TR-66126 Macromatic, TR-66126 Datasheet - Page 4

no-image

TR-66126

Manufacturer Part Number
TR-66126
Description
Relay; E-Mech; Timing; Delayed Interval; DPDT; Cur-Rtg 10A; Ctrl-V 12AC/DC; Socket Mnt
Manufacturer
Macromatic
Datasheet

Specifications of TR-66126

Contact Form
DPDT
Current, Rating
10 A
Function
Timing
Mounting Type
Socket
Number Of Pins
8
Power, Rating
2 VA
Relay Type
Electro Mechanical
Standards
cUL, UL, CSA, CE
Termination
Plug-In
Timer Type
Delayed Interval
Timing Range
0.6 to 2.5 sec., 1.5 to 5 sec., 2.5 to 10.5 sec., 5 to 21 sec., 10 to 42 sec., 0.4 to 1.4 min., 0.7 to 2.8 min., 1.5 to 5.5 min., 3 to 11 min., 5.5 to 22.5 min., 11 to 45 min., 0.4 to 1.5 hrs., 0.8 to 3 hrs., 1.5 to 6 hrs., 3 to 12 hrs., 6 to 24 hrs.
Voltage, Control
12 VAC⁄VDC
Voltage, Rating
240⁄28 VAC⁄VDC
Temperature
–28° to +65°C
Dimensions
1.7" × 2.4" × 3.5"
Lead Free Status / Rohs Status
RoHS Compliant part
Voltage Tolerance:
AC Operation:
DC Operation:
Load (Burden):
2 VA
Setting Accuracy:
Maximum Setting (Adjustable):
Minimum Setting (Adjustable):
Repeat Accuracy (constant voltage and temperature):
> 2 Seconds Delay
0.1 - 2 Seconds Delay
Reset Time:
On Delay/Interval/Repeat Cycle/Delayed Interval: 0.1 Seconds
Off Delay/Single Shot/Watchdog/
Triggered Delayed Interval: 0.04 Seconds
Start-up Time:
(Time from when power is applied until unit is timing)
120 & 240V units
12, 24 & 48V units
Maintain Function Time:
(Time unit continues to time after power is removed)
0.01 Seconds for all units
Temperature:
12-120V Input Voltage: -28
240V Input Voltage:
Dimensions
Revised: 6/08
Application Data
+10/-15% of nominal at 50/60 Hz.
+10/-15% of nominal.
0.05 Seconds
0.08 Seconds
-28
(60)
2.4
+0.1%
+2%
o
o
to 65
to 50
+5%, -0%
+0%, -50%
o
o
C (-18
C (-18
o
o
to 150
to 122
(43)
1.7
o
o
F)
F)
File #E109466
Insulation Voltage:
2,000 volts
Output Contacts:
DPDT 10A @ 240V AC/30V DC,
1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)
B300 & R300; AC15 & DC13
Life:
Mechanical: 10,000,000 operations
Full Load: 100,000 operations
Compatibility:
On all units triggered by input voltage or by a control switch, do
not use a solid state switch to initiate the timing sequence-
problems with leakage current could occur. On all units with a
power trigger, do not use a solid state switch with leakage
current exceeding 0.5ma. Contact Macromatic Controls for
additional information.
Triggering Off Delay, Single Shot or Watchdog Units:
Timing sequence must be initiated only after input voltage is
applied to unit. Minimum required trigger switch closure time is
0.1 seconds.
Approvals:
TIME DELAY RELAYS
Time Ranger
File #LR45565
(74)
2.9
Application Data & Dimensions
(89)
3.5
EN60947-1, EN60947-5-1
Multi-Range Plug-in
EMC Directives
Low Voltage &
TM
Programmable
Inches (Millimeters)
All Dimensions in
File #E109466
with
appropriate
socket
43