Preventive Maintenance Function. • Indication Accuracy Thermocouple input: ±0. (previous models: ±0.5%) Pt ...
Page 2
E5AN/E5EN Lineup E5AN/E5EN Terminal block Basic Type Note: Models with one control output or two control outputs can be used for heating/cooling control. Model Number Structure Model Number Legend Controllers E5AN/E5EN-@3@M@@-@-500 Control ...
Page 3
Ordering Information E5AN Controllers with Terminal Blocks Power Case Size supply Input type color voltage Thermocouple or Resistance thermometer 100 to 240 VAC Black 1/4 DIN 96 × 96 × 78 Analog (W × H × D) (current/voltage) Thermocouple 24 ...
Page 4
E5AN/E5EN E5EN Controllers with Terminal Blocks Power Case Size supply Input type color voltage Thermocouple or Resistance thermometer 100 to 240 VAC Black 1/8 DIN 48 × 96 × × H × D) Analog (current/volt- age) Thermocouple 24 ...
Page 5
Option Units Name Communications Unit Event Input Unit Accessories (Order Separately) USB-Serial Conversion Cable Model E58-CIFQ1 Terminal Cover Connectable models Model E5AN E53-COV16 E5EN Note: The Terminal Cover comes with the E5CN-@@@-500 models. Waterproof Packing Connectable models Model E5AN Y92S-P4 ...
Page 6
E5AN/E5EN Specifications Ratings model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power 100 to ...
Page 7
Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Input Platinum resistance type thermometer Name Pt100 JPt100 K J 2300 1800 1700 1600 1500 1400 1300 1300 1200 1100 1000 850 850 900 800 700 600 500.0 500.0 500.0 500 400 300 ...
Page 8
E5AN/E5EN Alarm Outputs Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit. Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also ...
Page 9
Characteristics Thermocouple: (±0.3% of indicated value or ±1°C, whichever is greater) ±1 digit max. ✽1 Platinum resistance thermometer: (±0.2% of indicated value or ±0.8°C, whichever is greater) ±1 digit max. Indication accuracy Analog input: ±0.2% FS ±1 digit max. CT ...
Page 10
E5AN/E5EN USB-Serial Conversion Cable Applicable OS Windows 2000, XP, or Vista Thermo Mini, CX-Thermo version Applicable software 4.0 or higher E5AN/E5EN/E5CN/E5CN-U/E5AN- Applicable models H/E5EN-H/E5CN-H USB interface standard Conforms to USB Specification 1.1. DTE speed 38400 bps Computer: USB (type A ...
Page 11
External Connections • A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect any of the control output terminals to ground. If the control output ...
Page 12
E5AN/E5EN Nomenclature E5AN Temperature unit SUB1 SUB2 SUB3 Operation indicators HA OUT1 STOP OUT2 CMW MANU Programmable PF Function Key/ A/M Auto/Manual Key E5AN Level Key Mode Key ✽ A 2-level display when shipped from the factory. A 3-level display ...
Page 13
E5EN 48 112 96 Waterproof Packing (Accessory) Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ1 USB connector (type A plug) Terminal Covers E53-COV16 (Six Covers provided 120 min. Terminal Cover Mounting Bracket (E53-COV16) (Accessory) (Accessory) Crimp terminal ...
Page 14
E5AN/E5EN Waterproof Packing Y92S-P4 (for DIN 96 × 96) Y92S-P5 (for DIN 48 × 96) Current Transformers E54-CT1 E54-CT3 30 40 × E54-CT3 Accessory • Armature Connection Example Plug Approx. 3 dia. 18 • ...