MKS2PI AC12 Omron Automation, MKS2PI AC12 Datasheet - Page 3

no-image

MKS2PI AC12

Manufacturer Part Number
MKS2PI AC12
Description
MKS RELAY
Manufacturer
Omron Automation
Datasheet

Specifications of MKS2PI AC12

Lead Free Status / Rohs Status
RoHS Compliant part
Specifications
■ Ratings
Coil Ratings
Note: 1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/−20% for AC rated current and
Contact Ratings
AC
DC
Load
Contact mechanism
Contact material
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching power
Rated voltage
2. Performance characteristic data are measured at a coil temperature of 23°C.
3. The maximum voltage is one that is applicable instantaneously to the Relay coil at 23°C and not continuously.
4. For DC-operated Relays with the LED indicator built-in, add an LED current of approx. 5 mA to the rated current.
±15% for DC coil resistance.
6 V
12 V
24 V
100 V
110 V
200 V
220 V
230 V
240 V
12 V
24 V
48 V
100 V
110 V
6 V
443 mA
221 mA
110 mA
26.6 mA
24.2 mA
13.3 mA
12.1 mA
10.0 mA
11.0 mA
224 mA
112 mA
55.8 mA
28.1 mA
13.5 mA
12.3 mA
50 Hz
Rated current
385 mA
193 mA
96.3 mA
23.1 mA
21.0 mA
11.6 mA
10.5 mA
11.5 mA
9.6 mA
60 Hz
NO
NC
NO
NC
Resistive load
(cosφ = 1)
Single
AgSnIn
10 A, 250 VAC
10A, 30 VDC
5 A, 250 VAC
5 A, 30 VDC
10 A
250 VAC, 250 VDC
10 A
2,500 VA/300 W
1,250 VA/150 W
3.1 Ω
13.7 Ω
48.4 Ω
760 Ω
932 Ω
3,160 Ω
3,550 Ω
4,250 Ω
4,480 Ω
26.7 Ω
107 Ω
430 Ω
1,710 Ω
7,390 Ω
8,960 Ω
Coil resistance
General-purpose Relays
80% max. of rated
voltage
Must operate
voltage
Inductive load
(cosφ = 0.4)
7 A, 250 VAC
30% min. of rated
voltage at 60 Hz
25% min. of rated
voltage at 50 Hz
15% min. of rated
voltage
Must release
voltage
MK-S New Model
110% of rated volt-
age
Max. voltage
Approx. 2.3 VA
at 60 Hz
Approx. 2.7 VA
at 50 Hz
Approx. 1.4 W
consumption
Power
3