C25BNB240T Eaton / Control Automation, C25BNB240T Datasheet - Page 4

no-image

C25BNB240T

Manufacturer Part Number
C25BNB240T
Description
CONTACTOR; DP; 2 POLE; 40A; 24VAC COIL
Manufacturer
Eaton / Control Automation
Datasheet

Specifications of C25BNB240T

Coil Voltage
24
Current, Rating, Inductive
40
Current, Rating, Resistive
50
Horsepower, Motor, Max At 115 V
3
Horsepower, Motor, Max At 230 V
7.5
Number Of Poles
Double-Pole
Temperature, Operating, Maximum
+70 °C
Temperature, Operating, Minimum
–25 °C
Insulation Voltage
690 V
Contacts
Double Break
Magnet Coil
Class F, 155°C
Operating Temperature Range
–13 to 158°F (–25 to +70°C)
Terminal Wire Range — Hex Washer Head Screws
16-10 AWG, 30 Lb.-In. Torque Rating
Mounting Position
Vertical, Horizontal or Tabletop
4
Product Description
Cutler-Hammer
Purpose Contactors 15A through 360A,
from Eaton’s electrical business incor-
porate most competitive contactor
mounting dimensions into a single
baseplate. Contactors are dual-rated
with inductive and resistive ratings as
well as horsepower and kilowatt rat-
ings. C25 contactors are furnished with
pressure plates and quick connect ter-
minals as standard on 15, 25 and 30A
devices and with box lugs and quick-
connect terminals on 40, 50, 60 and
75A. Other terminal configurations are
available, see Table 14. Contactors will
accept add-on auxiliary contacts —
order factory assembled or as kits for
field installation.
The separately available snap-on
mechanical interlock permits interlock-
ing two contactors for reversing or
two-speed applications.
Contactors rated 15 – 50A only are
available with DIN rail mount as a fac-
tory installed option.
Standards and Certifications
Technical Data and
Specifications
UL Recognized Components
UL File #E-1491, Guide NLDX2
CSA Certified Components
File #LR353, Class 3211 04, 481301
& 122201
IEC 60947-4-1
EN 60947-4-1
RoHS Compliance (15A to 50A Only)
Magnet coil:
Definite Purpose Control
Contactors
15 – 360A, 2-, 3- and 4-Pole — C25
Class B (C25E, F, G, H and K),
130°C
Class F (C25D and L), 155°C
Class H (C25D), 180°C (Available
as factory installed option)
50 mm DP Contactor
®
Type C25 Definite
Table 8. IEC/CE Ratings (IEC 60947-4-1, EN 60947-4-1) for 15A through 50A C25D_Contactors
Table 9. DC Ratings (15A to 50A Only)
Table 10. Contactor Torque Ratings
C25D_
Inductive
Rating
15A
25A
30A
40A
50A
Voltage
240V DC 3 Poles in Series —
120V DC 3 Poles in Series —
120V DC 2 Poles in Series 5.5
120V DC per Pole
24V DC per Pole
Contactor Size
120A
200 – 300A
360A
15 – 50A
60 – 75A
90A
For more information visit: www.eaton.com
The box lugs on the 15 – 50A device can accept 2 conductors per pole, the upper section will
accept 4 – 14 AWG and the lower section will accept 6 – 14 AWG.
The box lugs on the 60 – 75A device can accept 2 conductors per pole, the upper section will
accept 3 – 14 AWG and the lower section will accept 6 – 14 AWG.
Contacts: Double break
Coil terminals: 10 – 14 AWG
Ambient temperature: 150°F (65°C)
maximum
UL recognized, CSA certified and
conform to ARI 780
CE mark
Terminal wire range:
#8–32 binding head screw:
14 – 12 AWG (one conductor-
solid)
#8–32 screw/pressure plate:
– 14 – 8 AWG (one conductor)
– 14 – 8 AWG (two conductors)
Box lugs — 15 – 50A:
– # 2 posidrive screw or 5/32 hex
– Upper Level: 14 – 4 AWG (one
– Lower Level: 14 – 6 AWG (one
socket screw
conductor)
conductor)
AC-1 (Ic)
480V
20A
30A
40A
50A
65A
Terminal
8–32 Binding Head Screw
Screw/Pressure Plate
Box Lug
Box Lug
Box Lug
Box Lug
Box Lug
Box Lug
2-Pole,
15 – 30A Inductive
UL/
CSA
FLA hp
2
15
600V
20A
30A
40A
65A
1/2
1/10
AC-3 (Ie)
480V
15A
25A
30A
40A
50A
DC-3/
DC-5
I e
5.5
2
15
2-Pole,
40A Inductive
UL/
CSA
FLA hp I e
8
3.5
20
600V
15A
25A
30A
50A
3/4 8
1/4 3.5
Table 7. Lighting Duty Ratings
(25A to 50A Only)
C25D_
Inductive Rating
25A
30A
40A
50A
Wire Range
12 – 14 AWG
12 – 14 AWG
10 AWG
10 – 14 AWG
1/0 – 14 AWG
8 – 14 AWG
8 AWG
4 – 6 AWG
8 AWG
3 – 6 AWG
8 AWG
4 – 6 AWG
3 – 1/0 AWG
6 – 350 MCM
2 – 750 MCM
DC-3/
DC-5
20
Box lugs — 60 – 75A
– Upper Level: 14 – 2 AWG
– Lower Level: 14 – 6 AWG
Note: The box lugs on the 15 – 75A
device can accept two conductors per
pole.
Box lugs — 90A: 1/0 – 14 AWG
Box lugs — 120A: 3/0 – 8 AWG
Box lugs — 200 – 300A: 350
MCM – 6 AWG
Box lugs — 360A: 750 MCM – 2 AWG
AC-4 (Ie)
480V
15A
25A
30A
40A
50A
3-Pole,
15 – 30A Inductive
UL/
CSA
FLA hp
4
8
5.5
2
15
3/4
3/4
1/2
1/10
600V
DC-3/
DC-5
I e
4
8
5.5
2
15
Tungsten
& Ballast (480V)
30A
40A
50A
60A
Tightening Torque
200 lb-in
550 lb-in
22 lb-in
15 lb-in
15 lb-in
25 lb-in
40 lb-in
45 lb-in
40 lb-in
45 lb-in
50 lb-in
60 lb-in
40 lb-in
45 lb-in
50 lb-in
AC-8a
480V
15A
25A
30A
40A
50A
3-Pole,
40A Inductive
UL/
CSA
FLA hp I e
5
10
8
3.5
20
PG03502001E
1
1
3/4 8
1/4 3.5
600V
15A
25A
30A
50A
May 2007
DC-3/
DC-5
5
10
20

Related parts for C25BNB240T