OPTOEMU-SNR-3V OPTO 22, OPTOEMU-SNR-3V Datasheet - Page 2

no-image

OPTOEMU-SNR-3V

Manufacturer Part Number
OPTOEMU-SNR-3V
Description
Energy Monitoring Unit 120/240 VAC (5060 Hz) 32 MB memory
Manufacturer
OPTO 22
Type
Energyr
Datasheets

Specifications of OPTOEMU-SNR-3V

Features
Features:Monitor Real-time Energy Usage from Utility Meters, Electrical Panels, Subpanels and DevicesView Detailed Real-time and Historical Data Online Through Your Chosen Software ServiceCommunicate over Standard 10/100 Mbps Ethernet or Wireless LAN or Both at onceSturdy Metal Enclosure with Standard KnockoutsReal-Time Clock0 to 60°C Operating Temperature
Function
Energy Monitoring
Mounting Type
Directly to Panel
Sensing Mode
Current Transformers
Technology
Pulse and Direct Sensing
Voltage, Supply
120 or 240 VAC
Accuracy
0.2 %
External Width
15.2cm
External Depth
11.4cm
Input Voltage Max
400VAC
External Height
34.3cm
No. Of Channels
8
Accuracy %
0.2%
Lead Free Status / Rohs Status
RoHS Compliant part
PAGE
2
Configuration
The Sensor includes an easy-to-use utility program for
assigning an IP address for communication on your network,
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590-3614 • www.opto22.com
SALES 800-321-6786 • 951-695-3000 • FAX 951-695-3095 • sales@opto22.com • SUPPORT 800-835-6786 • 951-695-3080 • FAX 951-695-3017 • support@opto22.com
© 2010–2011 Opto 22. All rights reserved. Dimensions and specifications are subject to change. Brand or product names used herein are trademarks or registered trademarks of their respective companies or organizations.
Connecting directly to a panel
One Sensor can connect to one 3-phase electrical panel or
device or to three single-phase panels or devices. The
Sensor measures line-to-neutral voltage and is suitable for
up to 600 volt systems (346 VAC wye).
If you need a fusible disconnect or plan to power the
Sensor from the monitored panel, an auxiliary box
containing a transformer and fusible disconnect is
available.
Suitable, safe, easy-to-install CTs with a 0.333 VAC
secondary are available through Opto 22. See form #1938,
the
information.
0.333 VAC secondary, the Sensor can monitor voltage
and current directly from the main power load panel on
a building or facility. It can also monitor loads from
individual subpanels or electrical devices such as chillers,
boilers, compressors, elevators, and air handling units.
Split-Core Current Transformers Data
—Using suitable current transformers (CTs) with a
OptoEMU Sensor (Energy Monitoring Unit)
Sheet, for more
configuring the monitored devices, and entering the
necessary information to connect to the software service.
Communication
The OptoEMU Sensor uses standard computer networks and
protocols to send data to the online software service, which
displays energy use to authorized viewers over the Internet.
The OptoEMU Sensor communicates with these services over
a standard 10/100 Mbps Ethernet network or over an 802.11a,
b, or g wireless LAN (local area network). With two
Mounting and Wiring
If the OptoEMU Sensor is monitoring voltage and current
directly from a panel or device, it should be mounted right
next to it. Power for the unit is supplied by a standard 120 VAC
or 240 VAC wall outlet. If you need to power the Sensor from a
panel or device with higher voltage, also purchase the
auxiliary box with transformer and fusible disconnect.
WARNING: Follow all installation instructions in the OptoEMU
User’ s Guide to avoid serious or fatal injury or severe damage to
equipment. All electrical wiring to the unit must be done by a
licensed electrician.
independent Ethernet network
interfaces plus an independent wireless
interface, the unit gives you the
flexibility to monitor devices in hard-to-
reach areas and to set up networking
suited to your business.
Security on the wireless LAN includes
802.11i WPA2/AES, currently considered
the best wireless security, plus the older
WPA security standard for backwards
compatibility.
Data Storage
The OptoEMU Sensor can store data
internally. If communication with the
software service is lost, the unit stores
data until communication is restored.

Related parts for OPTOEMU-SNR-3V