5607018 Phoenix Contact, 5607018 Datasheet - Page 4

no-image

5607018

Manufacturer Part Number
5607018
Description
Din Rail mount control transformer, 100 VA output, single phase
Manufacturer
Phoenix Contact
Type
Controlr
Datasheet

Specifications of 5607018

Brand/series
CPT Series
Configuration
Encapsulated
Dimensions
3"W×4.21"H×3.46"D
Frequency
50/60 Hz
Mounting Type
DIN Rail
Phase
1
Phoenix Part Number
CPT-480-220/120-110/100
Power, Rating
100 VA
Standards
UL, CSA
Temperature, Operating
+55 °C
Termination
Screw Terminals
Voltage, Primary
220/230/240/440/460/480 VAC
Voltage, Secondary
110/115/120 VAC
Weight
5.37 lbs.
Lead Free Status / Rohs Status
RoHS Compliant part
4.
5.
Table 1
2439_en_A
CPT-480-220/120-110/50
CPT-480-220/120-110/100
CPT-480-220/120-110/150
CPT-480-220/120-110/250
CPT-480-220/120-110/500
Method A
Method B
Calculate the total inrush power, in VA, using one of the
two methods:
Using Table 1, select a control transformer with a pow-
er rating based on the following criteria:
a.
b.
If the nominal supply voltage does not fluctuate more
than 5%, refer to the 90% secondary voltage column in
Table 1 for the correct VA rating. If the supply voltage
varies upwards of 10%, the 95% secondary voltage
column should be used to size the transformer.
TotalInrush
Transformer
TotalInrush
With a continuous power rating that is equal to or
greater than the value in Step 2.
With a maximum inrush power equal to or greater
than the value obtained in Step 4.
Method B will result in a slightly larger trans-
former being selected.
Current standards require electromagnetic de-
vices to operate reliably at a minimum of 85%
of their rated voltage. However, contact life
may be affected with continuous start-ups at
that voltage level. Therefore, the minimum
85% secondary voltage in Table 1 is provided
only as a reference.
40% Power Factor
=
=
sealedpower
sealedpower
1300
2680
6300
270
655
Inrush power@40%
+
2
Power Factor
deviceinrush
+
deviceinrush
1010
2030
5035
210
520
1340
3305
160
370
700
2
Fuse Selection
Primary
The fuse protection listed below, in amps, is 300% of the
rated current of the transformer. Select the next higher fuse
rating if these numbers do not correspond to standard fuse
ratings.
Table 2
Secondary
The fuse protection listed below, in amps, is 125% of the
rated current of the transformer. Select the next higher fuse
rating if these numbers do not correspond to standard fuse
ratings.
Table 3
220
230
240
440
460
480
110
115
120
Secondary
Primary
Voltage
Voltage
Primary Fuse Recommendations
Secondary Fuse Recommendations
0.60
0.60
0.60
0.30
0.30
0.30
0.75
0.60
0.60
50
50
1.25
1.25
1.25
0.60
0.60
0.60
1.50
1.40
1.25
100
100
Control Panel Transformers
VA Rating
VA Rating
2.00
1.80
1.80
1.00
0.80
0.80
2.25
2.00
2.00
150
150
PHOENIX CONTACT
3.20
3.20
3.00
1.60
1.60
1.50
3.50
3.00
3.20
250
250
4.00
4.00
3.50
3.20
3.20
3.00
7.50
7.00
6.25
500
500
4