G3NA-490B-UTU-DC5-24 Omron Automation, G3NA-490B-UTU-DC5-24 Datasheet - Page 10

no-image

G3NA-490B-UTU-DC5-24

Manufacturer Part Number
G3NA-490B-UTU-DC5-24
Description
RELAY; SSR; ZERO-SWITCHING; CUR-RTG 90A; CTRL-V 5-24DC; VOL-RTG 200-480AC; SCREW
Manufacturer
Omron Automation
Datasheet

Specifications of G3NA-490B-UTU-DC5-24

Current, Rating
90 A
Current, Surge
1000 A (60 Hz, 1 Cycle)
Dielectric Strength
4000 VAC @ 50 Hz⁄60 Hz for 1 Minute
Dimensions
58 mm L x 43 mm W x 28 mm H
Function
Zero-Switching
Impedance, Input
72 Kiloohms
Relay Type
Solid State
Standards
UL, CSA, CE, TUV
Temperature, Ambient, Maximum
80 °C
Temperature, Ambient, Minimum
-30 °C
Termination
Screw
Voltage, Control
24 VDC
Voltage, Rating
480 VAC
Lead Free Status / Rohs Status
RoHS Compliant part
2
Specifications
■ Ratings
Input (at an Ambient Temperature of 25°C)
Note: 1. The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 240 VAC,
Output
Note: 1. The load current varies depending on the ambient temperature. Refer to Load Current vs. Ambient Temperature under Engineering Data.
■ Characteristics
468
G3NA-6@@B
G3NA-610B
G3NA-625B
G3NA-650B
Operate time
Release time
Output ON voltage drop
Leakage current
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Weight
Specifications
Solid State Relay (600 VAC)
Model
2. Refer to Temperature Characteristics (for Must Operate Voltage and Must Release Voltage) in Engineering Data for further details.
2. When an OMRON Heat Sink (refer to Options) or a heat sink of the specified size is used.
Model
the input impedance is measured at 240 VAC).
Item
Solid State Relays (600 VAC Models)
400 to 600 VAC
5 to 24 VDC
100 to 240 VAC
Rated load voltage
Rated voltage
1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)
1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)
1.8 V (RMS) max.
10 mA max. (at 400 VAC)
20 mA max. (at 600 VAC)
100 MΩ min. (at 500 VDC)
4,000 VAC, 50/60 Hz for 1 min
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Destruction: 1,000 m/s
Operating:−30°C to 80°C (with no icing or condensation)
Storage: −30°C to 100°C (with no icing or condensation)
Operating: 45% to 85%
Approx. 120 g
G3NA-6
G3NA-610B-UTU
4 to 32 VDC
75 to 264 VAC
Operating voltage
360 to 660 VAC
Load voltage range
2
7 mA max.
72 kΩ±20%
G3NA-6
(See note 1.)
Impedance
0.5 to 10 A (at 40°C)
0.5 to 25 A (at 40°C)
0.5 to 50 A (at 40°C)
With heat sink
Applicable load
(See note 2.)
G3NA-625B-UTU
Load current (See note 1.)
4 VDC max.
75 VAC max.
Must operate voltage
0.5 to 4 A (at 40°C)
0.5 to 4 A (at 40°C)
0.5 to 6 A (at 40°C)
Without heat sink
Voltage level
1 VDC min.
20 VAC min.
G3NA-650B-UTU
150 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
Must release voltage
Inrush current

Related parts for G3NA-490B-UTU-DC5-24