FP0-A21-A Panasonic Electric Works, FP0-A21-A Datasheet - Page 14

no-image

FP0-A21-A

Manufacturer Part Number
FP0-A21-A
Description
Programmable Controller, Analog Input/Output Unit; Analog Input; 1 Channel; LED
Manufacturer
Panasonic Electric Works
Type
PLCr
Datasheet

Specifications of FP0-A21-A

Brand/series
FP0 Series
Current, Input
20 mA
Dimensions
25mmW×90mmH×60mmD
Display Type
LED
Input Type
Analog Input
Max. Number Of Expansion I/o Points
300 Points
Max. Number Of Expansion Modules
3
Memory Type
Flash ROM Built-In (Program Memory) No Battery Backup Required
Number Of Inputs
2
Number Of Outputs
1
Primary Type
Controller
Programmable With
FP0 Adapter
Standards
Conforming to EN61131-2
Terminal Type
Screw
Termination
Screw
Voltage, Supply
24 VDC
Lead Free Status / Rohs Status
RoHS Compliant part
Analogue Signal Processing
FP0 Analogue Units
14
Features
The analogue units can be used with the FP0 and FP
scale machines to factory production systems.
Each CPU supports up to 3 FP0 analogue units. Combination with digital and analogue expansion units is freely allowed.
Highest performance is offered with 12-bit resolution. With a current and voltage output conversion time of up to
500µs, the units are capable of high-speed processing.
The multimode FP0 analogue unit can be configured via the DIP switches on the front side into the required analogue
ranges. Communication with the FP0 CPU unit is achieved via the expansion bus. The expansion bus is automatically
connected after the FP0 analogue unit is connected to the FP0 CPU unit.
Note: Function Blocks for FPWIN Pro Programming System can be downloaded free of charge from our WEB-page.
Multimode A/D, D/A conversion
Voltage, current and temperature selectable
2 analogue inputs (FP0-A21):
-10 to + 10V, 0 to 5V, 0 to 20mA,
8 analogue inputs (FP0-A80):
-10 to + 10V, 0 to 5V, -100 to + 100mV, 0 to 20mA
1 analogue output (FP0-A21): -10 to + 10V, 0 to 20mA
4 analogue outputs (FP0-A04V): -10 to + 10V
4 analogue outputs (FP0-A04I): 4 to 20mA
FP0-A21
2 Inputs/1 Output
FP0-A80
8 Inputs
10/2004
(Sigma) so wide range applications are possible from small-
FP0-A04V
4 Outputs
High resolution: 12-bit
High conversion speed
PID instruction with auto tuning
Screw terminal connection
FP0-A04V, FP0-A04I: 500µs
FP0-A04I
4 Outputs

Related parts for FP0-A21-A