SMART 3000NET Tripp Lite, SMART 3000NET Datasheet - Page 3

no-image

SMART 3000NET

Manufacturer Part Number
SMART 3000NET
Description
UPS, 3000VA, OOutlets: 8 four 15-amp & four 20-amp
Manufacturer
Tripp Lite
Type
Home/Office, Networkr
Datasheets

Specifications of SMART 3000NET

Brand/series
SmartPro®
Capacity
3000 VA
Color
Gray
Communication
DB9, RS232
Dimensions
43.2cmH×22.9cmW×31.75cmD
Input Type
NEMA L5-30P
Length, Cord
8 ft.
Mounting Type
Rack/Tower
Operation
Line-Interactive
Output Type
(4) NEMA 5-15R, (4) NEMA 5-15/20R
Power, Rating
2400 W
Time, Backup
7 min.
Voltage, Input
120 V
Voltage, Output
120 VAC
Voltage, Supply
2400/3000 W/VA
Weight
40.4 kg
Power Rating
3000 VA
Output Voltage Rating
120 V
Number Of Outlets
10
Interface Port
DB9 / Contact Closure
Runtime (full Load)
7 min
Runtime (half Load)
23 min
Topology
Line Interactive
Tower / Rackmount
Tower
Lead Free Status / Rohs Status
RoHS Compliant part
Battery recharge
rate
VOLTAGE REGULATION
Voltage
regulation
description
Overvoltage
correction
Direct pass
through
Brownout
correction
Severe brownout
correction
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
SURGE / NOISE SUPPRESSION
AC surge
suppression
AC suppression
response time
EMI / RFI AC
noise
suppression
PHYSICAL
Shipping weight
(lbs)
Shipping weight
(kg)
Shipping
Dimensions
(HWD/in)
Shipping
Dimensions
(HWD/cm)
Unit weight (lbs)
Unit weight (kg)
Unit Dimensions
(HWD/in)
Unit Dimensions
(HWD/cm)
Material of
construction
Form factors
supported
Cooling method
Receptacle Color
ENVIRONMENTAL
2-4 hours to 90%
Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to maintain
usable, computer grade output without consuming battery power.
Input voltages between 127 and 140V AC are reduced by 10%
Input voltages between 110 and 127V AC are passed through unchanged
Input voltages between 95 and 105V AC are boosted by 12%
Input voltages between 87 and 94V AC are boosted by 22%
Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE
REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information
Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel
alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Includes 2 front panel switches — one on/standby power switch and one dual function "alarm cancel" / "self test" button,
plus 1 rear panel system enable switch
480 joules
Instantaneous
Yes
96
43.6
22.25 x 12.75 x 16.5
57.2 x 32.4 x 42
89
40.4
17 x 9 x 12.5
43.2 x 22.9 x 31.75
PVC
Tower
Fan
BLACK